Failure Analysis and Design Optimization of Conventional Grounding Transformers

Felix Spark
Felix Spark
Field: Failure and maintenance
China

I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)

The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law, winding conductors are subjected to radial (inward compression) and axial (tensile/compressive) electrodynamic forces in a strong magnetic field. If the electrodynamic force exceeds the mechanical strength limit of the winding structure (conductors, spacers, press plates, binding systems), it will cause irreversible deformation, displacement, or distortion of the windings, eventually manifesting as winding end collapse—a typical failure mode of transformer-type equipment under short-circuit faults.

II. Associated Fault Triggers: Resonant Overvoltage and Energization with Residual Faults (Complying with Overvoltage Protection Standards such as DL/T 620 / IEC 60099)

  • System Resonant Overvoltage (Ferroresonance / Linear Resonance)
    Improper matching of system parameters (line capacitance, PT inductance, arc suppression coil inductance, etc.) can trigger ferroresonance or linear resonance, generating persistent overvoltage. This overvoltage repeatedly acts on insulation weak points (aged insulators, arresters, bushings, etc.), leading to intermittent arc grounding or repeated breakdowns, causing the grounding transformer to withstand high-frequency impact currents. This not only directly produces electrodynamic impacts but also accelerates the thermal and electrical aging of winding insulation (inter-turn, inter-layer, and main insulation), significantly reducing its dielectric strength and mechanical strength, making it more prone to collapse under subsequent impacts or normal operation.

  • Energization with Persistent Faults after Lightning Strike
    After a lightning strike causes a permanent grounding fault in the line, if the fault point is not isolated (e.g., the circuit breaker does not trip or fault indication is unclear), maintenance personnel mistakenly restore power (energization with faults), forcing the grounding transformer to continuously pass power-frequency fault current (far exceeding the design limit). Sustained overcurrent triggers the I²Rt Joule heating effect, causing the winding temperature to rise sharply beyond the insulation tolerance limit (e.g., 105°C for Class A), rapidly leading to thermal aging, carbonization, and loss of insulation performance, eventually resulting in winding short-circuit and burnout (thermal collapse). This condition causes devastating damage to the equipment.

III. Optimization Scheme: Enhancing Equipment Tolerance and Perfecting Protection Strategies (Integrating Equipment Selection, Relay Protection, and Condition Monitoring Standards)

  • Improving Equipment Body Short-Circuit Resistance (Complying with GB/T 1094.5 / IEC 60076-5)

    • Selection Requirements: Prioritize high short-circuit resistance models verified by strict short-circuit withstand tests (e.g., IEC 60076-5) for subsequent purchases, focusing on winding structure design (reinforced press plates, axial clamping systems, radial support structures, transposition conductor processes), material strength, and manufacturing processes.

    • Optional Series Current-Limiting Reactor: Install a current-limiting reactor in the neutral circuit of the grounding transformer to effectively suppress the amplitude and rise rate of fault currents, reducing electrodynamic impacts on windings. The impact on the system grounding mode and relay protection must be verified simultaneously.

  • Optimizing Relay Protection Configuration and Setting (Complying with Relay Protection Standards DL/T 584 / DL/T 559)

    • Setting Principle: The overcurrent protection settings (zero-sequence overcurrent, inverse-time overcurrent) of the grounding transformer must be strictly lower than the equipment's thermal and dynamic stability limits (calculated per GB/T 1094.5).

    • Gradation Coordination: The protection time delay of the grounding transformer (e.g., 100A/10s) must reliably coordinate with the upstream line protection (outgoing circuit breaker). Ensure that the line protection (zero-sequence Stage I: 0.2s, Stage II: 0.7s) can quickly clear grounding faults on the line, preventing the grounding transformer from enduring unnecessary stress. The grounding transformer protection, as a close backup, should have an operation time delay greater than the longest time delay of the line protection (including the gradation Δt).

    • Optimization of Grounding Transformer Body Protection Settings:

  • Strengthening Fault Fast-Clearing Capability (Complying with DL/T 584 / DL/T 559)

    • Directional Zero-Sequence Protection Configuration: Deploy and reliably activate directional zero-sequence current protection (Stage I/II) in line protection. The direction element accurately distinguishes between faulted and non-faulted lines, ensuring that the faulted line circuit breaker trips reliably within ≤0.2s during single-phase grounding faults, completely isolating the fault source—this is the core protection measure to prevent grounding transformer damage.

  • Deploying Intelligent On-Line Monitoring and Early Warning Systems (Complying with Condition Monitoring Standard DL/T 1709.1)

    • Real-Time Winding Hot Spot Temperature Monitoring: Install optical fiber or platinum resistance temperature sensors at key positions of the high-voltage winding ends to achieve real-time monitoring with ±1~2℃ accuracy. Set multi-level alarms (warning/alert) and tripping thresholds (calculated based on insulation class thermal models), automatically triggering protection actions when limits are exceeded to prevent thermal collapse.

    • Neutral Point Electrical Parameter Monitoring and Asymmetry Alarm: Continuously monitor neutral point current and system displacement voltage (zero-sequence voltage), and configure asymmetry over-limit alarm functions. When persistent/frequent abnormal neutral point electrical parameters are detected (indicating intermittent grounding, resonance, or insulation degradation), issue immediate warnings for early fault intervention.

Optimization Conclusions and Implementation Recommendations

  • Conclusion Summary

    • Equipment Strengthening: Select high short-circuit resistance equipment or install current-limiting reactors to enhance electrodynamic tolerance.

    • Protection Coordination: Precisely set protection values (≤equipment tolerance limits) and ensure gradation coordination with directional zero-sequence protection (Stage I ≤0.2s).

    • Condition Early Warning: Deploy high-precision temperature monitoring (±1~2℃) and neutral point electrical parameter alarm systems for early fault protection.

    • The direct cause of the accident is that the electrodynamic force generated by the single-phase grounding fault current exceeds the mechanical strength limit of the windings.

    • Deep-level triggers include: ① Intermittent impacts caused by system resonant overvoltage accelerating insulation aging; ② Thermal collapse due to energization with permanent faults after lightning strikes.

    • Systematic optimization should focus on three aspects:

  • Implementation Recommendations

    • Immediate implementation of protection setting adjustments, directional protection activation, and monitoring system installation.

    • Plan equipment body upgrades in conjunction with service life cycles and technical transformation schedules.

    • Incorporate this scheme into operation regulations and anti-accident measures, strictly prohibiting energization with grounding faults, and thoroughly investigating fault points before restoring power after lightning strikes.

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.