Key Considerations for Step-Up Transformer Selection in Grid-Connected PV Power Systems

Edwiin
Edwiin
Field: Power switch
China

In grid-connected photovoltaic (PV) power generation systems, the step-up transformer is a critical component. Optimizing transformer selection to minimize inherent losses and enhance efficiency is essential for improving overall system performance. This article outlines key considerations for proper step-up transformer selection in PV systems.

  • Transformer Capacity Selection
    The required transformer capacity is calculated as: Apparent Power = Active Power / Power Factor. Power factor requirements vary by region—typically 0.85 for construction and small industrial loads, and 0.9 for large industrial loads. For example, a 550 kW load at 0.85 power factor requires 550 / 0.85 = 647 kVA, so a 630 kVA transformer is suitable. Total load should not exceed 80% of the transformer’s rated capacity.

  • Transformer Voltage Selection
    The primary winding voltage should match the source line voltage, while the secondary voltage must align with the connected equipment. For low-voltage three-phase four-wire distribution, appropriate voltage levels (e.g., 10 kV, 35 kV, or 110 kV) should be selected based on primary-side requirements.

  • Transformer Phase Selection
    Choose between single-phase and three-phase configurations according to the power source and load requirements.

  • Transformer Winding Connection Group Selection
    Three-phase windings can be connected in star (Y), delta (D), or zigzag (Z) configurations. The globally preferred connection for distribution transformers is Dyn11, which offers several advantages over Yyn0:

    • Harmonic Suppression: The delta (D) connection effectively suppresses higher-order harmonics.

    • Harmonic Circulation: Third harmonic currents circulate within the delta winding, neutralizing third harmonic flux from the low-voltage side.

    • Harmonic Containment: Third harmonic EMF in the high-voltage winding remains confined within the delta loop, preventing injection into the public grid.

    • Lower Zero-Sequence Impedance: Dyn11 transformers exhibit significantly lower zero-sequence impedance, aiding in the clearance of low-voltage single-phase ground faults.

    • Superior Neutral Current Handling: Capable of handling neutral currents exceeding 75% of phase current, making them ideal for unbalanced loads.

    • Continuity Under Phase Loss: If one high-voltage fuse blows, the remaining two phases can continue operating with Dyn11, unlike with Yyn0.

Therefore, Dyn11-connected transformers are strongly recommended.

Load Loss, No-Load Loss, and Impedance Voltage
Due to the daytime operation pattern of PV systems, transformers incur no-load losses whenever energized, regardless of output. Minimizing load losses is crucial; if nighttime operation occurs, low no-load losses are also important.

This selection strategy ensures efficient transformer operation within PV systems, reducing overall losses and enhancing power generation performance.

Give a tip and encourage the author!
Recommended
What are the safety precautions and guidelines for using AC load banks?
What are the safety precautions and guidelines for using AC load banks?
AC load banks are electrical devices used to simulate real-world loads and are widely applied in power systems, communication systems, automation control systems, and other fields. To ensure personal and equipment safety during use, the following safety precautions and guidelines must be observed:Select an appropriate AC load bank: Choose an AC load bank that meets actual requirements, ensuring its capacity, voltage rating, and other parameters satisfy the intended application. Additionally, sel
Echo
11/06/2025
What should be noted when installing a Type K thermocouple?
What should be noted when installing a Type K thermocouple?
Installation precautions for Type K thermocouples are critical to ensuring measurement accuracy and extending service life. Below is an introduction to the installation guidelines for Type K thermocouples, compiled from highly authoritative sources:1.Selection and Inspection Select the appropriate thermocouple type: Choose the right thermocouple based on the temperature range, medium properties, and required accuracy of the measurement environment. Type K thermocouples are suitable for temperatu
James
11/06/2025
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah