| Marca | RW Energy | 
| Numerus Modeli | Circuitus Interruptor Limitans Currentum Altam/Currentum Limitans Circuitus Brevis(FCL) | 
| Votum nominatum | 20kV | 
| currus electricus nominatus | 1250A | 
| Frequenta nominata | 50/60Hz | 
| Series | DDXK | 
Componentis protectivus nuclearis pro systematibus electricis magnae capacitatis (retes 35kV-220kV, areae industriales), FCL responde in ≤10ms ad defectus circuitus brevis. Limitat currentem defectus ad 15%-50% valoris expectati ante fracturam securam, protegens generatores/transformatores. Supportans ratings currentis 630A-4000A, id convenit systematibus AC/DC et integratur cum apparatu commutationis pro operatione retis stabilis.
Characteristica
Interruptio Celeris: Operatur et interrumpit currentem defectus in parte frontali primi semicycli frequentiae potentiae defectus—longe antequam currentis ascendat ad suum culmen. Tempus interruptionis totale est 2–5 ms, fere 10–20 vicibus celerius quam interruptores circuitus consuetudinarii.
Limitatio Currentis Interruptiva: Incipit limitare currentem defectus 1 ms post defectum, et denique restricts currentem defectus ad 15%–45% valoris expectati.
Capacitas Interruptiva Magna: Amplitudo prospectiva rated short-circuit interruptionis currentis variat ab 63 kA ad 200 kA, dum amplitudo rated short-circuit interruptionis currentis interruptorum circuitus communium solito tantum attingit 40.5 kA ad 50 kA.
Sensor Currentis Rogowski Integratus: Praebet mensurationem accuratam, celeritatem responsionis velociorem, et potest disponi modo separato per phase aut integrari in armarios apparatorum commutationis.
Fides Alta: Una ex competitivis producti est fides eius eminentis. Designatio specialis et artificium asseverant fidem altam producti, quae verificata est et bene accepta in applicationibus in loco.
Parametri Principales
No.  |  
   Item  |  
   Unitas  |  
   Parametri Technici  |  
  |
1  |  
   Currentis Rated  |  
   A  |  
   630~6300  |  
  |
2  |  
   Voltage Rated  |  
   kV  |  
   7.2/12/20/40.5  |  
  |
3  |  
   Frequensia Rated  |  
   Hz  |  
   50/60  |  
  |
4  |  
   Rated Prospective Short - Circuit Breaking Current  |  
   kA  |  
   63/80/120  |  
  |
5  |  
   Niveles Insulationis Rated (Frequensia Potentiae / Fulgur)  |  
   7.2kV  |  
   kV  |  
   23/60 kV  |  
  
12kV  |  
   42/75 kV  |  
  |||
20kV  |  
   50/125 kV  |  
  |||
40.5kV  |  
   95/185 kV  |  
  |||
6  |  
   Tempus Interruptionis  |  
   ms  |  
   2~5ms  |  
  |
7  |  
   Currentis Interruptionis / Peak Value Prospective Short - Circuit Current  |  
   %  |  
   20~45  |  
  |
8  |  
   Resistensia DC Circuiti Principalis  |  
   μΩ  |  
   <40  |  
  |
9  |  
   Range Setting Currentis Operationis  |  
   kA  |  
   6kA~60kA  |  
  |
10  |  
   Rated Breaking Current of Fuse  |  
   kA  |  
   63/120  |  
  |
11  |  
   Rated Short - time Withstand Current of Main Circuit  |  
   kA/s  |  
   31.5/2  |  
  |
12  |  
   Rated Peak Withstand Current of Main Circuit  |  
   kA  |  
   80  |  
  |

Figura 4: Uti DDXK1 ut protectionis rapidae circuitus brevis pro generatoribus et transformatoribus
(a) Protectio rapidae circuitus brevis ad outlet 10kV/35kV lateris transformatorum
(b) Protectio rapidae circuitus brevis ad outlets generatorum
(c) Protectio rapidae circuitus brevis pro busbaris rami plantarum electricarum
(d) Protectio rapidae circuitus brevis ad outlets generatorum coniunctarum rete