| Brand | RW Energy | 
| Model NO. | DC Short-Circuit Current Limiter | 
| Rated voltage | 15kV | 
| Rated normal current | 1250A | 
| Rated frequency | 50/60Hz | 
| Series | DDX1-DC | 
The DC Short-Circuit Current Limiter shares the same fast-acting mode and interruption principle as the DDX1 AC product: it limits and interrupts the short-circuit current before the instantaneous value of the short-circuit current rises to the expected peak. The maximum instantaneous value of the actual short-circuit current is much lower than the peak value of the first major half-cycle of the short-circuit current, providing an economical and reasonable short-circuit current solution for DC users in power systems.
Its differences from the AC product lie in three aspects: (1) Sensor; (2) Electronic controller; (3) Fuse.
Main technical parameters
serial number  |  
   Parameter Name  |  
   unit  |  
   Technical parameters  |  
  |
1  |  
   Rated voltage  |  
   kV  |  
   12-40.5  |  
  |
2  |  
   Rated current  |  
   A  |  
   630-6300  |  
  |
3  |  
   Rated expected short-circuit breaking current  |  
   kA  |  
   50-200  |  
  |
4  |  
   Current limit coefficient = cut-off current / expected short-circuit current peak  |  
   %  |  
   15~50  |  
  |
5  |  
   Insulation level  |  
   Power frequency withstand pressure  |  
   kV/1min  |  
   42-95  |  
  
Lightning impact withstand pressure  |  
   kV  |  
   75-185  |  
  ||
Product Usage
Protection of DC transmission and distribution systems
Fast protection of DC system cables, power electronics