HM4- 12 Indoor SF6 gas insulated circuit-breakers
Drawings · ROCKWILL

HM4- 12 Indoor SF6 gas insulated circuit-breakers

Indoor withdrawable SF6 circuit‑breaker for 12kV, rated current 630‑3150A, short‑circuit breaking 31.5‑40kA. Forced‑air cooling radiator optional for high‑current rating, withdrawable truck‑type design for indoor switchgear cubicles.

Add us on Google
Updated2026.10
LanguageEnglish
FilePDF · 350.3 KB
SF6 circuit‑breaker Manufacturerwithdrawable SF6 circuit‑breaker SupplierSF6 gas insulated circuit-breakers

Document description

This document describes indoor withdrawable SF6 circuit‑breaker complying with IEC 62271‑100 and IEC 62271‑1 international standards for high‑voltage circuit‑breakers. It adopts modular withdrawable truck‑type construction, using SF6 gas for arc‑extinguishing and insulation.

Fixed‑contact dimension is upgraded corresponding to rated‑current level. For rated current ≥3150A, optional forced‑air‑cooling radiator enables operation up to 4000A. The datasheet covers overall installation dimensions, contact‑size parameters per current grade, gas‑pressure thresholds, partial‑discharge and lightning‑impulse withstand specifications.

It defines cubicle‑matching requirements, installation interface, SF6 gas management and thermal‑limit conditions, and clarifies application boundary for high‑current cooling accessories. It delivers full‑set technical reference for switchgear type‑selection, primary‑circuit design and site commissioning, widely used in indoor substation and industrial distribution switchgear.

Related Products

Frequently asked questions

Periodically verify fan rotation status and keep air‑duct free from dust and debris. If fan fails, 4000A operation is prohibited. Derating or alarm logic for fan failure shall be considered within switchgear control scheme.

Partial discharge acts as early warning signal for internal insulation defects; factory PD test is completed before delivery. Excessive PD during site acceptance test suggests possible foreign debris, moisture ingress or damaged insulation parts. Troubleshooting shall be performed before energization.

Higher rated‑current corresponds to larger fixed‑contact diameter and modified truck overall dimensions. Switchgear compartment, contact box and primary busbar interface must match breaker mechanical & contact dimensions. Fitting high‑current breaker into undersized cubicle causes mechanical interference and contact over‑heating.

Always keep breaker in open position before rack‑in /rack‑out. Confirm secondary aviation connector is properly engaged. Never force the truck if mechanical interlock blocks movement. Incomplete truck positioning leads to poor primary‑contact engagement and over‑heating during service.

We can supply the withdrawable breaker unit, optional forced-air cooling radiators and contact assemblies. Type test certificates, technical drawings and installation manuals are available. We also support technical consultation for switchgear integration and on-site technical guidance on request.