• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


DS7B 72.5kV 145kV 225kV 252kV 363kV 420kV 550kV 800kV High voltage disconnect switch supplier

  • DS7B 72.5kV 145kV 225kV 252kV 363kV 420kV 550kV 800kV High voltage disconnect switch supplier

Key attributes

Brand ROCKWILL
Model NO. DS7B 72.5kV 145kV 252kV 363kV 420kV 550kV 800kV High voltage disconnect switch supplier
Rated voltage 363kV
Rated normal current 3150A
Rated frequency 50/60Hz
Rated peak value withstand current 160kA
Rated short-time withstand current 63kA
Series DS7B

Product descriptions from the supplier

Description

Product introduction

DSDS7B series Switch Disconnector is a kind of outdoor HV electricity transmission equipment’s at three-phase AC frequency of 50Hz/60Hz. it is used for breaking or correcting HV lines under no loads so that these lines can be changed and connected and the way the electricity runs is changed. in addition, it can be used to exercise safe electrical insulation for such HV electric apparatuses as bus and breaker. The switch can open and close inductance/capacitance currant and is able to open and close the bus to switch current.

This product has three posts with horizontal open breaks. JW10 grounding switches may be attached to the product at one or two sides 72.5-252kV Switch Disconnector adopts C2 or SRCJ2 manual actuator to realize the tri-pole linkage. The earthing switch adopts CS11 or SRCR manual actuator to actualize tr-pole linkage,.363kV disconnect switch adopts SRCJ2 motor's actuator to realize the single pole operation; while the earthing switch takes SRCS manual actuator or SRCJ2 motor's actuator to realize the single pole operation and also tri-pole linkage.

This product has been verified by the Chinese competent authority as having uniqueness in design and reaching international advanced level of similar products.

GW7B Switch Disconnector comprises three single poles and actuator. Each single pole is made of a base, post insulator and conductive part. Three insulating posts are installed onto a long base, with two static contacts mounted at both ends to fix the top of the insulating post, and the conductive knife switch mounted onto the top of the rotating insulating post in between.

The actuator drives the rotating post in the middle to bring the conductive knife switch circumgyrate to open or close the breaker by contacting or detaching the static contacts fixed on the both ends of the post, Two horizontal insulating open breaks in series will appear at the closing moment.

In the opening and closing process, the conductive knife switch will horizontally swing and auto-rotate, with the aid of the turnover mechanism, to reduce the operating force and impact that occur in the opening and closing process and to improve the contact’s ability self-cleaning.

Main characteristic

  • The Switch Disconnector is of the turnover-type, and the conductive tube will move in two steps. At the closing moment, the conductive tube will rotate by some 70" on the horizontal surface, When the contacts at both ends are blocked up after having been placed in the static contact base, the turnover mechanism will drive the conductive tube to auto-rotate by about 45° when the movable contact will be in reliable contact with the touch finger. This process requires small operating force, thus causing no impacts on the insulators fixed at both ends. The main contact has the self-cleaning ability.

  • One end of the U-shaped finger within the static contact is fixed onto the contact base, forming a fixed connection and ensuring the reliable conduction; while the other end will produce contact pressure on the movable contact as a result of the influence of external spring and the own elastic force of the contact finger, and the gripping force will automatically increase when the short-circuit current passes through the contact. The contact spring is made of stainless steel and is equipped with insulating gasket, The spring will not corrupt nor shunt.

  • Provide one-key sequential control "double confirmation" function expansion.

  • The rotating parts of the disconnect switch are designed to be free of maintenance. The rotating base is designed into a closure structure which denies the access of moisture, dust and harmful gases so that the low-temperature lubricating cream within the bearing will not run off or harden.

  • 363kV and above earthing switch is in the single-arm standing and openable structure, with the structurally simple plug-type contact, The conductive rod for grounding will move in twosteps at the moments of opening and closing. At the moment of closing, the conductive rod will rotate vertically and rise up lo the fixed contact, and then automatically plug itself into the star-shaped contact, By doing so, the contact will be made reliable and be able to sustain the heavy short-circuit current.

Main technical parameters

Among these voltage levels 225kV/230kV/330kV/345kV Disconnect Switch, the rated short-circuit breaking current is 63kA, and customization is available.

NO

Specifications

Unit

Value

1

Product model

kV

DS7B - 72.5D

DS7B -145D

DS7B- 252D

DS7B - 363D

DS7B-420D

DS7B-550D

DS7B-800D

2

Rated voltage

kV

72.5

145

252

363

420

550

800

3

1min power frequency withstand voltage (r.m.s)

Phase to phase to earth

kV

204.8

380

588.8

510

520

740

960

Across isolating distance

kV

256

444

588.8 (+185.6)

510 (+210)

610

740 (+318)

960 (+462)

4

Lightning impulse withstand voltage (peak 1.2/50μs)

Phase to phase to earth

kV

448

870

1050

1175

1425

1675

2100

Across isolating distance

kV

524.8

1043

1050 (+200)

1175 (+295)

1425 (+240)

1675 (+450)

2100 (+650)

5

Rated frequency

HZ

50/60

50/60

50/60

50/60

50/60

50/60

60

6

Rated current

A

1250/2000/2500/3150/4000

1250/2000

2000/2500/3150/4000/5000

3150/5000

3150

3150

5000

7

Rated short - time withstand current (r.m.s)

kA

40/50

31.5/40

50/63

63

63

63

63

8

Ratedpeak withstand current

kA

100/125

80/100

125/160

160

160

160

160

9

Rated short - circuit withstand time

S

4

4

3

3

2

2

3

10

Wiring terminal static mechanical load

Longitudinal

N

750/1000

1250

1500

2500

2000

3000

3000

Horizontal

N

500/750

750

1000

2000

660

2000

2000

Vertical

N

750

1000

1250

1500

1500

2000

2000

11

Creepage distances

mm

1813, 2248

3625, 4495

6300, 7812

9450

10500

17050

20000

12

Mechanical life

Times

10k

13

Motor operating mechanism

Model

CJ2

SRCJ2

SRCJ

14

Motor voltage

V

AC380/DC220

15

Control circuit's voltage

V

AC220/DC220/DC110

16

Opening/closing time

S

7±1

16±1

24±2

17

Manual operating mechanism

Model

SRCS

SRCS


18

Electromagnetic lock's voltage

V

AC220

AC220/DC220/DC110


 

Order notice 

Product model, rated voltage, rated current, rated short-time withstand current, creepage distance and method of combination must be specified at the goods ordering time;

The methods of attaching earthing switches to Switch Disconnectores (left, right and both left and right);

Note: the way to judge the method of grounding: when one faces the name plate, the left grounding will be confirmed if the earthing switch is at the left hand side, and right grounding if at the right hand side;

The actuator's model and name, motor's voltage, control voltage and the number of contacts for auxiliary switch;

Current transformers are ordered by purchasers; however, it must be ensured that fixed contacts can be mounted onto such transformers:

When the Switch Disconnector is used at the incoming and outgoing terminals of the substation in the double loop parallel overhead power transmission line, if the earthing switch requires the opening/closing induction current, then such requirement shall be specified, Besides, the parameters and the side at which the earthing switch is set shall be defined. (Special notice: Not all earthing switches attached to the earthing switches and disconnect switches at the substation shall require the opening/closing induction current.)

 

FAQ
Q: What are the differences in mechanical life, operating time (motorized), and ingress protection (IP) rating among the 550kV disconnectors from Siemens, Hitachi, GE, and XD Group?
A:

 Smart Features and Digitalization

  • Siemens (3DN3-550): Integrates with SIPROTEC protection relays and offers a Digital Twin for advanced simulation and lifecycle management.

  • Hitachi Energy (DSSP-550): Features the APM-RM IoT module for remote condition monitoring and data analytics.

  • GE (PKG Gen3-550): Utilizes GridOS edge computing capabilities for localized grid intelligence and control.

  • XD Group (GW27-550): Offers an optional smart terminal as an add-on, providing a basic level of intelligence and monitoring.

Q: What are the uses of an isolating switch?
A:
 Isolating switches mainly serve the following purposes:
  • Isolating Voltage: During maintenance, isolate electrical equipment from the operating power grid to form a visible disconnection gap, ensuring the safety of operation and maintenance.
  • Switching Operation: Put standby busbars or bypass busbars into use, change the operation mode, and complete operations in coordination with circuit breakers; in dual-bus wiring, switch connecting elements between two busbars by controlling the on-off state of isolating switches on the two busbars.
  •  Closing and Opening Small-Current Circuits: Capable of closing and opening small inductive and capacitive currents, and can perform the following operations:

① Close and open voltage transformers and lightning arresters.

② Close and open no-load lines with a capacitive current not exceeding 5A (10kV, length within 5km; 35kV, length within 10km).

③ Close and open no-load transformers with an excitation current not exceeding 2A (35kV class less than 1000kVA, 110kV class less than 3200kVA).

  •  Automatic Quick Isolation: Under certain conditions, quickly isolate faulty equipment and lines to save the usage of circuit breakers.
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

Related Solutions

Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.