• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Test for Thickness of Insulation of Power Cable

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Definition of Insulation Thickness Test


A test to confirm the insulation and sheath thickness of power cables to ensure they meet specified standards.


Apparatus required to test for thickness of insulation of Power Cable


This is purely a measurement process, hence the apparatus for the test are to be chosen very carefully. There should be, a micrometer gauge capable of measuring at least 0.01 mm variation, a vernier caliper which can clearly read at least 0.01 mm count, a measuring microscope with linear magnification of not less than 7 times and the possibility of reading at least to 0.01 mm, and a graduated magnifying glass can read clearly at least 0.01 mm.409410dc42af76849681b9470765be15.jpeg

 

First, prepare different specimens for each measuring instruments and method. There are two types of specimens: core cable pieces and slice pieces.

 


10f101ebce836672e76455dd438d55aa.jpeg

Specimen Preparation


Specimens are cut from the cable and prepared for different measurement techniques.


Procedure for testing of Thickness of Insulation of Power Cable


Use pieces at least 300 mm long for round conductors and outer sheaths. Cut specimens from the final product and remove all coverings without damaging the insulation or sheath. Use slice pieces for optical measurements, removing outer and inner materials if needed. Cut slices thinly along the plane perpendicular to the cable axis. Preferably take measurements at room temperature. Measure the core and insulated core diameters with a micrometer gauge or vernier caliper, perpendicular to the cable axis.


Take measurements at three equal intervals along the specimen, about 75 mm apart for a 300 mm piece. Measure the inner and outer diameters of the insulation or sheath at each point. For accuracy, take two measurements at each point, totaling six measurements for both inner and outer diameters. Calculate the average outer diameter and inner diameter from these measurements. The average radial thickness of the insulation or sheath is the difference between the average outer and inner diameters, divided by two.


197d253084a18c65d262b00a412e35b8.jpeg

 


If visual inspection shows eccentricity, use the optical method by taking a slice section of the specimen.


In the case of sliced section the specimen is placed under a measuring microscope along the optical axis. For circular specimen 6 such measurements are taken along the periphery at a regular interval. For noncircular conductor, such measurement is done radially at each point where the thickness of insulation appears minimum. The numbers of slices are taken from a specimen at regular interval along its length in such a manner that the total of such measurement would be not less than 18. For example, in case of circular conductor, at least 3 slices are taken from a specimen and 6 measurements in each slice to be carried out. In case of noncircular conductor, the number of slices taken from a specimen depends upon the number of points of minimum thickness of insulation. As in this case measurement is only made at the minimum thickness points.


Cable Insulation Importance


Ensures the cable can safely handle voltage and mechanical stresses throughout its service life.


Calculation for Thickness of Insulation


For Core/Cable Piece

Where, Dout is the average of six measurements taken for outer diameter of the insulation/sheath. Where, Din is the average of six measurements taken for inner diameter of the insulation/sheath.

For Slice Piece – The average of 18 optical measurements is taken as the minimum thickness of insulation/sheath.

 

Give a tip and encourage the author!
Recommended
Three-Phase SPD: Types, Wiring & Maintenance Guide
Three-Phase SPD: Types, Wiring & Maintenance Guide
1. What Is a Three-Phase Power Surge Protective Device (SPD)?A three-phase power surge protective device (SPD), also known as a three-phase lightning arrester, is specifically designed for three-phase AC power systems. Its primary function is to limit transient overvoltages caused by lightning strikes or switching operations in the power grid, thereby protecting downstream electrical equipment from damage. The SPD operates based on energy absorption and dissipation: when an overvoltage event occ
James
12/02/2025
Railway 10kV Power Through Lines: Design & Operation Requirements
Railway 10kV Power Through Lines: Design & Operation Requirements
The Daquan Line has a large power load, with numerous and scattered load points along the section. Each load point has a small capacity, with an average of one load point every 2-3 km, so two 10 kV power through lines should be adopted for power supply. High-speed railways use two lines for power supply: primary through line and comprehensive through line. The power sources of the two through lines are taken from the dedicated bus sections fed by the voltage regulators installed in each power di
Edwiin
11/26/2025
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Railway power systems primarily consist of automatic block signaling lines, through-feeder power lines, railway substations and distribution stations, and incoming power supply lines. They provide electricity to critical railway operations—including signaling, communications, rolling stock systems, station passenger handling, and maintenance facilities. As an integral part of the national power grid, railway power systems exhibit distinct characteristics of both electrical power engineering and
Echo
11/26/2025
Application of Condition Monitoring Technology in UHV Transmission Lines
Application of Condition Monitoring Technology in UHV Transmission Lines
1. Application of Condition Monitoring Technology in UHV Transmission LinesAt present, the main characteristics of UHV (Ultra-High Voltage) transmission line condition monitoring technology in China are reflected in the following aspects: Comprehensiveness: In general, during the implementation of monitoring technology, supporting facilities and integrated systems are required to ensure effective monitoring performance; High value: UHV transmission line condition monitoring technology is a criti
Echo
11/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.