1. Brevis Expositio Solutionis
- Productum: KYN28 Armatura Metallina Extractibilis pro Interiori Usu
- Tensio: 3.6kV, 7.2kV, 12kV, aut 24kV (Selecta ex Tensione Systematis)
- Applicatio: Distributio in Centris Electricitatis, Receptio/Transmissio in Substationibus, Distributio Electricitatis in Plantis Industrialibus, Initiatio Magnorum Motorum HV.
- Principale Praestantiae: Design Centralizatum Extractibile pro Partiali Exclusione Energiae Durante Manutenctione, Minimizans Tempus Inoperativum.
2. Nucleares Specificationes Technicae
|
Parametri
|
Valores
|
|
Tensio Nominalis (kV)
|
3.6 / 7.2 / 12 / 24
|
|
Frequens Nominalis (Hz)
|
50 / 60
|
|
Currentus Nominalis (A)
|
630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000
|
|
Currentus Interrumpendi Nominalis (kA)
|
20 / 25 / 31.5 / 40
|
|
Currentus Sustinendi Nominalis (4s) (kA)
|
20 / 25 / 31.5 / 40
|
|
Tolerantia ad Tensionem Nominalis (1 min)
|
Siccum: 34-65kV (Variat Secundum Tensionem) Humidum: 28-50kV (Variat Secundum Tensionem)
|
|
Tolerantia ad Impulsus Fulminis (kV)
|
75-125kV (Variat Secundum Tensionem)
|
|
Gradus Protectionis (Carcas)
|
IP4X
|
|
Temperatura Ambientalis
|
-15°C ad +40°C
|
|
Altitudinis Maxima Installationis
|
1000m
|
|
Vita Mechanica (Interruptor)
|
VS1/VD4: 10,000 operatones VSM: 100,000 operatones
|
3. Principales Characteristicae Designi
- Compartmentalizatio Armata: Quattuor Compartimenta Metallica Plene Segregata (Busbar, Interruptor, Cabel, Instrumentum) pro Augmentata Securitate (Conformiter IEC 298 / GB 3906-91).
- Design Centralizatum Extractibile: Interruptor (e.g., VD4, VS1, 3AH3) Fixus in Carro Extractibili. Facit "Calorem" Manutenctionis Busbaris sine Totali Exclusione Systematis.
- Modularis & Flexibilis: Latitudines Standard (800mm/1000mm) Permittunt Facile Combinandum Unitatum Functionalium (Incomer, Feeder, Metering, PT).
- Specialis Design CT: Facilitat Montagem Frontalem et Accessum Manutenctionis.
- Componentes Altae Performance: Materialia Insulantia Superiora & Elementa Conductiva Certificant Stabilitatem Sub Conditionibus Defectus.
- Compatibilitas: Supportat Principales Interruptores Vacui (VS1, ABB VD4, Siemens 3AH3, GE VB2, ROCKWILL VSM).
4. Dispositio Physica & Dimensiones
(Selecta ex Currentu Nominali & Configuratione)
|
Largitudo Armarii (A)
|
Profunditas (B) (mm)
|
Altitudo (mm)
|
Pes Typicalis (kg)
|
Usus Recommandatus
|
|
650 mm
|
1400 mm
|
2200 mm
|
700
|
<1250A, Isolatio Composita, Accessus Cabellus Frontalis
|
|
800 mm
|
1500 mm
|
2200 mm
|
800
|
<1250A, Isolatio Aeris, Accessus Cabellus Frontalis
|
|
800 mm
|
1600 mm
|
2200 mm
|
900
|
<1250A, Linea Overhead Posterior
|
|
1000 mm
|
1500 mm
|
2200 mm
|
1100
|
**>1250A, Accessus Cabellus Frontalis**
|
|
1000 mm
|
1600 mm
|
2200 mm
|
1200
|
**>1250A, Linea Overhead Posterior**
|
|
900 mm
|
1700 mm
|
2200 mm
|
1000
|
Configuratio Specifica (e.g., cum Siemens 3AH5)
|
Nota: Altitudo Potest Reduci ad 1660mm pro Armariis Largis 1000mm cum Linea Overhead Posterior >1600A.
5. Selectio Componentum
- Optiones Interruptoris:
- VS1/VD4/3AH3: Optio Standard (10k operatones).
- VSM Actuator Magneticus: Ultra Longa Vita (100k operatones) pro Frequenti Commutatione.
- Instrumenta: Specialis CTs pro Accessu Frontali, VTs, Arrestatores Fulminis, Dispositiva Protectionis Relais (Supercarga, Circuito Corto, Defectus Terre).
- Busbars: Busbars Principales & Ramificati Rating Equalis Currenti Circuiti.
- Terre: Interruptor Terre Integralis.
6. Implementatio & Servitium
- Specification: Definire Tensionem, Currentum, Rating SC, Typum Interruptoris, et Dispositionem (Accessus Cabellus Frontalis/Posterior).
- Customizatio: ROCKWILL Proponit Solutiones Tailored (Design, Assemblage, Testing).
- Installation: Requiret Ambiens Stabile (<1000m, -15°C ad +40°C, <95% Humiditas). Nullae Gases Corrosivae/Vibrationes.
- Commissioning: Controles Functionales & Securitatis Secundum Standards IEC/GB.
- Manutentio: Utilizare Feature Extractibile pro Partiali Exclusione Energiae. Minima Manutentio Propter Robustum Design.
- Supportus Post-Venditionem:
- Guidance Technica per: Tel: +86 (577) 27869969
- Supportus Email: support@rockwill.com
- Resources: https://www.cnrockwill.com
7. Cur Hoc Solutionem Eligere?
- Securitas: Compartimenta Segregata, CTs Accessus Frontalis, Conformitas Cum IEC/GB/DL Standards.
- Reliabletas: Componentes Altae Qualitatis, Design Probatus, Testing Comprehensivum.
- Minima Tempora Inoperativa: Interruptor Extractibilis Facit Partialem Manutenctionem Sine Exclusione Totali.
- Flexibilitas: Design Modularis Simplificat Expansionem/Modificationem.
- Supportus Globalis: Expertise 20+ Anni ROCKWILL et Directus Supportus Technicus