What is Valve Type Lightning Arrester?

Edwiin
Edwiin
Field: Power switch
China

What is Valve Type Lightning Arrester?

Definition

A lightning arrester that consists of single or multiple gaps connected in series with a current - controlling element is known as a lightning arrester. The gap between the electrodes blocks the flow of current through the arrester, except when the voltage across the gap exceeds the critical gap flashover voltage. The valve - type arrester is also referred to as a gap surge diverter or a silicon carbide surge diverter with a series gap.

Construction of Valve - Type Lightning Arrester

The valve - type arrester is composed of a multiple - spark - gap assembly connected in series with a resistor made of a non - linear element. Each spark gap has two components. To address the non - uniform distribution between the gaps, non - linear resistors are connected in parallel across each gap.

The resistor elements are fabricated from silicon carbide with inorganic binders. The entire assembly is encased within a sealed porcelain housing filled with nitrogen gas or SF6 gas.

Working of Valve - Type Lightning Arrester

Under low - voltage conditions, due to the influence of the parallel resistor, no spark - over occurs across the gaps. Slow changes in the applied voltage do not pose harm to the system. However, when rapid voltage changes take place across the terminals of the arrester, the air - gap spark of the current is discharged to the ground through the non - linear resistor, which exhibits extremely low resistance.

After the passage of the surge, the voltage impressed across the arrester drops, and the arrester's resistance increases until the normal voltage is restored. When the surge diverter action ceases, a small low - power - frequency current flows in the path created by the flash - over. This current is referred to as the power follow current.

The magnitude of the power follow current diminishes to a value that can be interrupted by the spark gap as it recovers its dielectric strength. The power follow current is extinguished at the first current zero - crossing, and the power supply remains uninterrupted. Subsequently, the arrester is ready to resume normal operation. This process is called the resealing of the lightning arrester.

Stage of Valve - Type Lightning Arrester

When the surge reaches the transformer, it encounters the lightning arrester, as depicted in the figure below. In approximately 0.25 μs, the voltage reaches the breakdown value of the series gap, and the arrester starts to discharge.

As the surge voltage rises, the resistance of the non - linear element decreases. This enables the further discharge of surge energy, thereby limiting the voltage transmitted to the terminal equipment, as shown in the figure below.

When the voltage decreases, the current passing to the ground also diminishes, while the resistance of the lightning arrester increases. The lightning arrester reaches a stage where the current flow is interrupted by the spark gap, and the arrester seals once again.

The maximum voltage that develops across the arrester terminal and is transmitted to the terminal equipment is defined as the discharge value of the arrester.

Types of Valve - Type Lightning Arrester

Valve - type lightning arresters can be classified into station types, line types, arresters for the protection of rotating machines (distribution type), or secondary type.

  • Station - Type Valve Lightning Arrester:This type of valve arrester is primarily used for safeguarding critical power equipment in circuits ranging from 2.2 kV to 400 kV and higher. It features a high energy - dissipation capacity.

  • Line - Type Lightning Arrester:Line - type arresters are applied to protect substation equipment. They have a smaller cross - sectional area, are lighter in weight, and are more cost - effective. In comparison to station - type arresters, they allow a higher surge voltage across their terminals and have a lower surge - carrying capacity.

  • Distribution Arrester:This kind of arrester is typically mounted on poles and is utilized for protecting generators and motors.

  • Secondary Arrester:A secondary arrester is designed to protect low - voltage apparatus. The arrester for protecting rotating machines is engineered specifically for the protection of generators and motors.

 

 

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s