| Muhimmiya | ROCKWILL |
| Model NO. | Rukunin Bypass na Karamin Mounting Back Strap |
| Rated Voltage | 38kV |
| Raitidu kọ̀ọ̀kan | 600A |
| Rated Lightning Impulse Withstand Voltage | 150kV |
| Siri | BP3 |
An Chance Type BP3 Switches na ake amfani da shi don kawo gaba da reclosers da ake cikin tafiya, saboda haka za a iya yi yanayin kadan da ba ake rasa ƙarin. An samu waɗannan BP3 switches da 3 Pull Operation units, kuma zai iya kasancewa da single phase ko three phase units. Suna da ratings da dama 600A ko 900A, da Voltage Classes da dama 15, 27, 38kV, da Insulation levels 110kV, 125kV ko 150kV BIL. Idan an yi aiki da blades a ƙarfin ƙarshe, ana kawo gaba da recloser da kaɗe suka fiye da distribution system. Zai iya sauya a Cross Arms ko zai iya sauya zuwa tafiya ta hanyar Pole Mount Bracket Option. Zai iya kafa shi don Right Hand ko Left Hand opening, da kuma Angled ko Non Angled Bypass Blades. Babu ake amfani da BP3 switches don kawo gaba da Voltage Regulators saboda babu ake amfani da shi don kawo gaba da circulating current a regulator windings. Chance: The Brand and Quality You Can Trust!!
Fully Compliant with ANSI/IEEE C37.30.1
15, 27 and 38kV ratings
110, 125 and 150kV BIL ratings
600A and 900A ratings
ESP Polymer 2.25” Bolt Circle Insulator Assemblies
Right Hand and Left Hand opening Options
Non-Angled and Angled Bypass Blade Options
Cross arm or Pole Mount Options
3 Phase on 100” or 124” Cross Arms in Steel or Fiberglass
Principal Application: Recloser Maintenance
By design, the BP3 Switch provides an economical means for bypassing and disconnecting a pole-mounted distribution recloser. This permits de-energized periodic maintenance of the recloser without interrupting service. The BP3 Switch accomplishes this by a combination of three disconnect switches mounted on a common base. By operating the blades in proper sequence, the recloser is bypassed and isolated from the distribution system.
Operation
Figures below illustrate the BP3 Bypass Switch operation. In normal operation, the bypass switchblade is open and the two disconnect blades are closed, allowing the recloser to be in the circuit.
When recloser maintenance, testing, repair or removal isrequired, first close the bypass blade to provide a parallel current path. Then open the recloser’s internal contacts. And last, open both disconnect blades of the bypass switch. In this way, service continuity is maintained and the recloser is isolated from the line. To put the recloser back in service, the switch operating procedure is reversed.
Parameters