VD4-CS Indoor Withdrawable vacuum circuit breaker
Brochure · ROCKWILL

VD4-CS Indoor Withdrawable vacuum circuit breaker

Indoor withdrawable vacuum circuit‑breaker. Rated 36/38kV, 1250A, 31.5kA short‑time withstand current. Draw‑out modular design, synchronous switching, built‑in condition diagnosis, 30 000 mechanical operations.

Add us on Google
Updated2026.10
LanguageEnglish
FilePDF · 94.1 KB
vacuum circuit breakerIndoor vacuum circuit breaker
Download

Document description

This document describes indoor withdrawable vacuum circuit‑breaker complying with IEC 62271‑100 for high‑voltage AC circuit‑breakersIEC Websto.... It adopts draw‑out modular truck‑type construction for fast on‑site replacement. Synchronous switching delivers ultra‑low restrike and stable performance.

Built‑in diagnostic system enables real‑time condition monitoring. The low‑maintenance mechanism achieves 30 000 mechanical operations. Rated voltage 36/38kV, rated normal current 1250A, 31.5kA rated short‑time withstand / breaking capacity for 3 seconds, rated short‑circuit making capacity 94kAp.

Power‑frequency withstand voltage 85/95 kV, lightning impulse withstand voltage 185/195 kV for 50/60 Hz systems. Standard operating sequence O‑3 min‑CO‑15 s‑CO; opening time 39 ms, closing time 58 ms; opening time can extend by 1.5 T under synchronous‑switching mode. Customized solutions are available for indoor high‑voltage switchgear applications.

Related Products

Frequently asked questions

Customization covers secondary‑circuit interfaces, special operation sequences, truck dimension adaptation for different cubicles, control‑supply voltage and synchronous‑switching logic parameters. Switchgear and system operating conditions shall be provided at order stage.

No. 30 000 cycles is mechanical endurance for no‑load open‑close operations. Electrical service life depends on short‑circuit breaking counts & load magnitude. Short‑circuit interruptions cause contact wear inside vacuum interrupter and shall be assessed separately.

“T” denotes power‑system fundamental‑frequency cycle. Synchronous switching operates at specific voltage/current zero‑crossing phase point. Up to 1.5‑cycle delay for opening is normal to suppress switching over‑voltage and reduce restrike risk, not equipment failure.

The truck‑type module can be racked out from cubicle. It supports fast whole‑unit replacement during maintenance or failure without de‑energizing the complete switchgear bay, greatly cutting repair downtime for high‑continuity power‑supply requirements.