Uztaisnes primārās pārbaudes shēmas un parametru mērījumu atlase UHV GIS strāvas transformatoriem

Oliver Watts
Oliver Watts
Lauks: Pārbaude un tests
China

UHV GIS sistēmā strāvas transformatorus ir atzīmējuši kā elektriskās enerģijas mērīšanas galvenos elementus. To precizitāte nosaka enerģijas tirdzniecības apreķināšanu, tāpēc vietas pārbaude saskaņā ar JJG1021 - 2007 ir nepieciešama. Vietā izmanto strāvas avotus, sprieguma regultoru un strāvas pastiprinātājus. Tā kā tie ir iebūvēti GIS sistēmā, testa šķēršļu virkni veido caur atklātajiem masas lēknīm, izlaižu raudām un atgriezeniskajiem vadiem; pareiza virkne vienkāršo uzspraudumu un palielina precizitāti.

Pastāv problēmas, piemēram, liela testa strāva, ilgas virknes un augsts impedancija, bet reaktīvais kompensācijas (izmantojot augstāko induktīvo reaktanci GIS primārajā virknē) samazina aprīkojuma jaudas prasības. Precīza primārās virknes parametru mērīšana ir būtiska kompensācijai. Esošie metodes nederēja GIS primārajām virknēm, tāpēc šajā rakstā: sakārto UHV GIS strāvas transformatoru primārās virknes struktūras/rīcības, lai izvēlētos pārbaudes virknes; izstrādāta intelektuālas metodes, lai uzlabotu parametru mērīšanas intelektualitāti/automatizāciju.

1 UHV GIS Strāvas Transformatoru Primārā Virkne
1.1 Struktūra & Izmērojumi

GIS integrē apgabala primāro aprīkojumu (izņemot transformatorus) sešos komponentos (piemēram, CB, DS). Encapsulated in metal shells, GIS offers: miniaturization (via SF6), less space); high reliability (sealed live parts resist environment/earthquakes); safety (no electric shock/fire risks); superior performance (shields EM/static, no interference); short installation (factory assembly cuts on - site time); easy maintenance & long inspection (good structure, advanced arc extinction).

1.2 Circuit Selection

Circuit breakers sit mid - GIS pipelines, with current transformers on both sides. Disconnectors are outside, plus grounding switches for protection. Pipelines use (SF6), and transformers have epoxy resin semi - casting. Due to enclosure, use exposed grounding switches/bushings + return conductors. Four options exist: grounding switches at breaker ends, GIS pipeline shells, large - current conductors, or adjacent GIS busbars as return. After solving reactive compensation, adjacent GIS busbars (safe, simple, operable) are chosen for on - site verification.

2 Research on GIS Primary Circuit Intelligent Measurement Systems
2.1 Parameter Measurement Method Analysis

GIS primary circuits have equivalent resistance R and inductive reactance (ZL). Conventional methods (measure R, apply AC, calculate complex impedance Z then (ZL) need many devices, complex ops, and heavy calculations. This paper develops intelligent systems. Key tasks: system design (component matching, process planning); determine signal collection (points, methods, circuits for voltage/current); find voltage - current phase difference calculation; select line parameter methods (from amplitude/phase difference, get equivalent resistance/inductive reactance); overcome harmonics/interference for accuracy.

2.2 Overall Design of the Intelligent Measurement System

The intelligent measurement system centers around a microcontroller - based computer system, equipped with buttons, a display, a printer, and other peripherals. The voltage and current signals are captured by the signal acquisition system, then processed through a filter, multiplexer switch, automatic signal gain amplifier, and analog - to - digital (A/D) converter before reaching the microcontroller for signal processing. The hardware principle is illustrated in Figure 1.

System Components

  • Signal Acquisition System: Captures voltage and current signals from the circuit.

  • Filter: Eliminates interference signals.

  • Multiplexer Switch: Enables voltage and current signals to share one A/D converter, reducing hardware costs.

  • Automatic Signal Gain Amplifier: Adjusts amplification automatically based on signal strength to ensure stable output.

