RHD-145 dead-tank SF6 circuit breaker: 145kV, 2500-4000A, lightning impulse 650/750kV, 3s short-time 31.5-50kA, making peak 100-125kA. For 145kV outdoor substation primary circuits.

Updated2026.09
LanguageEnglish
FilePDF · 439.1 KB
Dead Tank Circuit-Breaker126/145 kV Dead Tank Circuit-BreakerDimension

Document description

RHD‑145 is outdoor dead‑tank SF6 circuit breaker adopting self‑blast arc‑extinguishing principle, three‑phase post porcelain insulator and pointer density relay. It has strict requirements for foundation static/dynamic load and base flatness. It complies with IEC 62271‑100 & GB/T 1984, with custom‑manufacturing and full project solutions available.

Related Products

Frequently asked questions

Foundation static load 23000 N; horizontal dynamic load 4000 N, upward vertical dynamic load 33000 N (including self‑weight). Foundation height difference ≤2 mm, base‑surface levelness tolerance ≤2 mm.

It complies with IEC 62271‑100 and GB/T 1984. It adopts self‑blast arc‑extinguishing, three‑phase post‑type porcelain insulators and pointer‑type SF6 density relay for outdoor substation application.