• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Unsang Breaker Wala'y Pagprotekta Kontra sa Ground Faults

Edwiin
Larangan: Switch sa kuryente
China

Ang usa ka broken neutral sa isang circuit nga may standard breaker mahimong mag-uli og shock hazard tungod kay ang breaker wala nimo monitor o protektahan ang neutral wire. Ang internal mechanism sa usa ka standard breaker wala gidisenyo aron mabuto ang ground-fault currents samtang operasyon. Ang mga standard circuit breakers giginhawa aron maprotektahan ang overloads ug short circuits, dili ang ground faults.

Ang mga standard breakers nag-monitor sa current sa hot wire ug trip kung ang current adunay gibag-o sa rating sa breaker—karon sa usa ka overload o short circuit. Pero, sama sa usa ka broken neutral, ang fault current mahimong mobalik sa source pinaagi sa ground wire. Kini nahitabo tungod kay ang ground ug neutral terminal bars gipadako sa main panel.

Isip resulta, ang usa ka current mas baba sa rated capacity sa breaker mahimong mopuyo sa circuit pinaagi sa usa ka unintended path. Tungod kay walay excessive current molihok sa hot wire, ang breaker wala mabuto og fault ug gi-remain closed. Isip resulta, ang bahin sa circuit gi-energized, nag-create og hidden shock risk nga wala ma-address sa breaker.

Ang pinaka common nga faults sa usa ka electric circuit mao ang sumala:
Overloads ug Short Circuits

Ang mga standard breakers reaksiyon sa excessive current gikan sa overloads o direct short circuits (high-current faults diin ang current molihok direkta gikan sa hot to neutral o hot to hot). Kini nga kondisyon mag-create og current surge, nga ang breaker mabuto ug trip aron maprevent ang damage.

Ground Faults

Ang ground fault mogahin kung ang current molaoy gikan sa hot wire ngadto sa grounded surface, bypassing the neutral wire (e.g., tungod sa usa ka broken neutral o usa ka live wire contacting a metal appliance case o wet surface). Ang ground faults dili mag-generate og high current surges required aron matrip ang standard breaker, lalo na kung gamay ra ang amount sa current molaoy sa ground. Kini nga leakage makapukaw og severe shock hazards wala pa maabot sa trip threshold sa breaker.

Pila Ka Standard Breaker Respond sa usa ka Short Circuit o Ground Fault?

Tananam-an ta pila ang standard breaker behaves ug reacts sa short circuits o ground faults sa circuit, as illustrated below.

Konsidera kini nga example: Sa 120V/240V main panel, ang lighting circuit gicontrol ug giprotektahan pinaagi sa 15-amp standard breaker sa 120V supply, ug ang neutral connection nawala.

As shown in the figure, if the neutral bar in the main panel is unavailable, return current tries to flow back to the neutral bar. Since the neutral bar is bonded to the ground bar, the current’s only path back to the source (typically the transformer) is through the ground wire. This forms a circuit, allowing approximately 2.4 amps of fault current to flow. The light bulb may still emit a dim glow.

Kini nga 2.4-amp fault current well below sa 15-amp rating sa breaker, so it does not trip. Consequently, ang circuit presents a shock hazard, as all metal components—including equipment enclosures, metal raceways, ug the metallic bodies of connected devices—become energized with approximately 72V AC.

Ngayon, considera another scenario diin ang neutral nawala ug ang hot wire contacts the metallic body of the device, creating a "double fault." In this case, ang light is off due to the absence of load resistance. As shown in the figure, a fault current of approximately 4 amps flows through the ground conductor back to the source.

Again, all metal components in the circuit become energized at 120V AC. This 4-amp fault current remains below the breaker’s 15-amp threshold, so the breaker does not trip. If an operator touches the equipment enclosure, metal raceway, or device’s metallic body, they risk a severe electric shock.

To mitigate these hazards, a GFCI (Ground Fault Circuit Interrupter) breaker is recommended over a standard breaker. GFCI breakers are engineered to detect ground faults and trip in dangerous scenarios—including those caused by a broken neutral—ensuring safer operation.

Maghatag og tip ug pagsalig sa author

Gipareserbado

Pangunahon nga Transformer Accidents ug Light Gas Operation Issues
1. Talaan sa Pagkamalasakit (Marso 19, 2019)Sa 16:13 sa Marso 19, 2019, ang background monitoring nagreport og light gas action sa No. 3 main transformer. Sumala sa Code for Operation of Power Transformers (DL/T572-2010), ang mga tawo sa operation and maintenance (O&M) nagsagol sa kondisyon sa No. 3 main transformer sa dapit.Konfirmasyon sa dapit: Ang WBH non-electrical protection panel sa No. 3 main transformer nagreport og Phase B light gas action sa transformer body, ug ang reset wala mae
02/05/2026
Mga Sayop ug Paghunahuna Sa Pag-atas Sa Iisa Ka Fasa Sa 10kV Distribution Lines
Mga Kinaiya ug mga Kaugalingong Detektor sa Single-Phase Ground Fault1. Mga Kinaiya sa Single-Phase Ground FaultMga Signal sa Central Alarm:Nagring ang warning bell, ug naglitaw ang indicator lamp nga gilabel “Ground Fault on [X] kV Bus Section [Y]”. Sa mga sistema nga may Petersen coil (arc suppression coil) nga naka-ground sa neutral point, ang “Petersen Coil Operated” nga indicator usab motindog.Mga Indikasyon sa Insulation Monitoring Voltmeter:Ang voltage sa nahisalaan nga phase mokubos (kon
01/30/2026
Neutral nga punto sa grounding operation mode alang sa 110kV~220kV power grid transformers
Ang pag-arrange sa mga modo ng operasyon ng grounding ng neutral point para sa 110kV~220kV power grid transformers dapat matugunan ang mga requirement ng insulation withstand sa mga neutral points ng transformer, ug usahay mao usab ang pagpanalipod sa zero-sequence impedance sa mga substation nga walay dako nga kausaban, samtang sigurado nga ang zero-sequence comprehensive impedance sa anumang punto sa short-circuit sa sistema dili mogawas sa tulo ka beses sa positive-sequence comprehensive impe
01/29/2026
Unsa ang Katuyohan sa Paggamit og Bato Gravel Pebbles ug Crushed Rock sa mga Substation?
Asa Kini ang mga Substation Usa ka Bato, Gravel, Pebbles, ug Crushed Rock?Sa mga substation, ang mga equipment sama sa power ug distribution transformers, transmission lines, voltage transformers, current transformers, ug disconnect switches nimo kinahanglan og grounding. Padulong sa grounding, karon atong ibutangan ang kahibawo bahin kon asa kini nga gravel ug crushed stone gamiton sa mga substation. Bisag ordinaryohan ra sila, importante kaayo ang papel nila sa seguridad ug pagkabana-bana.Sa d
01/29/2026
Inquiry
+86
I-klik aron i-upload ang file
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo