Test for Thickness of Insulation of Power Cable

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Definition of Insulation Thickness Test


A test to confirm the insulation and sheath thickness of power cables to ensure they meet specified standards.


Apparatus required to test for thickness of insulation of Power Cable


This is purely a measurement process, hence the apparatus for the test are to be chosen very carefully. There should be, a micrometer gauge capable of measuring at least 0.01 mm variation, a vernier caliper which can clearly read at least 0.01 mm count, a measuring microscope with linear magnification of not less than 7 times and the possibility of reading at least to 0.01 mm, and a graduated magnifying glass can read clearly at least 0.01 mm.409410dc42af76849681b9470765be15.jpeg

 

First, prepare different specimens for each measuring instruments and method. There are two types of specimens: core cable pieces and slice pieces.

 


10f101ebce836672e76455dd438d55aa.jpeg

Specimen Preparation


Specimens are cut from the cable and prepared for different measurement techniques.


Procedure for testing of Thickness of Insulation of Power Cable


Use pieces at least 300 mm long for round conductors and outer sheaths. Cut specimens from the final product and remove all coverings without damaging the insulation or sheath. Use slice pieces for optical measurements, removing outer and inner materials if needed. Cut slices thinly along the plane perpendicular to the cable axis. Preferably take measurements at room temperature. Measure the core and insulated core diameters with a micrometer gauge or vernier caliper, perpendicular to the cable axis.


Take measurements at three equal intervals along the specimen, about 75 mm apart for a 300 mm piece. Measure the inner and outer diameters of the insulation or sheath at each point. For accuracy, take two measurements at each point, totaling six measurements for both inner and outer diameters. Calculate the average outer diameter and inner diameter from these measurements. The average radial thickness of the insulation or sheath is the difference between the average outer and inner diameters, divided by two.


197d253084a18c65d262b00a412e35b8.jpeg

 


If visual inspection shows eccentricity, use the optical method by taking a slice section of the specimen.


In the case of sliced section the specimen is placed under a measuring microscope along the optical axis. For circular specimen 6 such measurements are taken along the periphery at a regular interval. For noncircular conductor, such measurement is done radially at each point where the thickness of insulation appears minimum. The numbers of slices are taken from a specimen at regular interval along its length in such a manner that the total of such measurement would be not less than 18. For example, in case of circular conductor, at least 3 slices are taken from a specimen and 6 measurements in each slice to be carried out. In case of noncircular conductor, the number of slices taken from a specimen depends upon the number of points of minimum thickness of insulation. As in this case measurement is only made at the minimum thickness points.


Cable Insulation Importance


Ensures the cable can safely handle voltage and mechanical stresses throughout its service life.


Calculation for Thickness of Insulation


For Core/Cable Piece

Where, Dout is the average of six measurements taken for outer diameter of the insulation/sheath. Where, Din is the average of six measurements taken for inner diameter of the insulation/sheath.

For Slice Piece – The average of 18 optical measurements is taken as the minimum thickness of insulation/sheath.

 

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.