Typical sensors used for UHF PD measurement for GIS

Edwiin
Edwiin
Field: Power switch
China

In most types of Gas - Insulated Switchgear (GIS), the Ultra - High - Frequency (UHF) energy is concentrated within the frequency range of 100 MHz to 2 GHz. The frequency response of the sensor is contingent upon its size, shape, and the connection method employed. Most sensors are, in themselves, resonant structures at UHF frequencies, and this characteristic can be exploited to enhance performance. Typical sensors are depicted in the figure.

Internal sensors are typically installed in a recess within the enclosure. In this area, the radial component of the electric field is the most significant. Since degassing of the GIS chambers is essential, internal sensors must be installed during the manufacturing of the GIS or retrofitted during maintenance. These sensors commonly take the form of a metal disc that is insulated from the GIS enclosure by a dielectric material. The measurement connection is established through a coaxial connector, which is usually attached to the center of the disc.

Externally mounted sensors (for instance, at an inspection window or barrier insulator) will be influenced by the field patterns in the structure on which they are mounted. In such cases, the mounting arrangement should be regarded as an integral part of the sensor. External sensors are installed in an aperture in the chamber wall, such as an inspection window or an exposed barrier edge.

Give a tip and encourage the author!
Recommended
SF6 Leak Detection Methods for GIS Equipment
SF6 Leak Detection Methods for GIS Equipment
For SF6 gas leakage rate detection in GIS equipment, when using the quantitative leak detection method, the initial SF6 gas content in the GIS equipment must be accurately measured. According to relevant standards, the measurement error should be controlled within ±0.5%. The leakage rate is calculated based on changes in gas content after a period of time, thereby evaluating the sealing performance of the equipment.In qualitative leak detection methods, direct visual inspection is commonly used,
Oliver Watts
10/31/2025
Why RMUs Fail? Condensation & Gas Leak Explaine
Why RMUs Fail? Condensation & Gas Leak Explaine
1. IntroductionRing main units (RMUs) are primary power distribution equipment that house load switches and circuit breakers within a metal or non-metal enclosure. Due to their compact size, simple structure, excellent insulation performance, low cost, easy installation, and fully sealed design [1], RMUs are widely used in medium- and low-voltage power systems across China’s grid network [2], especially in 10 kV distribution systems. With economic growth and increasing electricity demand, requir
Felix Spark
10/31/2025
Preventing RMU Insulation Failures: Key Causes
Preventing RMU Insulation Failures: Key Causes
1. Insufficient Creepage Distance or Air ClearanceInadequate creepage distance and air gaps are the main causes of insulation failure and accidents in solid-insulated ring main units (RMUs). Especially in drawer-type cabinets, manufacturers reduce cabinet size by minimizing space for circuit breakers, significantly decreasing isolation distances between plug contacts and ground. Without adequate reinforcement of insulation structure, such designs increase the risk of flashover under overvoltage
Felix Spark
10/31/2025
What Is Discharge Load for Energy Absorption in Power Systems?
What Is Discharge Load for Energy Absorption in Power Systems?
Discharge Load for Energy Absorption: A Key Technology for Power System ControlDischarge load for energy absorption is a power system operation and control technology primarily used to address surplus electrical energy caused by load fluctuations, power source faults, or other disturbances in the grid. Its implementation involves the following key steps:1. Detection and ForecastingFirst, real-time monitoring of the power system is conducted to collect operational data, including load levels and