Digitalicition example based by IEC 61850 in medium voltage switchgear

Edwiin
Edwiin
Field: Power switch
China

The utilization of Rogowski coils for current measurements, voltage dividers for voltage measurements, and a digital bus for sharing switchgear events and sampled measured values enables the separation of measuring hardware engineering from protection applications. This decoupling enhances flexibility and efficiency in electrical system design and operation.

For the protection functions of each Intelligent Electronic Device (IED), line - to - ground currents are consistently measured separately in every feeder. In incoming feeders, resistive dividers are connected to the cables, supplying the necessary voltage measurements to the IEDs within these feeders.

Outgoing feeder protection schemes often require the use of busbar voltage measurements. For example, in section A, one outgoing feeder is equipped with resistive voltage dividers linked to the section A busbar system. Additionally, a bus coupler in this setup has resistive voltage dividers connected to the section B busbar system.

The IEDs in these feeders not only potentially utilize the measured voltage for their own protection schemes but also publish voltage - sampled measured data to the digital communication network. This allows all other IEDs, whether located in section A or B, to subscribe to this digital voltage measurement for their specific protection requirements.

Finally, switchgear events are shared across all feeders, which is crucial for implementing switchgear control, blocking, and interlocking logic. This sharing of information ensures coordinated and reliable operation of the switchgear, enhancing the overall safety and stability of the electrical system.

Give a tip and encourage the author!
Recommended
 Electrical Room Power-On Safety Operation Guide
Electrical Room Power-On Safety Operation Guide
Power Supply Procedure for Low-Voltage Electrical RoomsI. Pre-Power-On Preparations Clean the electrical room thoroughly; remove all debris from switchgear and transformers, and secure all covers. Inspect busbars and cable connections inside transformers and switchgear; ensure all screws are tightened. Live parts must maintain adequate safety clearance from cabinet enclosures and between phases. Test all safety equipment before energizing; use only calibrated measuring instruments. Prepare fire-
Echo
10/28/2025
Low-Voltage Distribution Cabinet Maintenance Steps and Safety Guide
Low-Voltage Distribution Cabinet Maintenance Steps and Safety Guide
Maintenance Procedure for Low-Voltage Power Distribution FacilitiesLow-voltage power distr ibution facilities refer to the infrastructure that delivers electrical power from a power supply room to end-user equipment, typically including distribution cabinets, cables, and wiring. To ensure the normal operation of these facilities and guarantee user safety and power supply quality, regular maintenance and servicing are essential. This article provides a detailed introduction to the maintenance pro
Edwiin
10/28/2025
Low-Voltage Electrical Work Safety Preparation and Operation Guide
Low-Voltage Electrical Work Safety Preparation and Operation Guide
Low-Voltage Electrician Safety Operating Procedures1. Safety Preparation Before performing any low-voltage electrical work, personnel must wear approved protective equipment, including insulating gloves, insulating boots, and insulating workwear. Carefully inspect all tools and equipment for proper operation. Report any damage or malfunction immediately for repair or replacement. Ensure adequate ventilation at the worksite. Avoid prolonged work in confined spaces to prevent fire hazards or poiso
Echo
10/28/2025
How to Handle Common Faults in RMU and Transformer Substations?
How to Handle Common Faults in RMU and Transformer Substations?
1. Ring Main Unit (RMU) and Transformer SubstationThe ring main unit (RMU) and transformer substation is a critical terminal in a distribution ring network system. The operational status of this terminal is directly affected by the performance of the distribution ring network system. Therefore, this section discusses the advantages, system composition, and key characteristics of the distribution ring network.1.1 Advantages of RMU and Transformer SubstationDue to technological limitations, radial
Felix Spark
10/28/2025