Key attributes

Brand ROCKWILL
Model NO. EHV Dead tank SF6 circuit breaker source manufacturer-800kV
Rated voltage 800kV
Rated normal current 5000A
Rated frequency 50/60Hz
Series RHD
Description

800kV Dead Tank SF6 Circuit Breaker is a high-performance ultra-high voltage device designed for critical power transmission systems. Featuring a robust dead tank structure, its live components are sealed in an SF6 gas-insulated metal casing, delivering superior arc extinction efficiency and dielectric strength to rapidly interrupt fault currents and ensure grid stability.

The low-center-of-gravity design enhances seismic resistance, adapting to extreme climates and rugged terrains. Integrated with bushings and current transformers, it supports multi-function control for real-time measurement and protective switching.

With a mechanical/electrical lifespan exceeding 30 years and a fully sealed design, maintenance frequency is minimized, cutting operational costs. Equipped with anti-misoperation interlocks and dual-insulation safeguards, it prioritizes personnel safety and system reliability. Ideal for UHV grids, power plants, and industrial applications, this breaker sets a benchmark for efficiency and durability in 800kV high-stress environments.

Main Features

  • Exceptional Arc Extinction and Insulation: Using SF6 gas as the medium, it enables rapid arc extinction and has strong insulation properties. It can quickly interrupt fault currents, ensuring stable operation under high - voltage conditions.

  • Robust Dead - tank Structure: With a dead - tank design, the live parts are sealed in a metal tank, providing resistance to vibration, dust, and moisture, and enabling adaptation to harsh environments.

  • Integrated Functional Configuration: Integrates components such as bushings and current transformers, with functions like measurement and protection, simplifying the system layout.

  • Long Service Life and Low Maintenance: Boasts long mechanical and electrical service lives. The sealed structure reduces component aging, resulting in a long maintenance cycle and low costs.

  • Multiple Safety Guarantees: Equipped with anti - misoperation interlocking devices and multiple insulation protections to ensure the safety of personnel and equipment.

Technical specifications

Rated voltage

kV

800kV

Rated current

A

5000

Rated frequency

Hz

50/60

Rated short - circuit breaking current

kA

50kA、63kA

Rated short - time withstand current and duration

kA/s

50/3

63/2

Rated peak withstand current

kA

135

171

Rated short - circuit making current

kA

135

171

Number of breaks

 

2

Rated lightning impulse withstand voltage (peak value)

To ground

kV

2100

Break

2750

Rated switching impulse withstand voltage (peak value)

To ground

kA

1550

Break

1950

Rated short - time power - frequency withstand voltage (effective value)

To ground

kA

960

Break

1420

Environmental Conditions

Ambient air temperature upper limit +40 °C
Ambient air temperature 24-hour average +35 °C
Ambient air temperature lower limit –25 °C
Altitude above sea level ≤ 1000 m
Relative humidity (24-hour average) ≤ 95%
Relative humidity (monthly average) ≤ 90%
Water vapor pressure (24-hour average) ≤ 2.2 kPa
Water vapor pressure (monthly average) ≤ 1.8 kPa
Solar radiation ≤ 1000 W/m²
Pollution level Level III

Application Scenarios

  • Large Power Plant Step-Up / Grid Connection
  • Metropolitan & Heavy-Load Supply Hubs 
  • Seismic / Extreme-Climate Sites

Documentation Resource Library Dead tank SF6 circuit breaker

Restricted
Dead Tank Circuit Breakers Catalog Dead Tank Circuit Breakers Catalog
Catalogue
English
PDF
Public
Rockwill Electric Group Profile Rockwill Electric Group Profile
Brochure
English

Frequently asked questions

The leakage rate of SF₆ gas must be controlled at an extremely low level, typically not exceeding 1% per year. SF₆ gas is a potent greenhouse gas, with a greenhouse effect 23,900 times that of carbon dioxide. If a leak occurs, it can not only cause environmental pollution but also lead to a decrease in the gas pressure within the arc quenching chamber, affecting the performance and reliability of the circuit breaker.

To monitor the leakage of SF₆ gas, gas leakage detection devices are typically installed on tank-type circuit breakers. These devices help to promptly identify any leaks so that appropriate measures can be taken to address the issue.

In a live tank breaker, the arc chamber is mounted at the top or side of the column, exposed to ambient air. In a dead tank breaker, the arc chamber is placed inside the metal tank, fully sealed.

 Live tank breakers are well-suited for outdoor high-voltage distribution with a dispersed layout. Dead tank breakers flexibly adapt to both indoor and outdoor applications, especially in space-constrained substations or where compact installation is required.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales