| Muhimmiya | ROCKWILL |
| Model NO. | High - voltage pneumatic load break switch Gadon kisan kwaikwayo na tsakiyar hanyoyi |
| Rated Voltage | 12kV |
| Raitidu kọ̀ọ̀kan | 630A |
| Rated Frequency | 50/60Hz |
| Siri | FKN |
IEE-Business Product Overview
Na fadi - voltage pneumatic load break switches da kuma abubuwa masu shiga muhimman kan biyu - voltage wani wurin da ya gudanar da AC 12kV, 50Hz. Wannan load break switch yana da muhimmiyar tushen fasaha da inganci. Tsarin basic form of the operating mechanism shine manual spring - energy - storage type, ko zai iya samun electromagnetic spring operating mechanism. Daga baya na gasar da ba a canza arc - extinguishing tube ba, ana iya koyar da multiple times.
High - voltage load break switch yana iya kula, cikin da ka fara, da kuma kula load currents a wurin da aka faɗa, kuma yana da kyakkyawan kula short - circuit currents da kula short - circuit currents a lokacin da aka bayyana.
Load break switches zai iya samun earthing switches. Earthing switch yana da short - circuit making capacity da ta fi load break switch, da kuma dynamic da thermal stability capability, kuma yana da mechanical interlock mai kyau da load break switch, don haka ya ƙara misoperation daga tsari.
Muhimman Tushen
Idan FKN12 - 12 load break switch yana da high - voltage current - limiting fuse (da striker) don ƙoƙarin load break switch - fuse combination, yana yi overloading da short - circuit protection ga loads (kamar power transformers). Idan one or more phases of the fuse blow, three phases of the load break switch zai kula automatically.
High - voltage load break switch yana da kyakkyawa don installation a ring - main unit switch cabinets da sauran types of switch cabinets don receiving and distributing electrical energy.
Tushen Kirkiro
Nambar |
Suna |
Unit |
Yawan Yadda |
1 |
Rated Voltage |
KV |
12 |
2 |
Rated Frequency |
Hz |
50 |
3 |
Rated Current |
A |
630 |
4 |
Maximum Rated Current of Fuse |
A |
100 |
5 |
Rated Active Load Breaking Current, Rated Closed - loop Breaking Current |
A |
630 |
6 |
Rated Short - time Withstand Current (2S) |
KA |
20 |
7 |
Rated Short - circuit Making Current, Rated Peak Withstand Current |
KA |
50 |
8 |
1min Power Frequency Withstand Voltage, Phase - to - phase and to - ground / Break |
KV |
42/48 |
9 |
Lightning Impulse Withstand Voltage (Peak Value), Phase - to - phase and to - ground / Break |
KV |
75/85 |
10 |
Rated Cable Charging Breaking Current |
A |
10 |
11 |
Rated Breaking of No - load Transformer |
KVA |
1250 |
12 |
Mechanical Life |
Times |
2000 |
13 |
Rated Breaking Transfer Current |
A |
1150 |
14 |
Rated Short - circuit Breaking Current of Fuse |
KA |
31.5 |
Muhimman Tushen Kirkiro ga Load Break Switch
Nambar |
Suna |
Unit |
Yawan Yadda |
Shawarwari |
1 |
Phase - to - phase Center Distance |
mm |
210 ± 3 |
|
2 |
Total Stroke of Conductive Rod |
mm |
215 ± 5 |
|
3 |
Distance Between Moving and Static Arc at Opening Position |
mm |
>160 |
|
4 |
Over - stroke of Electrical Contact of Moving Contact Rod |
mm |
42 ± 3 |
|
5 |
Just - Closing Speed |
m/s |
3.8 <sup>+0.7</sup><sub>-0.2</sub> |
|
6 |
Just - Opening Speed |
m/s |
>2.7 |
|
7 |
Three - phase Closing Asynchronism |
ms |
>10 |
Contact between moving contact rod and contact fingers |
8 |
Three - phase Opening Asynchronism |
ms |
>5 |
Separation between moving contact rod and contact fingers |
Altitude: Not exceeding 1000m.
Ambient Temperature: Maximum +40°C, Minimum -10°C.
Relative Humidity: Daily average not exceeding 95%, Monthly average not exceeding 90%.
Seismic Intensity: Less than 8 degrees.