| Muhimmiya | Wone | 
| Model NO. | Fusible links for expulsion fuse cutout | 
| Raitingi na Tansufa | 200kVA | 
| Tafiyar muhimmanci aiki na transformer | 11.55A | 
| Siri | Fuse Links | 
Amsa da karkashin bayanin :
Type K, type T, type H da type SLOW-FAST fuse link suna gina da testo kamar hukumomin duniya na baya IEC 60282-2:2008 & IEEE Std C37.41-2008 & IEEE Std C37.42-2009.
Fusible element ya yi amfani da kayayyakin silver-copper alloy.Amata ya yi amfani da teknologi masu zama da tsarin testo masu kyau don tabbatar da cikakken tsari na lokaci-waɗannan.
Fusible element an sanya da cable wire, kuma an haɓaka da high strength strain wire.Wadannan ya ba ta fiye sosai, hatta idan ana iya da shiga kamar yawan hakuri ko karshe mai zama.
Arc extinguishing tube ya taka alaƙar daidai a lokacin da fault na biyu waɗanda suke.
An yi amfani da Type K da Type T twin pigtails fuse link, Twin pigtails fuse link ya taka wani muhimmanci da kuma yana da karfi a fadada cutout fusen mafi yawa zuwa single pigtail fuse links. Twin pigtails an haɓaka a farkon attachment stud na kwararren da ke.
Parametoci Mai Tsabta:
Type K Fuse Links:


11-15kv Fuse link length 21'(533mm)
24-27kv Fuse link length 23'(584mm)
33-38kv Fuse link length 31'(787mm)
Type T Fuse Links:


11-15kv Fuse link length 21'(533mm)
24-27kv Fuse link length 23'(584mm)
33-38kv Fuse link length 31'(787mm)
Type H Fuse Links:


11-15kv Fuse link length 21'(533mm)
24-27kv Fuse link length 23'(584mm)
33-38kv Fuse link length 31'(787mm)
Type Slofast Fuse Links:


11kv Fuse link leght 21'(533mm)
27kv Fuse link leght 23'(584mm)
33kv Fuse link leght 31'(787mm)
Type K Fuse Link Selection For Using Of Distribution Transformer Protection.Fuse da aka zaba ana zaɓe kamar tsari na lokaci-waɗannan na transformer,ma'anarsu kamar rated current na transformer.

NOTE: Rated capacity of transformer <160kVA,rated current of the selected fuse links should be 2-3 times of the full load current of the transformer. Rated capacity of transformer >160kVA,rated current of the selected fuse links should be 1.5-2 times of the full load current of the transformer.