Search


69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

  • 69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

Key attributes

Brand ROCKWILL
Series RHD
Rated maximum voltage 72.5kV
Rated maximum current 2000~3150 A
Lightning impulse withstand voltage 325/375
Rated short-circuit breaking current 31.5~50 kA
Rated frequency 50/60 Hz
Description

Description

69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker is suitable for the rated voltage of 66kV, the rated frequency of 50Hz of the high-voltage transmission and transformation system, through the distribution and combined load current, interrupt the fault current, to achieve the control, measurement and protection of the transmission line, the product structure is compact, the area is small, especially suitable for earthquake-prone areas, polluted areas and areas with relatively small space size. The circuit breaker has excellent breaking performance, and the rated short-circuit breaking current can reach 63kA; The product is easy to install and maintain.

Main Features

  • Excellent breaking performance and long electrical life (>20 operations).

  • Long mechanical life (10,000 cycles), reliable operation, frequent operability, low noise, simple structure, and long maintenance-free period.

  • Low center of gravity, suitable for seismic-prone areas.

  • Out-of-step breaking capability, usable as a tie circuit breaker.

  • Configurable built-in CTs per user requirements, with up to 15 current transformers for measurement or protection.

System Architecture

The gas-insulated metal composite combined electrical appliance (HGIS) is composed of several standard functional modules, such as circuit breaker GCB (single and double busbars), isolation-grounding switch TPS, voltage transformer PT, current transformer CT, etc. These modules have the same interface form and size. Various modules can be combined to meet the design and layout requirements of various substations.

69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

Single-busbar single-isolation scheme69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

Single-busbar double -isolation scheme69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

 

Main characteristics:

electrical

 Voltage Ratings: 3.6kV, 4.76kV, 7.2kV, 8.25kV, 11kV, 12kV, 13.2kV, 13.8kV, 15kV, 15.5kV, 17.5kV, 22kV, 22.9kV, 24kV, 25.8kV, 27kV, 33kV, 36kV, 38kV, 40.5kV, 44kV, 60kV, 63kV, 66kV, 69kV, 88kV, 115kV, 123kV, 125kV, 126kV, 132kV, 138kV, 145kV, 150kV, 170kV, 184kV, 204kV, 220kV, 225kV, 230kV, 245kV, 275kV, 330kV, 345kV, 400kV, 765kV, 800kV with a rated short-circuit breaking current of 50kA or 63kA, and we offer customization services.

Item Unit Parameters
Rated maximum voltage kV 72.5
Rated maximum current A 1600/2500/3150/4000
Rated frequency Hz 50/60
1min Power frequency withstand voltage kV 185
Lightning impulse withstand voltage kV 450
First open pole factor
1.5/1.5/1.3
Rated short circuit breaking current kA 25/31.5/40/50/63
Rated short - circuit duration s 4/3
Rated out - of - phase breaking current
10
Rated cable charging current
10/50/125
Rated peak value withstand current kA 80/100/125
Rated making current (peak) kA 80/100/125
Creepage distance mm/kV 25 - 31
SF6 gas leakage rate (per year)
≤1%
Rated SF6 gas pressure(20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.45
SF6 annual gas leakage rate
≤0.5
Gas moisture content Ppm(v) ≤150
Heater voltage
AC220/DC220
Voltage of control circuit DC DC110/DC220/DC230
Voltage of energy - store motor V DC 220/DC 110/AC 220/DC230
Applied standards
GB/T 1984/IEC 62271 - 100

mechanical

Name unit Parameters
Opening time ms 27±3
Closing time ms 90±9
Minute and conjunction time ms 300
Together--ivide the time ms ≤60
Simultaneity of opening ms ≤3
Closing simultaneity ms ≤5
Moving contact stroke mm 150+2-4
Contact contact stroke mm 27±4
Opening speed m/s 4.5±0.5
Closing speed m/s 2.5±0.4
Mechanical life times 6000
Operation sequence
O - 0.3s - CO - 180s - CO
Note: The opening and closing speed and time are the characteristic values of the circuitbreaker when it is single divided and closed under rated conditions. The closing speed is theaverage speed of the moving contact from the rigid closing point to 10 ms before closing, andthe opening speed is the average speed of the moving contact within 10 ms from the justequinox to 10 ms after the separation.

Product use environment

  • Place of use: outdoor.

  •  Ambient air temperature: -40℃~ +40℃

  • Altitude: no more than 1000m.

  • Air pollution level: Class IV.

  • Wind pressure: not more than 700Pa (equivalent to wind speed 34 m/s).

  • Earthquake level: no more than 9 degrees.

  • Relative humidity: the average daily relative humidity is not more than 95%; The average monthly relative humidity is not more than 90%.

