Why Can't VT Be Shorted & CT Be Opened? Explained

Echo
Field: Transformer Analysis
China

We all know that a voltage transformer (VT) must never operate short-circuited, while a current transformer (CT) must never operate open-circuited. Short-circuiting a VT or opening the circuit of a CT will damage the transformer or create hazardous conditions.

From a theoretical standpoint, both VTs and CTs are transformers; the difference lies in the parameters they are designed to measure. So why, despite being fundamentally the same type of device, is one prohibited from short-circuit operation while the other cannot be open-circuited?

VT.jpg

Under normal operation, a VT’s secondary winding operates in a near-open-circuit condition with a very high load impedance (ZL). If the secondary circuit shorts, ZL drops nearly to zero, causing a massive short-circuit current to flow. This can destroy secondary equipment and pose serious safety risks. To protect against this, a VT can have fuses installed on its secondary side to prevent damage from a short. Where possible, fuses should also be installed on the primary side to protect the high-voltage system from faults in the VT’s high-voltage winding or connections.

In contrast, a CT operates with a very low impedance (ZL) on the secondary side, effectively in a short-circuit state during normal operation. The magnetic flux generated by the secondary current opposes and cancels the flux from the primary current, resulting in a very small net excitation current and minimal core flux. Thus, the induced electromotive force (EMF) in the secondary winding is typically only a few dozen volts. 

However, if the secondary circuit opens, the secondary current drops to zero, eliminating this demagnetizing effect. The primary current, unchanged (since ε1 remains constant), becomes entirely excitation current, causing a dramatic increase in core flux Φ. The core quickly saturates. Given that the secondary winding has many turns, this results in a very high voltage (possibly reaching several thousand volts) across the open secondary terminals. This can break down insulation and poses a severe risk to personnel. Therefore, an open secondary circuit on a CT is absolutely prohibited.

Both VTs and CTs are transformers in principle—VTs are designed to transform voltage, while CTs transform current. So why can a CT not be open-circuited while a VT cannot be short-circuited?

In normal operation, the induced EMFs ε1 and ε2 remain essentially constant. A VT is connected in parallel with the circuit, operating at high voltage and very low current. The secondary current is also extremely small, nearly zero, forming a balanced condition with the near-infinite impedance of an open circuit. If the secondary is shorted, ε2 remains constant, forcing the secondary current to increase drastically, burning out the secondary winding.

Similarly, for a CT connected in series with the circuit, it operates at high current and very low voltage. The secondary voltage is nearly zero under normal conditions, forming a balanced state with a near-zero impedance (short-circuit). If the secondary circuit opens, the secondary current collapses to zero, and the entire primary current becomes excitation current. This causes a rapid surge in magnetic flux, driving the core into deep saturation and potentially destroying the transformer.

Thus, although both are transformers, their different applications lead to completely different operational constraints.

Give a tip and encourage the author!
Topics:
CT
VT

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Chinese Gas-Insulated Switchgear Enables Commissioning of Longdong-Shandong ±800kV UHV DC Transmission Project
On May 7, China's first large-scale integrated wind-solar-thermal-storage comprehensive energy base UHV transmission project—the Longdong~Shandong ±800kV UHV DC transmission project—was officially energized and put into operation. The project has an annual transmission capacity exceeding 36 billion kilowatt-hours, with new energy sources accounting for more than 50% of the total. After commissioning, it will reduce carbon dioxide emissions by approximately 14.9 million tons annually, contributin
12/13/2025
Functions and Specific Wiring Method of the Grounding Disconnect Switch for Pad-Mounted Transformers
The grounding disconnect switch of a pad-mounted transformer is a switching device used to isolate the pad-mounted transformer from the grounding cable. It is an essential component of pad-mounted transformer equipment and plays a critical role in protecting the safety of the transformer equipment. The grounding disconnect switch of a pad-mounted transformer serves important functions in grounding down leads, grounding switching, auxiliary grounding, and lightning protection.Its functions includ
12/04/2025
Installation Requirements and Procedures for 10 kV High-Voltage Disconnect Switches
First, the installation of 10 kV high-voltage disconnect switches must meet the following requirements. The first step is to select an appropriate installation location, typically near the switchgear power supply in the power system to facilitate operation and maintenance. At the same time, sufficient space must be ensured at the installation site to accommodate equipment placement and wiring.Secondly, equipment safety must be fully considered—for example, lightning protection and explosion-proo
11/20/2025
Send inquiry
+86
Click to upload file

IEE Business will not sell or share your personal information.

Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.