Key attributes

Brand ROCKWILL
Series RVB
Rated voltage 24-145kV
Rated frequency 50/60Hz
Operating Ambient Temperature −50 ~ +60℃
Description

The 24kV - 145kV Live tank Vacuum circuit breakers are advanced high - voltage electrical devices. Using vacuum as the arc - extinguishing and insulating medium, they leverage vacuum's superior insulation and rapid arc - quenching capabilities to instantly interrupt fault currents, preventing arc re - ignition and ensuring grid stability.

The live tank design encapsulates the vacuum interrupters within a metal tank filled with insulating gas, enhancing insulation, mechanical robustness, and environmental adaptability to withstand harsh weather and external impacts. Available in multiple voltage ratings, these breakers suit diverse high - voltage transmission and distribution scenarios, from urban power grids to industrial systems.

Equipped with precise operating mechanisms, they offer long mechanical life, swift and accurate operations, minimal maintenance, excellent short - circuit current interruption, and anti - aging performance, making them an ideal choice for reliable and safe high - voltage power transmission.

Rockwill Product Showcase Video

 

Main function introduction:

  • Wide Voltage Range: Covers 24kV - 145kV, suitable for various high - voltage power systems.

  • Vacuum Arc Extinction: Utilizes vacuum for rapid arc quenching and reliable insulation.

  • Live Tank Design: Encased in gas - filled metal tanks for enhanced mechanical strength and environmental resistance.

  • Efficient Interruption: Quickly cuts off fault currents to safeguard power grids.

  • Low Maintenance: Long - lasting mechanical operation with minimal upkeep requirements.

Technology parameters:

RVB-24

Item    Unit Specification
Rated voltage kV 24
Rated insulation voltage kV 24
Power frequency withstand kV/min 70 Dry / 60 Wet
Impulse withstand voltage kV peak 150
Rated frequency Hz 50/60
Rated normal current Amps 1250/1600/2000/2500/4000
Rated symmetrical breaking capacity kA rms 25/31.5
Rated short time withstand current (3s) kA rms 25/31.5
Rated making capacity kA peak 63/80
Operating sequence - O-0.3s-CO-180s-CO,O-0.3s-CO-15s-CO
Opening time ms 45±10
single capacitor bank breaking current A 400…800
back-to-back capacitor bank breaking current A 400…800
Arcing time ms 5-15
Total breaking time ms 50-60
Closing time ms 75±10
Weight kg 700/750
Operating temperature #1 ℃ -25…+40
Tropicalization - IEC:60068-2-30
Electromagnetic compatibility - IEC 62271-1 、IEC 61000-6-2、IEC 61000-6-4
Solar radiation W/m2 1000
Presence of pollution - IEC TS 60815-1
Creepage distance mm/kV 25#2
Ice coating mm 10
Wind speed m/s 34
Earth quake resistance g 0.6

RVB-36

Item Unit Specification
Rated voltage kV 36
Rated insulation voltage kV 36
Power frequency withstand kV/min 95 Dry / 80 wet
Impulse withstand voltage kV peak 200
Rated frequency Hz 50/60
Rated normal current Amps 1250/1600/2000/2500/4000
Rated symmetrical breaking capacity kA rms 25/31.5
Rated short time withstand current (3s) kA rms 25/31.5
Rated making capacity kA peak 63/80
Operating sequence - O-0.3s-CO-180s-CO,O-0.3s-CO-15s-CO
Opening time ms 45±10
single capacitor bank breaking current A 400…800
back-to-back capacitor bank breaking current A 400…800
Arcing time ms 5-15
Total breaking time ms 50-60
Closing time ms 75±10
Weight kg 850/900
Operating temperature #1 ℃ -25…+40
Tropicalization - IEC:60068-2-30
Electromagnetic compatibility - IEC 62271-1 、IEC 61000-6-2、IEC 61000-6-4
Solar radiation W/m2 1000
Presence of pollution - IEC TS 60815-1
Creepage distance mm/kV 25#2
Ice coating mm 10
Wind speed m/s 34
Earth quake resistance g 0.6

RVB-40.5

Item Unit Specification
Rated voltage kV 40.5
Rated insulation voltage kV 40.5
Power frequency withstand kV/min 118 Dry / 95 wet
Impulse withstand voltage kV peak 195
Rated frequency Hz 50/60
Rated normal current Amps 1250/1600/2000/2500/4000
Rated symmetrical breaking capacity kA rms 31.5
Rated short time withstand current (3s) kA rms 31.5
Rated making capacity kA peak 80
Operating sequence - O-0.3s-CO-180s-CO,O-0.3s-CO-15s-CO
Opening time ms 45±10
single capacitor bank breaking current A 400…800
back-to-back capacitor bank breaking current A 400…800
Arcing time ms 5-15
Total breaking time ms 50-60
Closing time ms 75±10
Weight kg 950
Operating temperature #1 ℃ -25…+40
Tropicalization - IEC:60068-2-30
Electromagnetic compatibility - IEC 62271-1 、IEC 61000-6-2、IEC 61000-6-4
Solar radiation W/m2 1000
Presence of pollution - IEC TS 60815-1
Creepage distance mm/kV 25#2
Ice coating mm 10
Wind speed m/s 34
Earth quake resistance g 0.6

