Understand the root causes of cable terminal overheating in high-power DC chargers. This guide covers electrochemical corrosion mechanisms, thermal expansion differences, and GB 50149 installation standards for Cu-Al transitions.
In the operation of high-power DC charging stations (120kW–360kW), site managers often encounter charred cable insulation, localized melting, or even equipment fires at the connection points. These failures typically occur where aluminum cables meet the copper busbars inside the charger.
Why do seemingly tight electrical connections fail and overheat under high-current loads? This article analyzes the physical and chemical triggers of terminal failure and provides a standardized installation framework to ensure long-term reliability and safety.
Copper and Aluminum have significantly different standard electrode potentials:
When these two metals are in direct contact in the presence of atmospheric moisture, they form a "galvanic cell." Aluminum, being the more reactive metal (the anode), undergoes rapid oxidation. This produces a layer of aluminum oxide (Al2O3Al2O3), which is a highly resistive insulator.
During high-load charging, temperatures rise, and the aluminum expands more than the copper busbar or the steel bolt. This causes the aluminum to undergo plastic deformation (creep). When the current stops and the joint cools, the aluminum contracts, leaving a microscopic gap that further increases resistance and oxidation for the next cycle.
To prevent galvanic corrosion, specialized transition hardware must be used.
Per GB 50149-2010 (Code for construction and acceptance of busbar device in electrical equipment installation):
"When connecting copper with aluminum or aluminum alloy terminals, copper-aluminum transition joints must be used."
After installation, the quality must be verified through thermal imaging during the first 24 hours of operation.