What Are The Types Of Capacitor Bank

Unit of a capacitor bank is normally called capacitor unit. The capacitor units are manufactured as single phase unit. These single phase units are connected in star or delta to farm a complete 3 phase capacitor bank. Although some rare manufacturers 3 phase capacitor unit but normally available capacitor units are single phase type. The

  • Externally fused capacitor bank.

  • Internally fused capacitor bank.

  • Fuse less capacitor bank.

Let us discuss these types of capacitor bank one by one.

Externally Fused Capacitor Bank

In this type of capacitor bank, the fuse unit is provided to each capacitor unit externally. On fault in any unit the externally provided fuse of that unit will be blown out. As the fusing system disconnects the faulty capacitor unit, the bank will continue it’s service without any interruption. In this type of capacitor units are connected in parallel.

As there are several capacitor units connected parallelly per phase of the capacitor bank, on failure of one unit, there will be not much affect on performance of entire bank. As one capacitor unit is missing in one phase the capacitance of that phase will be lower than that of other two phases. This will result higher voltage in other two phases of the bank. If the capacity of one capacitor unit in a bank is low enough then in absence of any unit in the bank there will not be much voltage unbalance. This is why the VAR rating per capacitor unit in a bank is restricted up to a specified limit.
In the externally fused
capacitor bank, the faulty unit can easily be identified by identifying blown out fuse unit through visual inspection.
The rating of capacitor unit is typically from 50 KVAR to 40 KVAR.
The main drawback of this type of capacitor bank is that, on failure of any fuse unit, there will be unbalance sensed, even all capacitor units of the bank are healthy.

Interally Fused Capacitor Bank

The entire capacitor bank is constructed in a single arrangement. As per rating of entire bank, several capacitor elements are connected parallel and series. Each of the capacitor elements is individually protected with fuse unit. As the fuses and capacitor elements are placed inside same casing, the bank is called internally fused capacitor bank. In this type of capacitor bank, each capacitor element is very small in ratings, so that if any of the elements are out of service, there will be no remarkable affect in the performance of the bank. Internally fused capacitor bank can run satisfactorily even more than one capacitor elements are out of service.
The main drawback of this bank is that, on failure of many number of capacitor elements, the entire bank is to be replaced. There is no scope of single unit replacement.
The main advantages is that, it is quite easy to install and also easy to maintain.

Fuse Less Capacitor Bank

In this type of capacitor bank required number of fuse units is connected in series to farm a capacitor string. Then required number of required number of these strings is connected in parallel to farm capacitor bank per phase. Then three similar per phase bank are connected in star or delta to farm entire 3 phase capacitor bank. The units of the capacitor strings are not at all protected by any internal or external fusing arrangement. In this system, if one of the unit of a string fails due to short circuit, there will be no remarkable change in current through this string as there are many other capacitor connected in series along this path. As the effect of short circuited unit in the string is small enough, the bank can be run up to prolong time before replacement of faulty unit. This is the reason, why fuse is not required to isolate the faulty unit from the system in this type of capacitor bank immediately after unit becomes faulty.

Advantages of Fuse Less Capacitor Bank

The main advantages of fuse less capacitor bank are,

  • They are less expensive then fused capacitor banks.

  • They require less space compared to fused capacitor bank.

  • Less chance of bird fault, snake fault or rat fault as the inter connecting wire can be insulated properly in fuse less capacitor bank.

Disadvantages of Fuse Less Capacitor Bank

There are also some disadvantages of fuse less capacitor bank.

  • Any earth fault in the bank, unit, such as bushing fault, insulation failure between tank and live part of the capacitor, should be cleared immediately by tripping of circuit brake associated with this bank as there is no provision of any fuse.

  • For replacement of any capacitor unit, only identical spare is required. It cannot be managed by available standard capacitor unit. So, there must be sufficient stock of identical capacitor units available at site which is an extra investment.

  • Some time it becomes difficult to locate actual faulty unit of the bank only by visual inspections. Then the time required to replace actual faulty unit will be higher.

  • Sophisticated relay and control system are essential for fuse less capacitor bank. The relay system of the bank should also be capable of tripping the circuit breaks associated with it in the event of input power failure to the relay.

  • External reactor is required to limit transient current in the capacitor.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.