What is Sweep Frequency Response Analysis Test ?

08/09/2024

What is Sweep Frequency Response Analysis Test ?

SFRA Test Definition

SFRA test of transformer is a method used to assess the condition of transformer windings by analyzing their frequency response to electrical inputs.

Purpose of SFRA testing

  • Assessing the mechanical integrity of windings: Detecting whether the windings are displacements, deforms or short circuits.

  • Monitoring the health of the transformer:Changes in the condition of the transformer windings can be tracked by comparing historical data.

  • Anticipate potential failures: Detect possible failures early so that preventive measures can be taken.

Principles of SFRA testing

  • Excitation signal:A wide-band sweep signal (usually from a few hundred Hertz to several megahertz) is applied to the transformer winding.

  • Response signal: The output signal of the winding is measured and its amplitude and phase response is recorded.

  • Data analysis: The state of the winding is analyzed by comparing the frequency response curves of the winding at different frequencies.

Test procedure

Preparation stage:

  • Disconnect the power supply to the transformer and ensure that it is fully discharged.

  • Connect the SFRA tester to the primary or secondary side of the transformer.

Excitation signal application:

  • A wide band sweep signal is applied to the winding using the tester.

  • Signals usually start at low frequencies and gradually increase to high frequencies.

Collection of response signal:

  • The tester will automatically record the output signal of the winding and obtain its amplitude and phase information.

  • Each winding is usually tested separately and at a different voltage tap position.

Data analysis:

  • The collected data is compared to raw or historical data.

  • Changes in the frequency response curve are analyzed to identify signs of winding deformation or displacement.

Data analysis index

  • Amplitude change:If the amplitude changes significantly at a particular frequency, it may indicate the presence of winding deformation or displacement.

  • Phase change:A sudden change in phase may also indicate a change in the winding structure.

  • Spectrogram: Anomalies can be identified by comparing spectrograms between different tests.

Matters needing attention

  • Test environment: Ensure that the test environment is dry and free of interference to obtain accurate test results.

  • Reference data: Benchmarking data is required for effective comparison.

  • Safety:All safety regulations should be observed during testing, especially when high voltage equipment is involved.

Example Data Sheet for SFRA Test Result

8a4705c0ff452024516e1564249bb665.jpeg

Conclusion

SFRA testing is a very effective tool that can help maintenance engineers assess the health of transformer windings, detect potential problems in time, and take appropriate measures to prevent major failures.

Wenzhou Rockwell Transformer Co., Ltd. It is a high - tech enterprise integrating R & D, production, sales, and service. It focuses on the manufacturing of power transformers and supporting equipment, and is committed to providing efficient, reliable, and energy - saving power transmission and distribution solutions for global customers. We can offer: •Distribution transformers and substations •Outdoor switchgears and breakers(recloser) •Switchgears and it’s components (GIS, RMU, VCB, SF6 CB) Market and Service: We always take customers as the orientation and provide customized services according to their requirements. Our products are exported to the Middle East, Africa, Northern Europe, South America, and many other countries and regions. Drive the future of electricity with technological innovation and become a leading global supplier of intelligent power equipment.

Fault Analysis and Treatment of Oil-Immersed Transformers
Fault Analysis and Treatment of Oil-Immersed Transformers
Oil Leakage at Welded JointsOil leakage at welded joints primarily stems from poor welding quality, such as incomplete or detached welds, and defects like pinholes and gas pores. Although oil-immersed transformers are initially coated with solder and paint during manufacturing, potentially masking these issues temporarily, the defects tend to surface during operation. Additionally, electromagnetic vibration can cause weld cracks, leading to oil leakage.To resolve such leaks, the first critical s
08/29/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Transformer Detection, Testing, Maintenance and Servicing
Transformer Detection, Testing, Maintenance and Servicing
Transformer testing, inspection, and maintenance are essential tasks to ensure normal operation and extend the service life of transformers. Below are some recommended steps:Visual Inspection: Regularly inspect the transformer's exterior, including the enclosure, cooling system, and oil tank. Ensure the enclosure is intact, free from corrosion, damage, or leakage.Insulation Resistance Testing: Use an insulation resistance tester to check the transformer's insulation system. Verify that the insul
Vziman
08/29/2025
Preventive Detection and Testing of Transformers
Preventive Detection and Testing of Transformers
I. DC Resistance Test of Transformer Primary and Secondary Windings:The DC resistance of transformer primary and secondary windings can be measured using the four-wire (Kelvin) method, which is based on principles related to accurate resistance measurement.In the four-wire method, two test leads are connected to both ends of the winding under test, while the other two leads are connected to adjacent winding terminals. An AC power source is then applied to the two leads connected to the adjacent
Rockwell
08/28/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!