What Are the Common Failures of AIS Voltage Transformers?

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Hey everyone! I’m Felix, a 10-year veteran in the power system industry. Today, we’re going to dive into an important topic — what are the common failures of Air Insulated Switchgear (AIS) voltage transformers? How do you identify these issues, and how can they be resolved? Let’s get started!

1. Insulation Damage
The Problem You Might Encounter:

One of the most frequent issues is insulation damage. This typically happens due to aging insulation materials, overvoltage surges, contamination, or mechanical damage after prolonged operation.

How to Detect It?

  • Visual Inspection: Check for cracks on the casing and ensure that seals are intact.

  • Insulation Resistance Test: Use a megohmmeter to measure insulation resistance. If it’s below the standard value (e.g., 500 MΩ), there’s likely a problem.

Solutions

  • For minor aging or contamination, clean and locally repair the affected areas.

  • In cases of severe damage, replace the damaged insulation parts or even the entire unit.

2. Open Circuit on the Secondary Side
The Problem You Might Encounter

Another headache is an open circuit on the secondary side. This usually occurs because of wiring errors, poor connections, or faults in secondary equipment. When this happens, your protection system may fail, which is quite dangerous!

How to Detect It?

  • Check Wiring: Ensure all connections are tight and secure.

  • Use a Multimeter: Measure continuity in the secondary circuit. If there’s a break, you have an open circuit.

Solutions

  • Tighten loose connections and correct any wiring mistakes.

  • If the issue lies with the secondary equipment itself, repair or replace the faulty device.

3. Core Saturation
The Problem You Might Encounter

When the magnetic flux density in the core exceeds its saturation point, core saturation occurs. This results in significant measurement errors, affecting the accuracy and reliability of the system.

How to Detect It?

  • Observe Output Signals: If you notice unstable or unusually large output signals from the voltage transformer, it might be experiencing core saturation.

  • Professional Testing: Use specialized instruments like harmonic analyzers to check the core's operational status.

Solutions

  • Adjust load conditions to avoid prolonged overload.

  • Consider replacing the voltage transformer with one suitable for higher voltage ratings if necessary.

4. Oil Leakage in Oil-Immersed Voltage Transformers
The Problem You Might Encounter

For oil-immersed voltage transformers, oil leakage is a significant concern. Aging or damaged seals can cause leaks, which not only affect insulation performance but can also lead to fires in extreme cases.

How to Detect It?

  • Regular Patrols: Look for signs of oil around the equipment.

  • Infrared Thermography: Sometimes small leaks invisible to the naked eye can be detected using infrared cameras.

Solutions

  • Promptly replace old seals.

  • In severe cases, shutdown for repairs or replacement of the entire unit may be required.

5. Excessive Error
The Problem You Might Encounter

Over time, due to manufacturing defects, wear, or environmental factors, the error in voltage transformers may exceed allowable limits. This impacts both metering accuracy and protective functions.

How to Detect It?

  • Regular Calibration: Perform calibration at specified intervals to ensure the error remains within acceptable limits.

  • Online Monitoring: Some advanced systems use online monitoring to track error trends in real-time.

Solutions

  • Calibrate or adjust voltage transformers that exceed error limits.

  • Replace units if they cannot meet requirements.

Conclusion

To sum up, common failures of AIS voltage transformers include insulation damage, open circuits on the secondary side, core saturation, oil leakage in oil-immersed units, and excessive error. Not only should we learn how to identify these issues, but we must also know how to effectively resolve them. Remember, prevention is always better than cure — regular maintenance, keeping the working environment clean and dry, installing appropriate overvoltage protection devices, and performing periodic error calibrations are key measures to ensure proper operation.

I hope this article helps fellow professionals! If you have any questions or want to share your experiences, feel free to leave a comment or send me a message. Let’s learn together and improve collectively!

— Felix

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.