  • A/D Converter: Transforms analog signals into digital format for microcontroller processing.

  • Display: Utilizes a direct - read digital screen for easy data viewing.

  • Buttons: Simplifies system operation with user - friendly controls.

  • Printer: Outputs measurement results on demand.

Operational Process

The acquired signals are processed and transmitted to the microcontroller, which runs pre - installed signal processing programs. The system analyzes the data via dedicated software, computes the results, and displays them on the screen.

2.3 Design of the Signal Acquisition Circuit

Given that measuring primary circuit parameters doesn’t require high currents, the system uses a regulated power supply with a 200A output. After passing through a current booster, the induced current on the line side is significantly lower than the GIS rated current, minimizing the need for large - capacity equipment. This setup keeps the current within the safe operating range of the GIS enclosure and grounding switches.

Circuit Options

The signal acquisition circuit can adopt any of the three test circuits discussed earlier (excluding the grounding - switch - based circuit, which doesn’t cover the entire GIS line). Using multiple methods simultaneously can enhance measurement accuracy. During testing, voltage and current transformers are installed to convert high primary - side values into manageable secondary - side signals for the acquisition system.

Circuit Design for Adjacent GIS Busbar Return Conductor

When using an adjacent GIS high - current busbar as the return conductor:

  • Connect a voltage transformer in parallel on the current - booster line side.

  • Install a current transformer in series between the current - booster line side and a GIS inlet bushing.

  • Feed the secondary - side voltage and current signals into the acquisition system.

The designed signal acquisition circuit is shown in Figure 2. The collected voltage and current data correspond to the total values of the circuit.

2.4 Selection of Calculation Method for Voltage and Current Phase Difference

This measurement system uses the zero - crossing phase angle method to measure the phase difference between voltage and current. The so - called zero - crossing phase angle method is to shape the fundamental wave components of the collected voltage and current signals into square waves, obtain their respective zero - crossing pulses through a differential circuit, measure the time difference between the two pulses, and then calculate the phase difference between the voltage and current.

Assume that the time of the rising edge of the voltage square wave is τ1 and the time of the rising edge of the current square wave is τ2. Then, the calculation formula for the phase difference φ between the two signals is as follows:

Among them: T is the period of voltage and current. Since the frequency of voltage and current is 50 Hz, its period is 0.02 s. The calculation formula for the phase difference of voltage and current can be simplified as:

2.5 Calculation Method for Line Parameters

These calculation processes have been programmed into the microcontroller's memory. Specialized signal - processing software is used to automatically handle the data, and the results are displayed on the device's monitor. For the convenience of analysis, the voltage and current mentioned below are by default considered to have been converted to the voltage and current of the primary side.

Assume that the amplitude of the total line voltage collected by the signal acquisition system is U, and the amplitude of the line current is I. Then, the total line resistance R1 and inductance L1 can be obtained from the following formulas

If the resistivity of the connecting conductor between the busbars of the GIS outgoing line bushing is measured as ρ, the effective cross - sectional area is s, and the length of the conductor is measured as l, then the impedance calculation formula for this connecting conductor is as follows

Neglecting other connecting conductors, the equivalent resistance R and equivalent inductance L of the primary circuit of the GIS pipeline can be obtained from the following formulas.

Error Control & Optimization

Each measurement method should be repeated 3 times at different intervals to reduce errors. If feasible, use all 3 methods simultaneously and compare results:

  • Consistent results: Average the values.

  • One outlier: Check for loose connections or wiring errors; discard the outlier if issues persist.

  • Inconsistent results: Recheck for interference. Modify the circuit if necessary; revise theoretical parameters if discrepancies remain.

To mitigate interference and harmonics:

  • Install hardware filters in the signal acquisition circuit.

  • Apply FFT software to extract fundamental wave components for calculation.

3. Conclusion

UHV GIS integrates primary equipment in sealed metal tanks, offering immunity to environmental factors, high reliability, and minimal footprint. For current transformer verification, using adjacent GIS busbars as return conductors simplifies wiring and ensures safety, making it ideal for primary detection circuits.

