1. Buhatan sa Solusyon
- Produkto: KYN28 Indoor Metal-Clad Withdrawable Switchgear
- Boltahan: 3.6kV, 7.2kV, 12kV, o 24kV (Piliin batas sa sistema voltaje)
- Paggamit: Distribusyon ng planta ng kuryente, pagtanggap/pagpapadala ng substation, industriyal na planta ng kuryente, pagsisimula ng malaking HV motor.
- Pangunahing Bentahe: Sentral na disenyo ng pagkuha para sa bahagi ng de-energization sa panahon ng pag-aayos, minimisa ang downtime.
2. Puntod ng Teknikal na Espekisipikasyon
|
Parameter
|
Halaga
|
|
Rated Voltage (kV)
|
3.6 / 7.2 / 12 / 24
|
|
Rated Frequency (Hz)
|
50 / 60
|
|
Rated Current (A)
|
630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000
|
|
Rated Short-Circuit Breaking Current (kA)
|
20 / 25 / 31.5 / 40
|
|
Rated Short-Time Withstand Current (4s) (kA)
|
20 / 25 / 31.5 / 40
|
|
Power Frequency Withstand (1 min)
|
Dry: 34-65kV (iba-ibang voltaje) Wet: 28-50kV (iba-ibang voltaje)
|
|
Lightning Impulse Withstand (kV)
|
75-125kV (iba-ibang voltaje)
|
|
Protection Class (Housing)
|
IP4X
|
|
Ambient Temperature
|
-15°C hanggang +40°C
|
|
Max. Installation Altitude
|
1000m
|
|
Mechanical Life (Circuit Breaker)
|
VS1/VD4: 10,000 ops VSM: 100,000 ops
|
3. Pangunahing Katangian sa Disenyo
- Armored Compartmentalization: Apat na buong nahahati metal compartments (Busbar, Breaker, Cable, Instrumentation) para sa enhanced safety (IEC 298 / GB 3906-91 compliant).
- Centralized Draw-Out: Breaker (halimbawa, VD4, VS1, 3AH3) na naka-mount sa isang withdrawable truck. Nagbibigay ng "hot" busbar maintenance nang walang full system shutdown.
- Modular & Flexible: Standard widths (800mm/1000mm) nagbibigay ng madaling pag-combine ng functional units (incomer, feeder, metering, PT).
- Special CT Design: Nagpapahusay ng front-end wall-mounting at maintenance access.
- High-Performance Components: Mas mahusay na insulating materials & conductive elements sigurado ang stability sa panahon ng fault conditions.
- Compatibility: Sumusuporta sa pangunahing vacuum breakers (VS1, ABB VD4, Siemens 3AH3, GE VB2, ROCKWILL VSM).
4. Pisikal na Layout & Dimensyon
(Piliin batas sa Rated Current & Configuration)
|
Cabinet Width (A)
|
Depth (B) (mm)
|
Height (mm)
|
Typical Weight (kg)
|
Recommended Use Case
|
|
650 mm
|
1400 mm
|
2200 mm
|
700
|
<1250A, Compound Insulation, Front Cable Access
|
|
800 mm
|
1500 mm
|
2200 mm
|
800
|
<1250A, Air Insulation, Front Cable Access
|
|
800 mm
|
1600 mm
|
2200 mm
|
900
|
<1250A, Rear Overhead Line
|
|
1000 mm
|
1500 mm
|
2200 mm
|
1100
|
**>1250A, Front Cable Access**
|
|
1000 mm
|
1600 mm
|
2200 mm
|
1200
|
**>1250A, Rear Overhead Line**
|
|
900 mm
|
1700 mm
|
2200 mm
|
1000
|
Specific config (e.g., with Siemens 3AH5)
|
Note: Height may reduce to 1660mm for 1000mm wide cabinets with rear overhead lines >1600A.
5. Pagpipili ng Component
- Circuit Breaker Options:
- VS1/VD4/3AH3: Standard choice (10k ops).
- VSM Magnetic Actuator: Ultra-long life (100k ops) for frequent switching.
- Instrumentation: Special CTs for front access, VTs, surge arresters, relay protection devices (overload, short-circuit, earth fault).
- Busbars: Main & branch busbars rated equal to circuit current.
- Earthing: Integral earthing switch.
6. Implementasyon & Serbisyo
- Specification: Define voltage, current, SC rating, breaker type, and layout (front/rear cable access).
- Customization: ROCKWILL provides tailored solutions (design, assembly, testing).
- Installation: Requires stable environment (<1000m, -15°C to +40°C, <95% humidity). No corrosive gases/vibration.
- Commissioning: Functional & safety checks per IEC/GB standards.
- Maintenance: Utilize draw-out feature for partial de-energization. Minimal maintenance due to robust design.
- After-Sales Support:
- Technical guidance via: Tel: +86 (577) 27869969
- Email support: support@rockwill.com
- Resources: https://www.cnrockwill.com
7. Bakit Pumili ng Ito?
- Safety: Segregated compartments, front-access CTs, compliance with IEC/GB/DL standards.
- Reliability: High-quality components, proven design, comprehensive testing.
- Minimal Downtime: Draw-out breaker enables partial maintenance without shutdown.
- Flexibility: Modular design simplifies expansion/modification.
- Global Support: ROCKWILL’s 20+ years of expertise and direct technical support