Master the internal structure of Zinc Oxide Arresters (MOA) and critical electrical tests including DC reference voltage and leakage current for power systems.
The surge arrester serves as the primary line of defense against overvoltage in power systems. Its operational status directly determines the insulation safety of major equipment such as transformers, motors, and switchgear. Zinc Oxide Arresters (MOA), with their superior non-linear voltage-current characteristics, have become the most widely used protective devices in modern grids. Deeply understanding their internal configuration and performing scientific preventive tests are essential to identifying hidden defects like valve aging or seal failure, ensuring long-term grid stability.
2.2 Zinc Oxide Valve V-I Characteristic:
I=k⋅Uα
Description:
This relationship describes the non-linear current and voltage behavior of zinc oxide valves. II is the current flowing through the valve, UU is the applied voltage, and kk is a material constant. αα (the non-linearity coefficient) is the core performance metric; a higher value indicates a stronger voltage-clamping capability during overvoltage and lower power loss at continuous operating voltage.
Description:
The total current II in an arrester consists of a capacitive component and a resistive component IrIr. By measuring the phase angle ϕϕ, the resistive current representing valve energy consumption and aging status can be isolated. A significant increase in IrIr is a direct warning sign of moisture ingress or valve degradation.
Measured using a 2500 V or 5000 V insulation resistance meter. For arresters rated 35 kV and below, the insulation resistance should typically not be less than 1000 MΩΩ. For 110 kV and above, it should not be less than 2500 MΩΩ.
Description:
This value is the most critical preventive test item. It measures the DC voltage required to cause a 1 mA current flow through the arrester. The measured value should be compared with the factory test report; a deviation exceeding ±5%±5% indicates potential valve degradation or uneven potential distribution.
Description:
Measurement of leakage current at 0.75 times the DC reference voltage. Typically, the current should not exceed 50 μμA. A significantly higher value indicates moisture ingress due to seal failure or severe surface contamination.
| Test Item | Pass Standard (110 kV MOA) | Typical Failure Manifestation | Diagnostic Recommendation |
|---|---|---|---|
| Insulation Resistance | ≥2500≥2500 MΩΩ | Drops exponentially to 500 MΩΩ | Internal moisture or external flashover |
| U1 mAU1 mA Voltage | ≥145≥145 kV (Ref. value) | Decrease exceeds 5%5% | Valve aging or material degradation |
| 75% U1 mAU1 mA Current | ≤50≤50 μμA | Increases beyond 200 μμA | Seal failure, moisture ingress |