| Marke | Switchgear parts | 
| Numru tal-Model | GYAR9-AC-TY-GYL9 Smart Auto Recloser | 
| Tal-Maxx ta' Voltiġi | AC220V | 
| Rated frequency | 50/60Hz | 
| Siri | GYAR9-AC | 
Il-seriali GYAR9 SMART AUTO RECLOSER taqdim ikkun robusta u soluzzjoni adattabbil għal sistemi elettriku fi setturi industriji u kommerċjalijiet. Kompattibbli ma’ GYL9 Residual Current Device, li jgħin bil-aġġornament tal-aħwa u r-affidabilità.
Rated Voltage: AC-220V jew DC-48V (dependenti mill-model)
Operating Voltage: 230V AC (70%-125%) jew 24-48V DC
Control Signals: MODBUS-RS485, wet node, jew dry contact
Durability: 10,000 operazzjonijiet elettriku u mekaniku
Protection Rating: IP20
Temperature Range: -26°C sa +70°C
Flexible Control Modes: Ozzjonijiet inklużu dry contact, wet contact, jew RS485 control għad-dħul seamless.
Voltage Protection: Il-model GYAR9-AC-UV joffri protezzjoni self-recovering over u under voltage biex isirvja l-equipment.
Fault Recovery Automation: Jreset awtomatikament wara ħsara temporanji, minn naqs id-down time.
Digital Monitoring Display: Ttaraħ voltage, switching counts, u kondizzjonijiet tal-ħsara għad-dħul quick status checks.
Self-Locking Safety: Previenu l-ikkuljata ripetuta waqt il-ħsara persistenti, isirvja l-sistema tiegħek.
| Standard | EN 50155, GB/T 24338.4-2018, EN 45545-2, IEC 61373 | 
| Red, MCB overcurrent fault | |
| Manual Remote control of opening&closing disabled | |
| (between S2C-RM DC and MCB) | 4kV (4.9kV at sea level) | 
| Adaption | Acti9 Series 1P-4 | 
| Ambient Temperature | -25…+70℃ | 
| Auto/Manual switching | Auto Remote control of opening&closing available | 
| Auxiliary signal terminal wiring capacity | 28-14AWG 1.5mm² | 
| Closing action time | < 1s | 
| Control circuit cable length | ≤1500m | 
| Control signal | MODBUS-RS485 Wet node 230V high level/pulse signal (optional) | 
| Current-carrying capacity of auxiliary contacts (terminals 8-9-10) | 1CO, minimum operating current 3mA (24VDC) (resistive) (optional) | 
| Current-carrying capacity of signaling contacts (terminals 5-6-7) | Maximum operating current 2A (30V DC), 0.5A (125V AC) (optional) | 
| DIN rail mounting | DIN rail EN 60715 (35 mm) | 
| Digital display | 3-digit voltage, switching times, fault status | 
| Effective control signal duration | >400ms | 
| Electrical Characteristics | |
| Electrical life | 10000 times, 3 times/minute | 
| Hazard class according to EN 45545-2 | EN 45545-2 R26 /HL3 | 
| Indicator Light | Green, Normal status | 
| Installation and Wiring | |
| Mechanical Characteristics | |
| Mechanical life | 10000 | 
| Mounting position | Mounting on DIN rail Any position | 
| Opening action time | < 0.5s | 
| Operating Voltage | 230V AC(70%~125%) 24-48V DC(optional) | 
| Over&Under voltage function | 160-275V ±5V (optional) | 
| Power and control signal terminal wiring capacity | 28-12AWG 2.5mm² | 
| Power consumption | ≤ 1.5VA (static); ≤25VA (dynamic) | 
| Protection class | Ip20 | 
| Rated Impulse Withstand Voltage Uimp | |
| Rated insulation voltage | 400V | 
| Resistance to heat and humidity IEC/EN 60068-2-30 | 28 cycles (55°C/90-96 % , 25°C/95-100 %) | 
| Self-locking protection | Within 10s of 3CO / 20s of 4CO / 30s of 6CO, the product will self-lock and recover automatically after 40s. | 
| Shock and vibration resistance According to IEC 61373 | category 1 – class A/B – body mounted | 
| Storage Temperature | -40…+70℃ | 
| Timing function | Available (optional) | 
 
                                         
                                         
                                         
                                         
                                        