• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is a Shunt Capacitor?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is a Shunt Capacitor?


Shunt Capacitor Definition


A shunt capacitor is defined as a device used to improve power factor by providing capacitive reactance to counteract inductive reactance in electrical power systems.


Power Factor Compensation


Shunt capacitors help improve the power factor, which reduces line losses and improves voltage regulation in power systems.


Capacitor Bank


The capacitor reactance is generally applied to the system by using static capacitor in shut or series with system. Instead of using a single unit of capacitor per phase of the system, it is quite effective to use a bank of capacitor units, in the view of maintenance and erection. This group or bank of capacitor units is known as capacitor bank.

 

There are mainly two categories of capacitor bank according to their connection arrangements.

 


  • Shunt capacitor.

  • Series capacitor.


The Shunt capacitor is very commonly used.


Connection of Shunt Capacitor Bank


The capacitor bank can be connected to the system either in delta or in star. In star connection, the neutral point may be grounded or not depending upon protection scheme for capacitor bank adopted. In some cases the capacitor bank is formed by double star formation.Generally large capacitor bank in electrical substation is connected in star.


The grounded star connected bank has some specific advantages, such as,


  • Reduced recovery voltage on circuit breaker for normal repetitive capacitor switching delay.



  • Better surge protection.



  • Comparatively reduced over voltage phenomenon.


  • Lesser cost of installation.


In a solidly grounded system, the voltage of all three phases of a capacitor bank remains fixed, even during two-phase operation.


Location Considerations


Ideally, a capacitor bank should be placed near reactive loads to minimize reactive power transmission across the network. When a capacitor and load are connected together, they disconnect simultaneously, preventing overcompensation. However, it’s not practical or economical to connect a capacitor to each individual load due to varying load sizes and availability of capacitors. Additionally, not all loads are connected continuously, so the capacitors may not be fully utilized.


Hence, capacitor, is not installed at small load but for medium and large loads, capacitor bank can be installed at consumer own premises. Although the inductive loads of medium and large bulk consumers are compensated, but still there would be considerable amount of VAR demand originated from different uncompensated small loads connected to the system. In addition to that, inductance of line and transformer also contribute VAR to the system. On viewing of these difficulties, instead of connecting capacitor to each load, large capacitor bank is installed at main distribution sub-station or secondary grid sub-station.

  


Give a tip and encourage the author!
Recommended
Three-Phase SPD: Types, Wiring & Maintenance Guide
Three-Phase SPD: Types, Wiring & Maintenance Guide
1. What Is a Three-Phase Power Surge Protective Device (SPD)?A three-phase power surge protective device (SPD), also known as a three-phase lightning arrester, is specifically designed for three-phase AC power systems. Its primary function is to limit transient overvoltages caused by lightning strikes or switching operations in the power grid, thereby protecting downstream electrical equipment from damage. The SPD operates based on energy absorption and dissipation: when an overvoltage event occ
James
12/02/2025
Railway 10kV Power Through Lines: Design & Operation Requirements
Railway 10kV Power Through Lines: Design & Operation Requirements
The Daquan Line has a large power load, with numerous and scattered load points along the section. Each load point has a small capacity, with an average of one load point every 2-3 km, so two 10 kV power through lines should be adopted for power supply. High-speed railways use two lines for power supply: primary through line and comprehensive through line. The power sources of the two through lines are taken from the dedicated bus sections fed by the voltage regulators installed in each power di
Edwiin
11/26/2025
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Railway power systems primarily consist of automatic block signaling lines, through-feeder power lines, railway substations and distribution stations, and incoming power supply lines. They provide electricity to critical railway operations—including signaling, communications, rolling stock systems, station passenger handling, and maintenance facilities. As an integral part of the national power grid, railway power systems exhibit distinct characteristics of both electrical power engineering and
Echo
11/26/2025
Application of Condition Monitoring Technology in UHV Transmission Lines
Application of Condition Monitoring Technology in UHV Transmission Lines
1. Application of Condition Monitoring Technology in UHV Transmission LinesAt present, the main characteristics of UHV (Ultra-High Voltage) transmission line condition monitoring technology in China are reflected in the following aspects: Comprehensiveness: In general, during the implementation of monitoring technology, supporting facilities and integrated systems are required to ensure effective monitoring performance; High value: UHV transmission line condition monitoring technology is a criti
Echo
11/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.