| Brand | ROCKWILL |
| Series | JDS |
| Rated system voltage | 10kV-35kV |
| Connection group | ZNyn11 |
| Rated frequency | 50 / 60 Hz |
Product Overview
As a pioneer and the first dedicated original equipment manufacturer (OEM) in China's neutral grounding transformer industry, we have laid the original benchmark for the industry's development with our profound technical strength accumulated through decades of intensive cultivation. From the independent R&D of core technologies to large-scale mass production, we have built a full-process independently controllable system. Relying on our stable and leading product performance and unparalleled reliability, we have become a preferred partner in the field of power grid construction.
Rockwill delivers reliable and high-performance earthing transformers designed for 66kV power systems. Our oil-immersed transformers are engineered to provide stable neutral grounding solutions while ensuring operational safety and system protection. Manufactured in compliance with international standards including IEC and GB, these transformers incorporate premium materials and rigorous quality control throughout production.
Basic Info.
Some of these earthing transformers cover voltage levels including:3.3kV / 6kV / 11kV / 15kV / 20kV / 22kV / 30kV / 33kV / 34.5kV / 36kV / 44kV / 66kV / 88kV / 110kV / 132kV / 145kV / 150kV / 220kV / 275kV / 330kV / 400kV, etc. The current withstand time ranges from 1s, 2s, 3s, 5s, 6s, 8s, 9s, 10s, 30s, 60s, 1hour to 2hours, and customization is available.
Parameter |
Detail |
Parameter |
Details |
Cooling Method |
Oil-Immersed Type Transformer |
Core |
Core-type Transformer |
Certification |
ISO9001 |
Usage |
Power Transformer |
Frequency Characteristics |
Power Frequency |
Shape of Core |
Ring |
Brand |
Rockwill |
Item |
3 Phase Oil Type Earthing 6kv Power Transformer |
Primary Voltage |
66kv |
Secondary Voltage |
0.4kv |
Rating Capacity |
350kVA |
Transformer |
66kv Power Transformer |
Iron Core |
Wounded Core |
Coil Structure |
Isolation |
Loss |
Low Losses |
Tank Design |
Sealed |
Specification |
CTQC type tested |
Transport Package |
Wooden Case |
Origin |
Zhejiang China |
Trademark |
Rockwill |
Key Features
Voltage Class: 66kV system voltage (200 BIL)
Capacity Range: Standard units from 100kVA to 10,000kVA
Winding Configuration: Optimized zigzag (ZNyn) design
Cooling System: ONAN/OFAF cooling options
Insulation: Mineral oil or synthetic ester fluid
Construction:
Corrugated tank or radiator cooling
Hermetically sealed or conservator tank options
CRGO silicon steel core
Copper/aluminum windings
Technical Advantages
Enhanced Safety: Built-in Buchholz relay and pressure relief device
Low Impedance: Zero-sequence impedance <15Ω for effective fault current management
Durability: Corrosion-resistant paint system for outdoor installations
Efficiency: Reduced no-load losses through optimized core design
Flexibility: Off-circuit tap changer (±5% in 2.5% Steps)
Typical Applications
Utility Networks:
Neutral grounding for 66kV transmission systems
Arc suppression coil connections
Resistance grounding systems
Industrial Plants:
Petrochemical facilities
Mining operations
Steel manufacturing plants
Renewable Energy:
Wind farm collector stations
Solar PV substations
Hydroelectric plants
Performance Specifications
Temperature Range: -30°C to +40°C Ambient
Humidity: ≤95% Monthly Average
Altitude: Up to 2000m ASL
Sound Level: ≤75dB at 1m
Efficiency: ≥99.2% at Full Load
Testing Protocol
All units undergo comprehensive testing including:
Zero sequence impedance measurement
Induced overvoltage test (260Hz)
Lightning impulse test (350kV)
Temperature rise test (65K max.)
Oil dielectric strength test (≥50kV)
Service Conditions
Suitable for indoor/outdoor installation
Wind resistant up to 35m/s
Non-explosive environments
Seismic capability: 0.3g horizontal acceleration
Application Fields
66kV/88kV/110kV/132kV Power Distribution Network Construction
New Energy Power Plants (e.g., Wind Power/Photovoltaic)
Power Distribution Stations in Large Industrial Parks
Railway Traction Power Supply Systems
Urban Power Grid Upgrading and Renovation Projects
High-Voltage Power Supply Systems for Industrial and Mining Enterprises
Grounding Protection Projects of Regional Substations
Rockwill ZNyn11 zigzag earthing transformer is built to create a stable artificial neutral point for delta-connected or ungrounded medium voltage power grids ranging from 10kV to 35kV.
It provides a reliable dedicated path for single-phase earth fault current, effectively suppressing arc grounding overvoltage and ferromagnetic resonance overvoltage while balancing three-phase phase voltages.
This equipment can be matched with Petersen arc suppression coils or neutral grounding resistors, which is essential for earth fault detection and relay protection in distribution networks, photovoltaic and wind farm grid interconnection systems.
This JDS zigzag earthing transformer covers standard system voltages including 10kV, 15kV, 20kV, 33kV and 35kV. Its capacity range spans from 30kVA up to 10,000kVA.
Key electrical parameters such as zero-sequence impedance, short-time fault withstand duration and insulation levels are not fixed; we can adjust all these indicators precisely according to your project’s earth fault protection scheme and local grid requirements.
Yes, an optional 0.4kV auxiliary winding with a maximum capacity of 500kVA is available for selection. With this optional winding design, the earthing transformer realizes dual functions.
It not only undertakes the core neutral grounding task for the medium voltage system, but also serves as a station service transformer to supply local low-voltage loads inside the substation.
This integrated design helps customers reduce procurement costs and save installation space on site.
We offer two mainstream cooling configurations: ONAN, natural oil natural air cooling, which suits most conventional indoor and outdoor installation scenarios; and ONAF, oil natural air forced cooling, recommended for high-load working conditions or areas with high ambient temperature.
The transformer supports both indoor and outdoor installation. You can also choose an IP-rated protective cabinet, together with integrated CT, VT or isolation switch, to form a complete factory pre-assembled unit and lower the workload for EPC contractors during field installation.
Absolutely. We are a direct Chinese source manufacturer of Z-type earthing transformers with mature OEM and ODM capabilities.
You can customize multiple items including voltage class, zero-sequence impedance value, cooling mode, auxiliary winding configuration, surface paint standard, enclosure structure and factory test reports.
We can also adjust our design and documentation to comply with IEC standards and regional grid specifications, catering to the demands of EPC companies, electrical distributors and large power investors.