| Branda | Switchgear parts |
| Uimhir Módel | DNRH8 Comhdáilte Switch i Sísteam Stórála Fuinnimh |
| Voltáil réamhsraithe | DC 1500V |
| Cúr amach ar a dtugtar an-réiteach | 630A |
| Sraith | DNRH8 |
Is é an DNRH8 Combined Switch ná réiteach aon-chorpach ar son scuabadh carraigeacha DC agus díolaim, cuireadh ráta air go dtí 1500 VDC agus 630 A. Tá sé deartha chun catagóirí úsáide DC-PV1, DC-PV2, agus DC-21B a shásamh, ag comhbhaint reláidí príomha agus roinnt-lánú le chéile i gcothromán teorainneach amháin, agus tá sé meastar IP67. Is íobartach é don DNRH8 do chórais fotovoltaice (PV), córais stórála fuinnimh bataí (BESS), agus feidhmchláir DC tionscail, ag éascú suíomhú, ag laghdú ar earráid scuabadh, agus ag soláthar scuabadh sciobtha, iontaofa le cosaint uafriochvoltage.
Voltage & Current: DC 1500 V, operational current 200 A–630 A.
Switching Capacity: Making/withstand capacity 15 kA (0.1 s) / 10 kA (1 s); conditional short-circuit current 100 kA.
Arc Performance: Arc distance minimized; arcing time < 3 ms.
Protection Rating: IP67 (external); IP20 (internal).
Control Modes: Manual or 24 V remote control with auto/manual selection.
Undervoltage Module: Active/passive trip options (response < 0.5 s, 2 min power-loss backup).
Optional Relay Module: JDQMK series integrates main/pre-charge relays and resistors.
Environmental Tolerance: –40 °C to +80 °C (derating above +60 °C); altitude up to 5000 m with derating.
Durability: > 10,000 mechanical cycles; 400–2000 electrical cycles.
| Parameter | Value |
| Rated Operational Voltage (VDC) | 1500 V |
| Rated Operational Current (A) | 200, 225, 250, 275, 325, 400, 500, 630 |
| Rated Insulation Voltage (Ui) | 1500 V |
| Making Capacity (Icm) | 15 kA |
| Withstand Capacity (Icw) | 15 kA @0.1 s / 10 kA @1 s |
| Conditional ShortCircuit Current (Iq) | 100 kA |
| Electrical Lifespan (cycles) | 400–2000 |
| Mechanical Lifespan (cycles) | > 10 000 |
| Control Method | Manual / Remote (24 V) |
| Ambient Temperature | –40 °C to +80 °C (derate >60 °C) |
| Humidity | ≤ 50% @40 °C; ≤ 90% @20 °C |
| Altitude | ≤ 2000 m (derate to 5000 m) |
| Pollution Degree | III |
| Installation Category | IV (power), III (control) |
| Ingress Protection | IP20 (internal) / IP67 (external) |
| Optional Functions | Undervoltage Module, Relay Module |