| Brand | Switchgear parts |
| Numero ng Modelo | DNRH8 Combined Switch sa Sistema ng Pagsimpan ng Enerhiya |
| Nararating na Voltase | DC 1500V |
| Narirating na kuryente | 250A |
| Serye | DNRH8 |
Ang DNRH8 Combined Switch ay isang all-in-one na solusyon para sa pag-switch ng DC load at paghihiwalay, na may rating hanggang 1500 VDC at 630 A. Ito ay disenyo upang matugunan ang mga kategorya ng paggamit na DC-PV1, DC-PV2, at DC-21B, na naglalaman ng pangunahing at pre-charge relays sa isang compact, IP67-rated na housing. Ideal para sa mga photovoltaic (PV) systems, battery energy storage systems (BESS), at industriyal na DC applications, ang DNRH8 ay nagpapadali ng pag-install, binabawasan ang mga error sa wiring, at nagbibigay ng mabilis at maasahan na pag-switch na may undervoltage protection.
Voltage & Current: DC 1500 V, operational current 200 A–630 A.
Switching Capacity: Making/withstand capacity 15 kA (0.1 s) / 10 kA (1 s); conditional short-circuit current 100 kA.
Arc Performance: Minimized na arc distance; arcing time < 3 ms.
Protection Rating: IP67 (external); IP20 (internal).
Control Modes: Manual o 24 V remote control na may auto/manual selection.
Undervoltage Module: Active/passive trip options (response < 0.5 s, 2 min power-loss backup).
Optional Relay Module: JDQMK series na naglalaman ng main/pre-charge relays at resistors.
Environmental Tolerance: –40 °C to +80 °C (derating above +60 °C); altitude up to 5000 m with derating.
Durability: > 10,000 mechanical cycles; 400–2000 electrical cycles.
| Parameter | Value |
| Rated Operational Voltage (VDC) | 1500 V |
| Rated Operational Current (A) | 200, 225, 250, 275, 325, 400, 500, 630 |
| Rated Insulation Voltage (Ui) | 1500 V |
| Making Capacity (Icm) | 15 kA |
| Withstand Capacity (Icw) | 15 kA @0.1 s / 10 kA @1 s |
| Conditional ShortCircuit Current (Iq) | 100 kA |
| Electrical Lifespan (cycles) | 400–2000 |
| Mechanical Lifespan (cycles) | > 10 000 |
| Control Method | Manual / Remote (24 V) |
| Ambient Temperature | –40 °C to +80 °C (derate >60 °C) |
| Humidity | ≤ 50% @40 °C; ≤ 90% @20 °C |
| Altitude | ≤ 2000 m (derate to 5000 m) |
| Pollution Degree | III |
| Installation Category | IV (power), III (control) |
| Ingress Protection | IP20 (internal) / IP67 (external) |
| Optional Functions | Undervoltage Module, Relay Module |