| Brand | Switchgear parts |
| Model NO. | RNN-24D Inflatable cabinet load switch |
| Rated voltage | 24kV |
| Rated normal current | 630A |
| Rated frequency | 50Hz |
| Series | RNN-24D |
The RNN-24 630A charging cabinet load switch is a core control component designed specifically for 24kV medium voltage distribution systems, with advantages such as easy installation, minimal maintenance, long lifespan, small size, affordable price, safety and reliability. This series of products will be shipped after passing the full inspection and comply with the relevant requirements of GB1984-89 and GB/T1984-2014 AC high-voltage circuit breakers.

Product Parameters
| Serial Number | Item | Unit | Parameter | Remark |
|---|---|---|---|---|
| 1 | Rated Voltage | kV | 24 | |
| 2 | Rated Frequency | Hz | 50 | |
| 3 | Rated Current | A | 630 | |
| 4 | Rated Short-time Withstand Current | kA/s | 20/4 | |
| 5 | Rated Peak Withstand Current | kA | 50/63 | |
| 6 | Rated Short-circuit Making Current | kA | 50/63 | |
| 7 | Rated Active Load Breaking Current | A | 630 | |
| 8 | Rated Line Closed-loop Breaking Current | A | 630 | |
| 9 | Rated No-load Transformer Breaking Current | A | 6.3 | |
| 10 | Rated Cable Charging Breaking Current | A | 10 | |
| 11 | Active Load Breaking Operation Times | times | 100 | |
| 12 | Power Frequency Withstand Voltage: Phase-to-Phase, Phase-to-Ground / Break | kV | 65/79 | In Insulating Gas such as SF6 or C4 |
| 13 | Lightning Impulse Withstand Voltage: Phase-to-Phase, Phase-to-Ground / Break | kV | 125/145 | In Insulating Gas such as SF6 or C4 |
| 14 | Mechanical Life | times | 5000 | |
| 15 | Main Circuit Resistance | μΩ | ≤35 | |
| 16 | Phase-to-phase Center Distance | mm | 150 |
Installation dimensions