Note: When the use conditions of the circuit breaker exceed the above provisions, it shall be determined by the user and the manufacturer through negotiation.

Solutions - Dead Tank Circuit Breaker

  • South Africa Regional Dead Tank SF6 Circuit Breaker Solution Report
    Ⅰ. Project BackgroundAs the first African country adopting dead tank SF₆ circuit breaker technology, South Africa's grid system faces these challenges: Aging Dead Tank SF₆ Circuit Breakers:Existing high-voltage circuit breakers exhibit severe aging, particularly legacy dead tank SF₆ circuit breakers with increased failure rates. Dead Tank SF₆ Circuit Breaker Limitations:In high-altitude regions (>2,000m), conventional dead tank SF₆ circuit breakers experience insulation degradation from low-t

Case Studies - Dead Tank Circuit Breaker

  • Rockwill Dead Tank Circuit Breakers Empower Intelligent Retrofit of 72.5kV Substations in Extremely Cold Regions
    High‑voltage circuit breakers are vital cornerstones for stable power supply in frigid alpine regions.Extremely low temperatures easily trigger SF₆ liquefaction and mechanism failure for conventional substation equipment.Project OverviewIn the intelligent transformation project of a 72.5kV substation in the alpine region of Hulunbuir, Inner Mongolia, our company’s RMR-72.5/126 SF₆ circuit breaker was successfully commissioned. Facing extreme winter temperatures of -40°C, the product utilizes a "
  • Rockwill 69 kV Dead Tank Circuit Breakers have been integral to smart substation upgrades, achieving near-perfect power supply reliability.
    Dead‑tank circuit breakers serve as key equipment guaranteeing safe operation of smart substations.Coastal high‑salt‑humidity environments raise stringent requirements for equipment reliability and environmental adaptability.Project OverviewDeployed in a 110kV smart substation upgrade at a coastal industrial park in Guangdong Province, our RMR-72.5kV vacuum circuit breaker has delivered 24 months of zero-failure operation under high-salinity, high-humidity conditions and frequent switching deman
  • Case Study of Rockwill 72.5kV Dead Tank Circuit Breaker Project in South Africa
    Facing the stringent operational challenges of South Africa’s high-load industrial power grid, the 72.5kV fully enclosed dead-tank circuit breaker delivers robust performance to withstand intense solar radiation, dust and high temperatures. With superior insulation and high short-circuit breaking capacity, it builds a long-term high-voltage safety barrier for mining areas and main power grids.01 Project Overview1.1 Project BackgroundSouth Africa, as the most industrialized country in Africa with

Documentation Resource Library Dead Tank Circuit Breaker

RHB Hybird Switchgear Catalog
Restricted
RHB Hybird Switchgear Catalog RHB Hybird Switchgear Catalog
Selection Guide
English
PDF
RHD-40.5 Dead tank SF6 gas circuit breaker FLYER
Public
RHD-40.5 Dead tank SF6 gas circuit breaker FLYER RHD-40.5 Dead tank SF6 gas circuit breaker FLYER
Brochure
English
RHD-145 SF6 Gas Dead tank Circuit Breaker FLYER
Public
RHD-145 SF6 Gas Dead tank Circuit Breaker FLYER RHD-145 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
2026 RHD Dead tank SF6 gas circuit breaker
Restricted
2026 RHD Dead tank SF6 gas circuit breaker 2026 RHD Dead tank SF6 gas circuit breaker
Catalogue
English
PDF
Rockwill Electric Group Profile
Public
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English
RHD-72.5 SF6 Gas Dead tank Circuit Breaker FLYER
Public
RHD-72.5 SF6 Gas Dead tank Circuit Breaker FLYER RHD-72.5 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
RHD-170 SF6 Gas Dead tank Circuit Breaker FLYER
Public
RHD-170 SF6 Gas Dead tank Circuit Breaker FLYER RHD-170 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
RHD-245 SF6 Gas Dead tank Circuit Breaker FLYER
Public
RHD-245 SF6 Gas Dead tank Circuit Breaker FLYER RHD-245 SF6 Gas Dead tank Circuit Breaker FLYER
Brochure
English
RHD-72.5 SF6 Gas Dead tank Circuit Breaker
Public
RHD-72.5 SF6 Gas Dead tank Circuit Breaker RHD-72.5 SF6 Gas Dead tank Circuit Breaker
Drawings
English

Frequently asked questions

In a live tank breaker, the arc chamber is mounted at the top or side of the column, exposed to ambient air. In a dead tank breaker, the arc chamber is placed inside the metal tank, fully sealed.

 Live tank breakers are well-suited for outdoor high-voltage distribution with a dispersed layout. Dead tank breakers flexibly adapt to both indoor and outdoor applications, especially in space-constrained substations or where compact installation is required.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register