This document describes indoor withdrawable vacuum circuit‑breaker complying with IEC 62271‑100 for high‑voltage AC circuit‑breakersIEC Websto.... It adopts draw‑out modular truck‑type construction for fast on‑site replacement. Synchronous switching delivers ultra‑low restrike and stable performance.
Built‑in diagnostic system enables real‑time condition monitoring. The low‑maintenance mechanism achieves 30 000 mechanical operations. Rated voltage 36/38kV, rated normal current 1250A, 31.5kA rated short‑time withstand / breaking capacity for 3 seconds, rated short‑circuit making capacity 94kAp.
Power‑frequency withstand voltage 85/95 kV, lightning impulse withstand voltage 185/195 kV for 50/60 Hz systems. Standard operating sequence O‑3 min‑CO‑15 s‑CO; opening time 39 ms, closing time 58 ms; opening time can extend by 1.5 T under synchronous‑switching mode. Customized solutions are available for indoor high‑voltage switchgear applications.