Dielectric Withstand Capability of AC Vacuum Contactors and Countermeasures

Felix Spark
Field: Failure and maintenance
China

During operation, AC vacuum contactors are often subjected to various overvoltages such as lightning overvoltage and switching overvoltage. Therefore, AC vacuum contactors must have a certain voltage withstand capacity.

An AC vacuum contactor is composed of a vacuum interrupter (its structure is shown in Figure 1), a housing, an electromagnetic system, a secondary circuit, and other components. Among these, the vacuum interrupter is the "heart" of the AC vacuum contactor, and its performance directly affects the voltage withstand capacity of the AC vacuum contactor.

Figure 1 Structure of vacuum interrupter.jpg

1. Influencing Factors and Hazards

After the design and manufacture of a vacuum interrupter are completed, the gap d between its moving and static contacts remains unchanged. Therefore, the magnitude of the gap breakdown voltage mainly depends on the pressure p, that is, the vacuum degree of the vacuum interrupter. When the vacuum degree is relatively high, the relative density of electrons is very low, and of course, the number of charged particles is also small. The discharge capacity of the gas is very weak, so the breakdown voltage is large, and the voltage withstand capacity of the vacuum interrupter is strong. Therefore, theoretically, the higher the vacuum degree, the lower the pressure, the higher the dielectric strength of the contact gap, the higher the breakdown voltage, the stronger the voltage withstand capacity of the vacuum interrupter, and at this time, the leakage current is smaller.

The factors affecting the voltage withstand capacity of the vacuum interrupter, in addition to the charged particles existing in the contact gap (the vacuum degree plays a major role), are also related to the outer shell of the vacuum interrupter. As shown in Figure 1, the outer shell of the vacuum interrupter is made of ceramic or glass. Since ceramic and glass are both hydrophilic insulating materials, they have a strong ability to absorb water, and water absorbs impurities. Under the action of an applied voltage, these impurities are easily ionized into charged particles and cause surface discharge, reducing the voltage withstand capacity of the vacuum interrupter. At this time, the insulation strength of the shell decreases, and the leakage current increases.

Under the action of an applied voltage, the main contact gap of the vacuum interrupter and the outer shell of the vacuum interrupter form a parallel circuit. If the surface discharge of the vacuum interrupter develops into a flashover, it indicates that the vacuum interrupter breaks down along the surface of the shell, seriously affecting the insulation performance of the vacuum interrupter. In addition, for the AC vacuum contactor, the quality of the outer shell is also a factor affecting its voltage withstand capacity.

2. Improvement Measures

Since the voltage withstand capacity of the AC vacuum contactor mainly depends on the vacuum interrupter, and the factors affecting the voltage withstand capacity of the vacuum interrupter include the inside of the interrupter and the outer shell, measures should be taken from these two aspects for improvement.

First, from the perspective of the inside of the vacuum interrupter, attention should be paid to the following aspects:

Improve the physical structure of the contacts to make the electric field of the vacuum interrupter as uniform as possible. When the contact gap of the vacuum interrupter is determined, improving the distribution of the electric field in the interrupter to make it more uniform helps to improve the voltage withstand capacity of the vacuum interrupter and reduce the leakage current.

In practice, first, the thickness of the contacts should be appropriately increased, and the sharp corners and edges of the contacts should be blunted, so that the electric field distribution at these parts is not too concentrated, thereby helping to improve the voltage withstand capacity of the vacuum interrupter. In addition, for high-voltage and large-capacity vacuum interrupters, a voltage-equalizing shield should also be designed around the contacts, and an auxiliary voltage-equalizing shield should be designed at the end of the voltage-equalizing shield to effectively improve the electric field distribution near the contacts. Designing end shields near the end caps at both ends of the vacuum interrupter can effectively reduce the electric field intensity near the end caps of the vacuum interrupter.

Improve the vacuum degree. The vacuum degree is an important parameter reflecting the quality of the vacuum interrupter. The vacuum degree of a qualified vacuum interrupter has a range, between 10^-4~ 10^-2 Pa, that is, 10^-6~10^-4 mmHg As shown in Figure 2, when the pressure of the vacuum interrupter is greater than 10^-2 Pa, its voltage withstand capacity decreases rapidly.

Relationship Between Withstand Voltage and Gas Pressure in Vacuum Interruption Chambers.jpg

The contact surface should be smooth and flat. If necessary, burrs on the contact surface should be removed through conditioning.

Improve the coaxiality. The guide sleeve can effectively ensure the coaxiality of the vacuum interrupter, but sometimes the coaxiality is still not in the best state and needs to be carefully adjusted. The improvement of coaxiality ensures the effective contact of the moving and static contacts, which can reduce the contact resistance, reduce the heat generated when the contacts are closed, and effectively reduce the surface damage caused by fusion welding when the contacts are opened.

Second, from the perspective of the outer shell of the vacuum interrupter, attention should be paid to the following aspects:

  • Increase the creepage distance. Especially in the case of product miniaturization, this goal can be effectively achieved by designing the outer shell into a corrugated shape.

  • Maintain the cleanliness of the outer shell and pay attention to the use environment. Especially for vacuum switches used outdoors in polluted and humid environments, measures should be taken to keep the outer shell clean.

  • For high-voltage and large-capacity vacuum interrupters, adding silicone grease insulation between the outer surface of the vacuum interrupter and the insulating porcelain sleeve can effectively improve the insulation strength of the outer surface of the vacuum interrupter. In addition, materials with high insulation strength must be selected to improve the voltage withstand capacity of the outer shell of the AC vacuum contactor.

3. Conclusion

By improving the internal insulation of the vacuum interrupter and reducing the surface conductivity of the outer shell of the vacuum interrupter, and improving the voltage withstand capacity of the outer shell of the AC vacuum contactor, the voltage withstand capacity of the AC vacuum contactor can be greatly improved, and the product quality can be enhanced.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
High-Voltage DC Contactor Wiring Essentials: Polarity Requirements and Safety Guidelines
High-Voltage DC Contactors Usually Have Polarity DistinctionsThis is especially true in application scenarios with high current and high voltage.Why Polarity Distinctions ExistArc CharacteristicsDC current has no zero-crossing point, making arc extinction more difficult than that of AC. Polarity (current direction) may affect the stretching and extinguishing effect of the arc.Internal Structural DesignSome contactors optimize arc-extinguishing devices (such as magnetic blowout coils and permanen
Echo
09/09/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.