RHD-126/145 Dead Tank Circuit-Breaker
disegno · ROCKWILL

RHD-126/145 Dead Tank Circuit-Breaker

RHD-145 dead-tank SF6 circuit breaker: 145kV, 2500-4000A, lightning impulse 650/750kV, 3s short-time 31.5-50kA, making peak 100-125kA. For 145kV outdoor substation primary circuits.

Ultimo aggiornamento2026.09
LinguaEnglish
FilePDF · 439.1 KB
Dead Tank Circuit-Breaker126/145 kV Dead Tank Circuit-BreakerDimension

Descrizione documento

RHD‑145 is outdoor dead‑tank SF6 circuit breaker adopting self‑blast arc‑extinguishing principle, three‑phase post porcelain insulator and pointer density relay. It has strict requirements for foundation static/dynamic load and base flatness. It complies with IEC 62271‑100 & GB/T 1984, with custom‑manufacturing and full project solutions available.

Prodotti correlati

Domande frequenti

Carico statico della fondazione 23000 N; carico dinamico orizzontale 4000 N, carico dinamico verticale verso l'alto 33000 N (incluso il peso proprio). Dislivello della fondazione ≤2 mm, tolleranza di planarità della superficie di base ≤2 mm.

È conforme alle norme IEC 62271-100 e GB/T 1984. Adotta un sistema di estinzione dell'arco ad auto-soffiaggio, isolatori in porcellana di tipo a supporto trifase e un relè di densità SF6 con indicatore a lancetta per applicazioni in sottostazioni all'aperto.