RVB-52

Item Unit Specification
Rated voltage kV 52
Rated insulation voltage kV 52
Power frequency withstand kV/min 120 Dry / 95 wet
Impulse withstand voltage kV peak 250
Rated frequency Hz 50/60
Rated normal current Amps 1250/1600/2000/2500/4000
Rated symmetrical breaking capacity kA rms 40
Rated short time withstand current (3s) kA rms 40
Rated making capacity kA peak 100
Operating sequence - O-0.3s-CO-180s-CO,O-0.3s-CO-15s-CO
Opening time ms 45±10
single capacitor bank breaking current A 400…800
back-to-back capacitor bank breaking current A 400…800
Arcing time ms 5-15
Total breaking time ms 50-60
Closing time ms 75±10
Weight kg 1000
Operating temperature #1 ℃ -25…+40
Tropicalization - IEC:60068-2-30
Electromagnetic compatibility - IEC 62271-1 、IEC 61000-6-2、IEC 61000-6-4
Solar radiation W/m2 1000
Presence of pollution - IEC TS 60815-1
Creepage distance mm/kV 25#2
Ice coating mm 10
Wind speed m/s 34
Earth quake resistance g 0.6

RVB-72.5

Item Unit Specification
Rated Voltage (Ur) kV 72.5
Rated Frequency Hz 50 / 60
Rated Short-Circuit Breaking Current kA 31.5 / 40
Rated Short-Time Withstand Current (Duration) kA / s 31.5 / 40 (4s)
Rated Peak Withstand Current kA 80 / 100
1min Power-Frequency Withstand Voltage (to earth / between phases) kV 160
1min Power-Frequency Withstand Voltage (across open contacts) kV 185
Rated Lightning Impulse Withstand Voltage (to earth / between phases) kV 350
Rated Lightning Impulse Withstand Voltage (across open contacts) kV 400
Partial Discharge Level pC <10
Operating Ambient Temperature ℃ −50 ~ +60

RVB-145

Item Unit Specification
Rated Voltage (Ur) kV 145
Rated Frequency Hz 50 / 60
Rated Short-Circuit Breaking Current kA 31.5 / 40
Rated 3s Short-Time Withstand Current kA 31.5 / 40
Rated Peak Withstand Current kA 80 / 100
1min Power-Frequency Withstand Voltage (to earth / between phases) kV 275
1min Power-Frequency Withstand Voltage (across open contacts) kV 316
Rated Lightning Impulse Withstand Voltage (to earth / between phases) kV 650
Rated Lightning Impulse Withstand Voltage (across open contacts) kV 812
Partial Discharge Level pC <10
Operating Ambient Temperature ℃ −50 ~ +60

RVB Live Tank Vacuum Circuit Breakers Product Drawing

RVB-145

RVB-145 Product Drawing

40.5kV、72.5kV Live Tank Vacuum Circuit Breaker Factory Real‑life Photos

Low‑maintenance live tank vacuum circuit breaker supplier-24kV to 145kV

Service environment

Ambient temperature ‑30°C ~ +40°C
Altitude <1000m
Wind speed <34m/s
Daily temperature difference <25°C
Solar irradiance < 0.1W/cm²
Monthly average relative humidity <90%
Ice‑coating thickness <10mm
Seismic acceleration resistance Horizontal <0.2g, vertical <0.1g
Installation location Outdoor

Solutions - Vacuum circuit breaker

Case Studies - Vacuum circuit breaker

Documentation Resource Library Vacuum circuit breaker

Outdoor live tank SF6 circuit breaker
Restricted
Outdoor live tank SF6 circuit breaker Outdoor live tank SF6 circuit breaker
Catalogue
English
PDF
RVD-145 Dead tank vacuum circuit breaker
Restricted
RVD-145 Dead tank vacuum circuit breaker RVD-145 Dead tank vacuum circuit breaker
Catalogue
English
PDF
RVD-145  Dead tank vacuum circuit breaker
Public
RVD-145 Dead tank vacuum circuit breaker RVD-145 Dead tank vacuum circuit breaker
Brochure
English
RVD Dead tank SF6 Free/vacuum circuit breaker
Public
RVD Dead tank SF6 Free/vacuum circuit breaker RVD Dead tank SF6 Free/vacuum circuit breaker
Brochure
English
RVB Outdoor live tank vacuum circuit breaker
Restricted
RVB Outdoor live tank vacuum circuit breaker RVB Outdoor live tank vacuum circuit breaker
Catalogue
English
PDF
RVB Outdoor Live Tank Vacuum Circuit Breaker
Public
RVB Outdoor Live Tank Vacuum Circuit Breaker RVB Outdoor Live Tank Vacuum Circuit Breaker
Brochure
English
Rockwill Electric Group Profile
Public
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
RVB Type China Outdoor Vacuum Circuit Breaker
Restricted
RVB Type China Outdoor Vacuum Circuit Breaker RVB Type China Outdoor Vacuum Circuit Breaker
Operating Instruction
English
PDF
RVB(S) Outdoor Single Phase Vacuum Circuit Breaker
Restricted
RVB(S) Outdoor Single Phase Vacuum Circuit Breaker RVB(S) Outdoor Single Phase Vacuum Circuit Breaker
Operating Instruction
English
PDF

Frequently asked questions

ABB’s high-voltage live-tank vacuum breakers are reliable but costly with long lead times. Hitachi Energy is mature yet lacks local high-voltage track records and smart features. Schneider Electric excels in 40.5kV distribution but is limited in voltage range and extreme performance.

In contrast, Rockwill offers up to 363kV SF₆-free vacuum solutions with fast local service and spare parts delivery. Featuring robust mechanisms, full smart functions, and superior resistance to extreme cold, heavy salt fog, and short-circuit currents, our breakers ensure long maintenance-free service and lower LCC.

Yes. The product follows IEC tropicalization and EMC standards, all type test data meets IEC requirements, acceptable for global tender projects.

Vacuum interrupter has no need to replace arc-extinguishing medium. With stable mechanical structure and gas-filled live tank design, only simple routine inspection required during long-term operation.

   Yes. Customization available for enhanced anti-pollution, anti-corrosion or special altitude adaptation upon request.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear

Comments

Share your question or perspective
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register