I.Overview
Ania nga solusyon gamiton ang high-performance nga main control chip ug multi-module collaborative architecture aron makuha ang eksakto nga pagkuha, proseso, display, ug remote transmission sa three-phase power grid parameters, naa'y pagsalig sa real-time monitoring requirements sa power systems. Habang nagsiguro sa measurement accuracy, kini nga digital power meter maayo nga nahatagan og solusyon ang mga issue sa interference pinaagi sa daghang teknikal nga innovation ug gin-optimize ang production costs.
II. Overall Meter Structure and Function
System Architecture
Nagamit og architecture model nga "main control chip as the core, multi-module collaboration" aron mapahimulos ang integrated functions sa data acquisition, processing, display, ug transmission.
Core Module Functions
- Main Control Chip Module
- Core Device: MSP430F5438A chip
- Integrated Functions: AD conversion circuit, high-frequency crystal oscillator circuit, low-frequency crystal oscillator circuit
- Main Responsibilities: Controlling system modules and processing data signals
- Special Design: Ang low-frequency crystal oscillator circuit adunay built-in compensation capacitors; ang main frequency input is solely connected to a 32768Hz low-frequency crystal.
- Signal Acquisition Circuit Module
- Voltage Acquisition: Three-phase grid voltage attenuation voltage divider circuit
- Current Acquisition: Three-phase current transformers
- Signal Conditioning: Operational amplifier circuit (amplification and level conversion)
- Channel Configuration: Voltage analog sampling channels, current analog sampling channels
- Function: Achieves precise acquisition of three-phase voltage and current signals.
- Auxiliary Function Modules
- Real-Time Clock (RTC): Provides a precise time base, ensuring data timestamp accuracy.
- Internal Information Memory: Stores meter operation parameters and acquired data, supports content modification.
- Display Control Module: Displays power grid parameters, equipped with anti-interference protection.
- Communication Interface: RS485 interface, supports connection to remote monitoring computers for real-time data upload.
- Power Supply Module: Multi-level power output
- 5V Output: For signal acquisition circuit module.
- 3.3V Output: For main control chip, RTC, memory, display control module.
- Isolated 5V Output: For communication interface.
III. Core Technical Improvements and Advantages
- Neutral Line Interference Solution
- Traditional Issues
- Ang neutral line kinahanglan nga mopasabot sa 4 resistors nga total resistance 1.496MΩ.
- Ang neutral line conductor susceptible to interference when floating.
- Abnormal three-phase voltage display when no voltage is applied.
- Unstable data, affecting sampling and metering accuracy.
- Improved Design
- Ang neutral line sa voltage analog sampling channel directly connected to the system ground.
- Technical Advantages
- Completely resolves neutral line interference issues.
- Eliminates 4 neutral line resistors, simplifying circuit design.
- Reduces production difficulty and cost.
- Anti-EFT Interference Design
- Design Solution
- An anti-EFT module is placed between the display control module and the main control chip.
- The module consists of 4 capacitors (C1-C4), corresponding one-to-one with the communication signal lines.
- Capacitor Specifications: C1, C3, C4 are 10000pF; C2 is 3300pF.
- One end of the capacitor is connected to the signal line, the other end is grounded.
- Technical Advantages
- Provides effective protection for each communication signal line.
- Passes 4kV EFT immunity test.
- Possesses strong anti-EFT capability.
- Anti-Electrostatic Discharge and Clock Stability Optimization
- Crystal Oscillator Configuration
- The main frequency input of the main control chip is solely connected to a 32768Hz low-frequency crystal.
- The chip's internal low-frequency oscillator circuit has built-in compensation capacitors.
- Triple Advantages
- ESD Performance: Passes 15kV air discharge ESD test, operates stably.
- Clock Accuracy: Generates a seconds clock through frequency division, ensuring ADC sampling clock stability.
- Circuit Simplification: Eliminates the external AD conversion circuit and 2 crystal oscillator compensation capacitors.
IV. Overall Technical Effectiveness
- Functional Realization
- Stably completes the acquisition and processing of three-phase grid voltage and current signals.
- Real-time data display function.
- Real-time data upload to monitoring computers via the RS485 interface.
- Meets the real-time monitoring needs of the power sector.
- Performance Improvements
- Effectively resolves three core issues: neutral line interference, electrostatic interference, and EFT interference.
- Significantly improves data acquisition and metering accuracy.
- Greatly enhances equipment operational stability.
- Cost Optimization
- Eliminates multiple resistors, capacitors, and the external AD conversion circuit.
- Simplifies production process, reduces production difficulty.
- Reduces manufacturing costs, possessing high engineering application value.
V. Application Value
Ania nga digital power meter solution, pinaagi sa innovative circuit design ug anti-interference technology, nakamit ang high-performance, high-reliability power parameter monitoring. Sa parehas nga oras, gi-optimize ang product cost structure, naghatag og competitive technical product alang sa power system monitoring field, suitable for various industrial power monitoring scenarios.