| Brand | Switchgear parts |
| Model NO. | 24kV Inflatable cabinet circuit breaker switch |
| Rated voltage | 24kV |
| Rated normal current | 630A |
| Rated frequency | 50Hz |
| Series | RNV-B1 |
The RNV-B1-24 SF6 circuit breaker switch is mainly used in 24KV/630 SF6 gas filling cabinets. As the main component of the gas filling cabinet, it undertakes the main function and has the rated current and load current for opening and closing; Performance such as closing and breaking short-circuit currents.
This series of products will be shipped after passing the full inspection and comply with the relevant requirements of GB1984-89 and GB/T1984-2014 AC high-voltage circuit breakers.

Product Parameters
| Serial Number | Item | Unit | Parameter |
|---|---|---|---|
| 1 | Rated Frequency | kV | 24 |
| 2 | Rated Current | A | 630 |
| 3 | Rated Breaking Current / Thermal Stability Time | kA/s | 20/4 |
| 4 | Rated Peak Withstand Current | kA | 50/63 |
| 5 | Rated Short-circuit Making Current | kA | 50/63 |
| 6 | Short-circuit Making Times | times | 30 |
| 7 | Power Frequency Withstand Voltage: Phase-to-Ground | kV | 65 |
| 8 | Power Frequency Withstand Voltage: Break | kV | 79 |
| 9 | Lightning Impulse: Phase-to-Ground | kV | 125 |
| 10 | Lightning Impulse: Break | kV | 145 |
| 11 | Main Circuit Resistance | μΩ | ≤60 |
| 12 | Mechanical Life of Arc Extinguishing Chamber | times | 10000 |
| 13 | Mechanical Life of Isolation / Earthing Switch | times | 5000 |