HM4-24 Indoor SF6 gas insulated circuit-breakers
Drawings · ROCKWILL

HM4-24 Indoor SF6 gas insulated circuit-breakers

Indoor withdrawable SF6 circuit breaker for 24kV, rated current 630‑2500A, short‑circuit breaking current 25‑31.5kA. Withdrawable truck design with SF6 for arc extinction & insulation, suitable for 24kV indoor switchgear for easy maintenance.

Add us on Google
Updated2026.10
LanguageEnglish
FilePDF · 369.5 KB
SF6 circuit breaker OEMSF6 gas insulated circuit-breaker ChinaIndoor SF6 gas insulated circuit-breaker

Document description

This document introduces indoor withdrawable SF6 circuit breaker for 24kV, complying with IEC 62271‑100 and IEC 62271‑1:2017 international standards for high voltage switchgear.

It adopts modular withdrawable truck construction, using SF6 gas for arc extinction and insulation, fitted inside 24kV indoor switchgear. The datasheet covers multiple rated current and short‑circuit breaking ratings, including overall mounting dimensions, primary contact parameters, SF6 working pressure, partial discharge and lightning impulse withstand values.

The withdrawable design enables safe isolation, inspection and replacement on site, widely applied in industrial distribution, substation and renewable energy 24kV power systems.

Related Products

Frequently asked questions

It can work under relative humidity up to 95% (non‑condensing) for short term. Long‑term operation requires no condensation. Dew will corrode secondary circuits and outer insulators and accelerate equipment ageing.

Higher altitude reduces external air insulation, but the sealed SF6 tank inside the breaker is not affected by ambient atmospheric pressure. Only the external insulation of the switchgear cabinet needs insulation derating correction for high‑altitude application.

Site acceptance mainly includes SF6 gas moisture measurement, leak detection, contact resistance, power frequency withstand voltage and partial discharge test. Mechanical operation characteristic and interlock function also need verification. Energization is allowed only after all tests pass.

The phase‑to‑earth and phase‑phase clearance requirement for 24kV is larger than 12kV. Cubicle compartment layout, busbar insulators and air gaps must be calculated based on 24kV withstand specification. Reusing 12kV cabinet structure directly will lead to failure in dielectric test.

We supply the withdrawable breaker unit and primary contact assemblies. Full set of type test certificates, 2D/3D installation drawings and operation manual are available. We support technical consultation for 24kV switchgear integration and remote technical guidance on request.