• DS5 40.5kV 72.5kV 126kV High voltage disconnect switch
DS5 40.5kV 72.5kV 126kV High voltage disconnect switch
discuss personally
Model
DS5-126/2000-40
DS5-72.5/2000-40
DS5-40.5/2500-40
Basic info
Brand ROCKWILL
Model NO. DS5 40.5kV 72.5kV 126kV High voltage disconnect switch
Rated voltage 72.5kV
Rated normal current 2000A
Series DS5
Product Detail

Description:

DS5 series disconnector adopts double-column horizontal V-type rotation structure, which is composed of three unipolar and operating mechanism. Each single electrode consists of a base, a post insulator, and a conducting part. A rotating pillar insulator is installed at both ends of the base, and the contact arm and contact arm of the main electrical part are respectively fixed on the top of the pillar insulator.

The operating mechanism drives one end of the pillar insulator to rotate, and drives the other end of the pillar insulator to reverse rotate 90° through the cross connecting rod, so that the conductive knife can turn on the horizontal plane to realize the isolation switch opening and closing. The opening state forms a horizontal insulation fracture.

 

Main Features:

 

  •  The conductive arm is made of rectangular aluminum alloy tube or aluminum alloy plate, high strength, light weight, large heat dissipation area, good anti-corrosion performance;

  • The contact part of the conductive arm adopts external pressure plate spring structure. The plate spring is made of alloy material with good elasticity, which can keep the contact pressure stable for a long time and overcome the drawbacks of the spring internal pull structure.

Technical parameter:

 

 

What are the main functions of the disconnector?

 

This is the primary function of an isolator switch. When performing maintenance or inspection on electrical equipment, the isolator switch is opened to create a clear break point between the equipment and the power supply. The insulation distance at this break point must meet relevant standards to ensure that no voltage from the power side is applied to the equipment side, thus ensuring the safety of the operators and the equipment. For example, when inspecting a transformer in a substation, the isolator switch connected to the transformer is first opened to isolate the transformer from the grid, before proceeding with subsequent maintenance work.

Auxiliary Function in Switching Operations:

In switching operations in substations and other electrical systems, isolator switches are used in conjunction with circuit breakers and other switching devices. Although isolator switches cannot interrupt normal load currents or short-circuit currents, they can be used to change the connection configuration of the circuit after the circuit breaker has already interrupted the circuit. For instance, they can be used to switch a line from one busbar to another. However, these operations must be performed strictly according to the operating procedures, as incorrect operation sequences can lead to serious electrical accidents.

Opening and Closing Small Current Circuits;

Isolator switches can be used to open and close small current circuits, such as the no-load currents of voltage transformers and surge arresters, and capacitive currents. However, they cannot be used to open and close normal load currents or short-circuit currents because they lack arc-quenching devices (or have very weak arc-quenching capabilities). Attempting to open or close large currents can result in intense arcs, damaging the isolator switch and potentially causing electrical fires or other accidents.


 

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Analysis of Partial Discharge Principle (1)
Analysis of Partial Discharge Principle (1)
Analysis of Partial Discharge Principle (1)Under the action of an electric field, in an insulation system, discharge occurs only in some regions and does not penetrate between the conductors with the applied voltage. This phenomenon is called partial discharge. If partial discharge occurs near a conductor surrounded by gas, it can also be called corona.Partial discharge can occur not only at the edge of a conductor but also on the surface or inside an insulator. The discharge occurring on the su
Leon
07/19/2025
What types of FACTS controllers are there?
What types of FACTS controllers are there?
According to the type of connection FACTS Controller with the power system, it is classified as;Series Connected ControllerShunt Connected ControllerCombined Series-Series ControllerCombined Shunt-Series ControllerSeries-Connected ControllersSeries controllers introduce a voltage in series with the line voltage, typically using capacitive or inductive impedance devices. Their primary function is to supply or absorb variable reactive power as needed.When a transmission line is heavily loaded, the
Edwiin
07/19/2025
What are FACTS and related technologies?
What are FACTS and related technologies?
FACTS (Flexible Alternating Current Transmission System) refers to a power electronics-based system that uses static devices to enhance the power transfer capability and controllability of AC transmission networks.These power electronic devices are integrated into conventional AC grids to boost key performance metrics, including:Power transfer capacity of transmission linesVoltage stability and transient stabilityVoltage regulation precisionSystem reliabilityThermal limits of transmission infras
Edwiin
07/19/2025
What are the differences between HVAC and HVDC?
What are the differences between HVAC and HVDC?
Difference Between HVAC and HVDCElectricity generated in power plants is transmitted over long distances to electrical substations, which then distribute it to consumers. The voltage used for long-distance power transmission is extremely high, and we will explore the reasons for this high voltage later. Additionally, the transmitted power can be in either alternating current (AC) or direct current (DC) form. Therefore, power can be transmitted using either HVAC (High Voltage Alternating Current)
Edwiin
07/19/2025
What are the Advantages of HVDC over HVAC?
What are the Advantages of HVDC over HVAC?
What are the Advantages of HVDC over HVAC?Electricity travels long distances before reaching consumers. Power plants, often remote, supply electricity through hundreds of miles and multiple substations. High-voltage transmission reduces line losses, with both AC and DC used. Though AC is familiar via utility poles and home outlets, HVDC offers unique advantages in power transmission.The goal of power transmission is to minimize losses and costs. While both face influencing factors, HVDC has more
Edwiin
07/19/2025
Is the neutral - point grounding method of the power grid of 110kV and above only the neutral - point direct grounding method?
Is the neutral - point grounding method of the power grid of 110kV and above only the neutral - point direct grounding method?
Neutral - Point Grounding Modes and Protection of Transformers in Power GridsFor systems ranging from 110 kV to 500 kV, an effective grounding method shall be adopted. Specifically, under all operating conditions, the ratio of zero - sequence reactance to positive - sequence reactance X0/X1 of the system should be a positive value and not exceed 3. Meanwhile, the ratio of zero - sequence resistance to positive - sequence reactance R0/X1should also be a positive value and not exceed 1.In 330 kV a