Sequence Network

04/22/2025

Sequence Network

Definition

The sequence impedance network is defined as an equivalent balanced network for a balanced power system under a hypothetical operating condition, where only a single sequence component of voltage and current exists within the system. Symmetrical components play a crucial role in calculating unsymmetrical faults at various nodes of a power system network. Additionally, the positive sequence network is fundamental for load flow studies in power systems. 

Every power system comprises three sequence networks: the positive, negative, and zero sequence networks, each carrying distinct sequence currents. These sequence currents interact in specific ways to model different unbalanced fault scenarios. By calculating these sequence currents and voltages during a fault, the actual currents and voltages in the system can be accurately determined.

Characteristics of Sequence Networks

During the analysis of symmetrical faults, the positive sequence network takes precedence. It is identical to the sequence reactance or impedance network. The negative sequence network shares a similar structure with the positive sequence network; however, its impedance values have opposite signs compared to those of the positive sequence network. In the zero sequence network, the internal part is isolated from the fault point, and the current flow is solely driven by the voltage at the fault location.

Sequence Network for Fault Calculation

A fault in the power system disrupts its balanced operation, plunging it into an unbalanced state. This unbalanced condition can be represented by a combination of a balanced positive sequence set, a symmetrical negative sequence set, and a single - phase zero sequence set. When a fault occurs, it is conceptually equivalent to injecting these three sequence sets into the system simultaneously. The post - fault voltages and currents are then determined by the system's response to each of these component sets.

To analyze the system's response accurately, the three sequence components are indispensable. Assume that each sequence network can be replaced by a Thevenin's equivalent circuit between two key points. Through simplification, each sequence network can be reduced to a single - voltage source in series with a single impedance, as illustrated in the figure below. The sequence network is typically depicted as a box, where one terminal represents the fault point, and the other corresponds to the zero potential of the reference bus N.

image.png

In the positive sequence network, the Thevenin voltage is equivalent to the open - circuit voltage VF at point F. This voltage VF represents the pre - fault voltage of phase a at the fault location F, and is also denoted by Eg. In contrast, the Thevenin voltages in the negative and zero sequence networks are zero. This is because, within a balanced power system, the negative and zero sequence voltages at the fault point are inherently zero.

The current Ia flows from the power system into the fault. Consequently, its symmetrical components Ia0, Ia1, and Ia2 flow away from the fault point F. The symmetrical components of the voltage at the fault point can be expressed as follows:

image.png

Where Z0, Z1 and the Z2 are the total equivalent impedance of the zero, positive and negative sequence network up to the fault point.

Zhejiang Vziman Electric Group Co., Ltd. is a high-tech enterprise specializing in R&D, manufacturing, and service of power electrical equipment. Committed to innovation, quality, and customer satisfaction, it supplies smart solutions for global power sectors, covering grid construction, new energy, and industrial distribution. Core Business • Switchgear (GIS, circuit breakers, Recloser, Load break switch) • Distribution equipment (transformers, RMU, smart terminals) • Power automation systems • Engineering services (installation, maintenance, consulting) Technical Strength • Provincial R&D center, multiple patents • Modern production, ISO/GB/IEC/CE/UL certified • High capacity, large-scale delivery support Market & Vision Serves State Grid, Southern Grid, and global projects (Asia, Africa, Europe, etc.). Aims to lead in smart grids and new energy, promoting sustainable energy development.

Difference Between Short Circuit & Overload
Difference Between Short Circuit & Overload
One of the main differences between a short circuit and an overload is that a short circuit occurs due to a fault between conductors (line-to-line) or between a conductor and earth (line-to-ground), whereas an overload refers to a situation where equipment draws more current than its rated capacity from the power supply.Other key differences between the two are explained in the comparison chart below.The term "overload" typically refers to a condition in a circuit or connected device. A circuit
08/28/2025
Difference Between Leading and Lagging Power Factor
Difference Between Leading and Lagging Power Factor
Leading and lagging power factors are two key concepts related to the power factor in AC electrical systems. The main difference lies in the phase relationship between current and voltage: in a leading power factor, the current leads the voltage, whereas in a lagging power factor, the current lags behind the voltage. This behavior depends on the nature of the load in the circuit.What is Power Factor?Power factor is a crucial, dimensionless parameter in AC electrical systems, applicable to both s
08/26/2025
Difference Between Electromagnet and Permanent Magnet
Difference Between Electromagnet and Permanent Magnet
Electromagnets vs. Permanent Magnets: Understanding the Key DifferencesElectromagnets and permanent magnets are the two primary types of materials that exhibit magnetic properties. While both generate magnetic fields, they differ fundamentally in how these fields are produced.An electromagnet generates a magnetic field only when an electric current flows through it. In contrast, a permanent magnet inherently produces its own persistent magnetic field once it has been magnetized, without requirin
08/26/2025
Interpretation of the “Five Mandatory Surveys” for On - site Investigation in the Operation and Maintenance Specialty
Interpretation of the “Five Mandatory Surveys” for On - site Investigation in the Operation and Maintenance Specialty
The power outage and work scopes must be clearly inspectedCollaborate with the site survey leader to confirm the equipment to be maintained and the work area involved. Consider requirements such as the use of special vehicles and large machinery, and safe distances from adjacent energized equipment. Verify on-site whether the proposed power outage scope is sufficient to meet the operational needs.On-site safety measures must be clearly inspectedCollaborate with the site survey leader to verify s
Vziman
08/14/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!