Small inductive current switching condition for switchgear

Edwiin
01/14/2025

Current Chopping and Reignition in Circuit Breakers Handling Small Inductive Currents

When a circuit breaker (CB) opens or closes shunt reactor banks or unloaded power transformers, it typically switches small inductive currents, usually several tens of amperes, with a 90-degree lag relative to the voltage phase. However, these currents are often prematurely forced to zero by a phenomenon known as current chopping. This can result in chopping overvoltages and subsequent reignition overvoltages, which may cause severe consequences depending on the CB's performance and the circuit conditions.

Current Chopping Phenomenon

The typical behavior of voltage and current during current chopping is illustrated in the figure below for small inductive current interruption. When current chopping occurs, it is accompanied by an expanding high-frequency current oscillation that leads to a sudden current zero. This phenomenon is due to arc instability caused by the arc characteristics and circuit conditions.

  • Arc Instability: The arc characteristic and circuit conditions lead to instability, causing the current to be abruptly interrupted before reaching its natural zero crossing.
  • High-Frequency Oscillation: As the current is chopped, high-frequency oscillations occur, contributing to the abrupt cessation of the current.

Reignition Phenomenon

Another phenomenon following the interruption of small inductive currents is reignition. Circuit breakers can easily interrupt small inductive currents even with short arcing times and small contact gaps. However, the dielectric withstand strength of a CB increases with the contact gap. Therefore, a small contact gap is more prone to voltage breakdown during the transient recovery voltage (TRV) period if the TRV exceeds the dielectric withstand across the contact gap.

  • Dielectric Withstand Strength: The dielectric strength of the CB improves as the contact gap increases.
  • Voltage Breakdown Risk: A smaller contact gap increases the risk of voltage breakdown during the TRV period when the TRV surpasses the dielectric withstand capability of the CB.

Summary

In summary, when a circuit breaker handles small inductive currents:

  • Current Chopping: Premature interruption of the current can lead to high-frequency oscillations and overvoltages.
  • Reignition: After the initial interruption, there is a risk of reignition due to insufficient contact gap, leading to further overvoltages.

These phenomena can have significant impacts on the system, depending on the performance of the circuit breaker and the specific circuit conditions. Understanding and mitigating these effects are crucial for ensuring the reliable operation of electrical systems.

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f