This study introduces an intelligent measurement system for GIS primary circuits, enabling precise measurement of equivalent resistance and inductance. The system's user - friendly interface, high accuracy, and robust anti - interference capabilities advance automation in GIS verification. Further field testing is recommended for validation and refinement.

Dodot padomu un iedrošināt autoru
Ieteicams
Pārskati par transformatoriem var tikt veikti bez jebkādiem detektīves rīkiem.
Pārskati par transformatoriem var tikt veikti bez jebkādiem detektīves rīkiem.
Transformātori ir elektrotehniskie ierīces, kas maina spriegumu un strāvu, balstoties uz elektromagnētiskās indukcijas principu. Elektrības pārnesanas un sadalīšanas sistēmās transformatori ir būtiski, lai paaugstinātu vai samazinātu spriegumu, lai samazinātu enerģijas zudumus pārnesanā. Piemēram, rūpnieciskās objekti parasti saņem enerģiju 10 kV spriegumā, kas pēc tam tiek samazināts līdz zemam spriegumam ar transformatoru palīdzību vietējai lietošanai. Šodien mēs iepazīsimies ar dažiem bieži i
Oliver Watts
10/20/2025
Vakuumaizolētiās līkstes kondensatoru grupas pārslēgšanai
Vakuumaizolētiās līkstes kondensatoru grupas pārslēgšanai
Reaktivā spēka kompensācija un kondensatoru pārslēgšana elektrotīklosReaktivā spēka kompensācija ir efektīvs līdzeklis, lai paaugstinātu sistēmas darbības uzlādi, samazinātu tīkla zudumus un uzlabotu sistēmas stabilitāti.Parastie slodzes veidi elektrotīklos (impedancijas veidi): Pretestība Induktīvā pretestība Kapacitīvā pretestībaIeslēguma strāva konondu torzīšanas laikāElektrotīklu operācijās kondensatori tiek pārslēgti, lai uzlabotu jaudas faktoru. Slēgšanas momentā rodas liela ievades strāva
Oliver Watts
10/18/2025
Vakuuma veida slēdzes izturības sprieguma testa rokasgrāmata
Vakuuma veida slēdzes izturības sprieguma testa rokasgrāmata
Vakuumaizolēto līknesātāju izolācijas sprieguma izturības tests standartiVakuumaizolēto līknesātāju izolācijas sprieguma izturības testa galvenais mērķis ir pārbaudīt, vai iekārtas izolācijas veiktspēja augstā spriegumā atbilst prasībām, un novērst bojājumus vai sprādzienus darbības laikā. Testa process jāveic stingri saskaņā ar enerģētikas nozares standartiem, lai nodrošinātu iekārtu drošību un elektrosapravu uzticamību.Testa objektiTesta objekti ietver galveno ceļu, vadības ceļu, sekundāro ceļ
Garca
10/18/2025
Kā Pārbaudīt Vakuumu Vakuumbrīvdarbības Aizslegēs
Kā Pārbaudīt Vakuumu Vakuumbrīvdarbības Aizslegēs
Vakuuma integritātes testēšana automātiskajos izolatoros: Kritiska mērījuma metode veiktspējas novērtēšanaiVakuuma integritātes testēšana ir galvenais paņēmiens vakuuma veiktspējas novērtēšanai automātiskajos izolatoros. Šis tests efektīvi novērtē izolatora izolācijas un loksnes apgāšanas spēju.Pirms testēšanas, pārliecinieties, ka automātiskais izolators ir pareizi instalēts un savienots. Bieži izmantotās vakuuma mērījumu metodes ietver augstfrekvences metodi un magnētiski kontrolēto gāzes izpl
Oliver Watts
10/16/2025
Pieprasījums
Lejupielādēt
Iegūt IEE Business lietojumprogrammu
Lietojiet IEE-Business lietotni lai atrastu aprīkojumu iegūtu risinājumus savienotos ar ekspertiem un piedalītos nozares sadarbībā jebkurā laikā un vietā pilnībā atbalstot jūsu enerģētikas projektus un biznesa attīstību