11kV~550kV Live‑Tank SF6 Circuit Breaker Series features flexible configuration and reliable performance for harsh outdoor environments. The RHB outdoor live‑tank SF6 circuit breaker has passed KEMA type test and complies with IEC 62271‑1, IEC 62271‑100, covering rated voltage of 11kV~550kV rated current up to 5000A, 50/60Hz frequency, 3‑s rated short‑time withstand current of 20‑63kA, rated short‑circuit making current (peak) of 50‑158kA with operating sequence O‑0.3s‑CO‑3min‑CO.
Adopting hybrid self‑blast puffer arc quenching principle and oil‑free spring mechanism, it supports composite or porcelain insulators as options, widely used for circuit control and fault‑protection within transmission substations and power plants.