• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Are PM Actuators Reliable? Compare Types & Benefits

Edwiin
Field: Power switch
China

The performance of circuit breaker operating mechanisms is decisive for reliable and safe power supply. While various mechanisms each have their advantages, the emergence of a new type does not completely replace traditional ones. For example, despite the rise of eco-friendly gas insulation, solid insulation ring main units still hold about 8% of the market, showing new technologies rarely fully displace existing solutions.

The permanent magnet actuator (PMA) consists of permanent magnets, a closing coil, and an opening coil. It eliminates mechanical linkages, tripping and latching mechanisms found in spring-operated mechanisms, resulting in a simple structure with very few parts. Only one primary moving component operates during switching, providing high reliability. It uses permanent magnets to maintain the breaker’s position, belonging to the category of electromagnetic actuation with permanent magnetic latching and electronic control. However, due to the high electromagnetic energy required for closing and opening, a large-capacity energy storage capacitor is typically needed.

ABB.jpg

PMA mechanisms are classified into different types, mainly single-stable and bi-stable, and single-coil or dual-coil configurations, with no clear superiority among them.

A bi-stable permanent magnet mechanism uses permanent magnets at both the closing and opening positions for latching. Closing and opening actions are achieved by energizing separate excitation coils to drive the moving iron core. Under the same conditions, the bi-stable type has a lower peak closing current. Smaller currents simplify control circuitry, enhance reliability, and reduce the risk of controller damage. Additionally, smaller capacitor capacity is required—typically a 100V/100,000μF electrolytic capacitor can support reclosing operations. However, the initial opening speed of a bi-stable PMA vacuum circuit breaker is lower than its average speed over full contact travel.

A single-stable permanent magnet mechanism uses a permanent magnet for closing position latching, while a spring maintains the open position. Closing is achieved by energizing the closing coil to drive the moving core, simultaneously storing energy in the opening spring. Opening is accomplished by releasing the stored energy in the spring.

Since the single-stable PMA relies on a spring for opening, its initial opening speed and average opening speed are superior to those of the bi-stable type, better matching the breaker’s opening counter-force characteristics. However, because energy must be stored in the opening spring during closing, the peak closing current is significantly higher than in a bi-stable mechanism under comparable conditions.

The AMVAC permanent magnet actuated vacuum circuit breaker has a maximum rated voltage of 27kV. The 15kV model supports a rated current up to 3000A, a short-circuit breaking current of 50kA, and a short-circuit making current of 130kA.

Why Hasn't It Been Widely Adopted?

1. Cost-Effectiveness (Value for Money)

PMA circuit breakers have fewer moving parts, a simpler structure, and electromagnetic force characteristics well-matched to vacuum interrupters. They offer mechanical endurance exceeding 100,000 operations—significantly higher than the 30,000 operations typical of spring mechanisms. This makes them ideal for frequent switching and high-operation-count applications. Their electronic control also facilitates automation. However, high-quality PMA breakers are significantly more expensive. As a result, they are primarily used in premium applications abroad, such as in petrochemical plants and offshore platforms, where maintenance-free operation, high reliability, and improved power continuity are critical.

2. Quality Concerns

PMA breakers demand extremely high-quality components, including capacitors, permanent magnets, electromagnets, and electronic circuits. Comparing low-end PMA breakers with standard spring mechanisms is unfair and misleading. Using inferior capacitors or other components compromises overall product quality. Unlike spring-operated mechanisms, which allow individual component replacement and repair, PMA mechanisms are difficult and costly to repair. This high replacement cost further hinders the widespread adoption of PMA circuit breakers.

Give a tip and encourage the author!

Recommended

HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Case Studies of Installation and Manufacturing Defects in 110kV HV Circuit Breaker Porcelain Insulators
1. SF6 gas leakage occurred in the ABB LTB 72 D1 72.5 kV circuit breaker.Inspection revealed gas leakage at the fixed contact and cover plate area. This was caused by improper or careless assembly, where the dual O-rings slipped and were misplaced, resulting in gas leakage over time.2. Manufacturing Defects on the Outer Surface of 110kV Circuit Breaker Porcelain InsulatorsAlthough high-voltage circuit breakers typically have their porcelain insulators protected with covering materials during tra
12/16/2025
Overview of Defect Diagnosis Methods for High-Voltage AC Circuit Breakers
1. What are the characteristic parameters of the coil current waveform in high-voltage circuit breaker operating mechanisms? How to extract these characteristic parameters from the original trip coil current signal?Answer: The characteristic parameters of the coil current waveform in high-voltage circuit breaker operating mechanisms may include the following: Steady-state peak current: The maximum steady-state current value in the electromagnet coil waveform, representing the position where the
12/16/2025
300MW+ Unit Generator Circuit Breaker Automatic Tripping: Causes, Phenomena & Handling Measures
Units with a capacity of 300MW and above are usually connected in a generator-transformer unit configuration and connected to the power system through the circuit breaker on the high-voltage side of the transformer. During the normal operation of the unit, the circuit breaker may trip automatically due to various reasons. Operators must make correct judgments and take timely measures to ensure the safe operation of the unit.1. Causes of Automatic Circuit Breaker Tripping Tripping due to relay pr
11/27/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.