Test for Thickness of Insulation of Power Cable

Encyclopedia
09/05/2024

Definition of Insulation Thickness Test


A test to confirm the insulation and sheath thickness of power cables to ensure they meet specified standards.


Apparatus required to test for thickness of insulation of Power Cable


This is purely a measurement process, hence the apparatus for the test are to be chosen very carefully. There should be, a micrometer gauge capable of measuring at least 0.01 mm variation, a vernier caliper which can clearly read at least 0.01 mm count, a measuring microscope with linear magnification of not less than 7 times and the possibility of reading at least to 0.01 mm, and a graduated magnifying glass can read clearly at least 0.01 mm.409410dc42af76849681b9470765be15.jpeg

 

First, prepare different specimens for each measuring instruments and method. There are two types of specimens: core cable pieces and slice pieces.

 


10f101ebce836672e76455dd438d55aa.jpeg

Specimen Preparation


Specimens are cut from the cable and prepared for different measurement techniques.


Procedure for testing of Thickness of Insulation of Power Cable


Use pieces at least 300 mm long for round conductors and outer sheaths. Cut specimens from the final product and remove all coverings without damaging the insulation or sheath. Use slice pieces for optical measurements, removing outer and inner materials if needed. Cut slices thinly along the plane perpendicular to the cable axis. Preferably take measurements at room temperature. Measure the core and insulated core diameters with a micrometer gauge or vernier caliper, perpendicular to the cable axis.


Take measurements at three equal intervals along the specimen, about 75 mm apart for a 300 mm piece. Measure the inner and outer diameters of the insulation or sheath at each point. For accuracy, take two measurements at each point, totaling six measurements for both inner and outer diameters. Calculate the average outer diameter and inner diameter from these measurements. The average radial thickness of the insulation or sheath is the difference between the average outer and inner diameters, divided by two.


197d253084a18c65d262b00a412e35b8.jpeg

 


If visual inspection shows eccentricity, use the optical method by taking a slice section of the specimen.


In the case of sliced section the specimen is placed under a measuring microscope along the optical axis. For circular specimen 6 such measurements are taken along the periphery at a regular interval. For noncircular conductor, such measurement is done radially at each point where the thickness of insulation appears minimum. The numbers of slices are taken from a specimen at regular interval along its length in such a manner that the total of such measurement would be not less than 18. For example, in case of circular conductor, at least 3 slices are taken from a specimen and 6 measurements in each slice to be carried out. In case of noncircular conductor, the number of slices taken from a specimen depends upon the number of points of minimum thickness of insulation. As in this case measurement is only made at the minimum thickness points.


Cable Insulation Importance


Ensures the cable can safely handle voltage and mechanical stresses throughout its service life.


Calculation for Thickness of Insulation


For Core/Cable Piece

Where, Dout is the average of six measurements taken for outer diameter of the insulation/sheath. Where, Din is the average of six measurements taken for inner diameter of the insulation/sheath.

For Slice Piece – The average of 18 optical measurements is taken as the minimum thickness of insulation/sheath.

 

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Ground Wire in Overhead Transmission LinesThe ground wire (also called earth wire or OPGW) installed above phase lines in overhead transmission lines acts as a key protective and safety component. It provides lightning protection, ground fault defense, and helps prevent electrical system disruptions.In overhead transmission lines, positioning the ground wire above phase lines serves specific safety and performance purposes. Referred to as a "shield wire" or "static wire," this configuration has
Edwiin
06/04/2025
What is the Power Angle in a Power Transmission Line?
What is the Power Angle in a Power Transmission Line?
The power angle, denoted by δ, is the phase angle difference between two voltage levels in a power transmission line. Specifically, it represents the angular discrepancy between the sending-end voltage phasor and the receiving-end voltage (or between voltages at two bus points). In simpler terms, it quantifies the phase shift between voltage and current waveforms in the transmission line.Also referred to as the torque angle or load angle, this parameter is critical for two key reasons: it
Edwiin
06/04/2025
Comparison Between Overhead & Underground Transmission Systems
Comparison Between Overhead & Underground Transmission Systems
Key Differences and Comparison Between Underground and Overhead Power Transmission & DistributionPublic SafetyIn terms of public safety, underground systems outperform overhead transmission systems. With all transmission and distribution components buried, underground setups minimize risks from obstacles and external interference. Additionally, they are less susceptible to environmental factors like wind, storms, and heavy rain, making them inherently more secure.Initial CostUnderground syst
Edwiin
05/30/2025
Charging Current in Transmission Line
Charging Current in Transmission Line
Charging Current in Transmission LinesIn a transmission line, air serves as the dielectric medium between conductors. When voltage is applied to the sending end, current begins to flow between conductors due to the imperfect insulating properties of the dielectric. This current is known as the charging current of the transmission line.In other words, the current associated with the line capacitance is defined as the charging current. The magnitude of charging current depends on the line voltage,
Edwiin
05/23/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!