Un (Nominal Voltage) — The nameplate of the grid, e.g., "330 kV system."
Um (Rated Maximum Voltage) — The highest voltage the equipment can continuously withstand; the real basis for selection.
A 275 kV system corresponds to Um = 300 kV. 330 kV, 345 kV and 362 kV systems all correspond to Um = 362 kV.
These four nominal voltages represent only two insulation classes.
In multi-break designs, stray capacitance to ground causes uneven voltage distribution across breaks. Grading capacitors equalize the voltage. 275 kV class uses 2 capacitor sets; 362 kV requires 2–3 sets with higher capacitance values.
Above 1000 m, air density decreases and insulation strength drops. At 3000 m altitude, the insulation margin must increase by 20%. The 362 kV class, starting from a higher voltage base, is more severely affected.
Equipment height and center of gravity directly determine seismic performance. The 362kV unit features longer bushings and a higher overall structure, with its center of gravity approximately 15–20% higher than that of the 275kV model. In areas with high seismic fortification intensity, 362kV equipment generally requires reinforced flanges, composite bushings or integral frame strengthening, while the 275kV equipment has relatively lenient requirements in these aspects.
| Parameter | 275 kV Class | 362 kV Class |
|---|---|---|
| SF₆ charge | ~100–150 kg | ~180–300 kg |
| Bushing height | ~3.5–4 m | ~4.5–5 m |
| Overall height | ~5–6 m | ~7–8.5 m |
| Single-phase shipping weight | ~4–6 t | ~7–10 t |
More Test Duties: 362 kV class falls underBeyond the standard T10, T30, T60, T100 tests, it also requires T100s (short-line fault) and T100a (asymmetrical breaking) tests.
Higher Test Cost: Each short-circuit test requires shipping the test object to a high-power lab. Test circuit costs rise significantly with voltage. A full type test program for a 362 kV breaker costs 2–3 times that of a 275 kV breaker.
More Severe Dielectric Tests: The 362 kV class requires LI across-open contacts of 1175 kV — far more challenging for both the test facility and the breaker itself than 950 kV.