• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the key considerations for photovoltaic transformer selection?

Echo
Echo
Field: Transformer Analysis
China

Sizing Principles and Technical Parameters of Photovoltaic Transformers

Sizing photovoltaic transformers requires a comprehensive consideration of multiple factors, including capacity matching, voltage ratio selection, short - circuit impedance setting, insulation class determination, and thermal design optimization.  The key sizing principles are as follows:

(I) Capacity Matching: Fundamental for Load Bearing

Capacity matching is the core prerequisite in sizing photovoltaic transformers. It requires accurately matching the transformer capacity to the installed capacity of the photovoltaic system and the expected maximum output power, ensuring stable operation under the intended load. The capacity calculation formula is:

where U2 represents the secondary - side voltage of the transformer (typically 400V). Considering the inherent variability of photovoltaic systems (e.g., fluctuations in sunlight and load changes), the calculation must incorporate a safety margin (1.1–1.2 times), load - rate fluctuation coefficient (e.g., KT = 1.05, and power factor (usually 0.95).

Example: For a photovoltaic system with a peak power output of 500kW, a 630kVA, 800V/400V transformer can be selected to adapt to different sunlight and load conditions. Additionally, in accordance with the Technical Guidelines for Distributed Photovoltaic Grid Connection, the capacity of a single distributed photovoltaic power station should not exceed 25% of the maximum load in the power supply area of the upper - level transformer, to avoid grid impacts.

(II) Voltage Ratio Selection: Adapting to Fluctuations and Voltage Regulation

The voltage ratio must align with the output characteristics of the photovoltaic system (inverter voltage typically fluctuates by ±5%) and grid connection requirements, featuring dynamic adjustment capabilities. There are two main adjustment methods:

  • Tap - changer adjustment: Applicable to off - load tap - changing transformers, usually with three ±5% taps (e.g., 10.5kV/10kV/9.5kV), requiring a power - off operation.

  • Automatic voltage regulation module adjustment: Applicable to on - load tap - changing transformers, enabling online dynamic adjustment with a response time ≤200ms.

In actual operation, appropriate taps should be selected based on load characteristics: 5% tap for light loads, and 2.5% or 0% taps for heavy loads, balancing voltage rise during high photovoltaic generation and voltage drop during nighttime peak loads.

(III) Short - Circuit Impedance Setting: Balancing Protection and Stability

Short - circuit impedance should be designed according to the system's short - circuit current level and transformer type (oil - immersed/dry - type), with the calculation formula:

Oil - immersed: 4%–8%; dry - type: 6%–12%. For large transformers (e.g., 9150kVA), increase impedance ( Zk ≥ 20% ). Do temperature correction (75°C for oil - immersed, 120°C for dry - type).

(IV) Insulation Class

Fit outdoor environments. Prefer Class F (155°C) or H (180°C). Use H - class for deserts, salt - spray - resistant materials for coasts, moisture - resistant for high humidity. Consider thermal aging: +6°C doubles aging; - 6°C halves it.

(V) Thermal Design

Optimize by environment. Cooling methods: natural/forced air cooling, oil - immersed self - cooling. For high - temp areas: forced air or hybrid; high - humidity: dry - type + axial ducts; high - dust: IP54 + filters. A desert station uses micro - channel liquid cooling (7:3 deionized water + ethylene glycol) for 3× efficiency.

V. Sizing & Inspection for Different Scenarios

Solutions for typical scenarios:

(I) Grid - Connected

Sizing: Cover inverter/auxiliary power + 1.15× margin (e.g., 1092.5kVA). Match ±5% voltage, 4%–8% impedance, ≥Class F, natural/oil - air cooling. Inspection: Check insulation,THD ≤ 5%, voltage regulation (±2.5%), impedance (±2% of factory value).

(II) Off - Grid

Sizing: 1.2–1.5× load power. Adapt to inverter (e.g., 800V/400V), 6%–12% impedance, ≤200ms voltage regulation, 400V + 220V windings.
 Inspection: Test overload (≥120%), voltage regulation response, voltage balance, and system fluctuations.

(III) High - Temperature

Sizing: Dry - type + forced air or oil - immersed + naphthenic oil. Use high - temp insulation, IP55, 80°C - start/60°C - stop fans. Inspection: Quarterly thermography, semi - annual oil tests, check cooling, monitor winding temp.

(IV) High - Humidity/Coastal

Sizing: IP65 epoxy dry - type, 316L + fluorocarbon coating, salt - resistant insulation, increased spacing. Inspection: Check coating, oil moisture/gases, salt - spray test (≤5% power drop), monitor hydrogen.

(V) High - Dust

Sizing: Fully sealed, IP54, three - stage filters, enlarged cooling area, wear - resistant windings. Inspection: Replace filters quarterly, thermography, check dust - proofing, clean regularly.

(VI) Electromagnetic Interference

Sizing: Sandwich windings (≤500pF), LC filters ( THD ≤ 4% ), meet EMC (GB/T 21419 - 2013), dual - redundant comms. Inspection: Annual EMC tests, monitor harmonics/unbalance, check grounding (≤0.5Ω), test bit error 10-8.

(VII) PV - Energy Storage Integration

Sizing: Integrate PCS (Modbus RTU), 400V + 220V windings, ≤200ms reactive compensation, consider combined loads. Inspection: Verify PCS compatibility, voltage balance (≤1%), test voltage regulation (≤±2%), check storage connections.

Summary: Accurate matching of capacity, voltage, impedance, insulation, and thermal design, plus thorough inspection, ensures safe, efficient, and long - life operation, aligning with distributed PV development under carbon goals.

Give a tip and encourage the author!
Recommended
How to Design 10kV Overhead Line Poles
How to Design 10kV Overhead Line Poles
This article combines practical examples to refine the selection logic for 10kV steel tubular poles, discussing clear general rules, design procedures, and specific requirements for use in 10kV overhead line design and construction.Special conditions (such as long spans or heavy ice zones) require additional specialized verifications based on this foundation to ensure safe and reliable tower operation.General Rules for Overhead Transmission Line Tower SelectionThe rational selection of overhead
James
10/20/2025
How to select a dry-type transformer?
How to select a dry-type transformer?
1. Temperature Control SystemOne of the main causes of transformer failure is insulation damage, and the greatest threat to insulation comes from exceeding the allowable temperature limit of the windings. Therefore, monitoring temperature and implementing alarm systems for transformers in operation are essential. The following introduces the temperature control system using the TTC-300 as an example.1.1 Automatic Cooling FansA thermistor is pre-embedded at the hottest spot of the low-voltage win
James
10/18/2025
How to Choose the Right Transformer?
How to Choose the Right Transformer?
Transformer Selection and Configuration Standards1. Importance of Transformer Selection and ConfigurationTransformers play a critical role in power systems. They adjust voltage levels to suit different requirements, enabling electricity generated at power plants to be efficiently transmitted and distributed. Improper transformer selection or configuration can lead to serious issues. For example, if the capacity is too small, the transformer may not support the connected load, causing voltage dro
James
10/18/2025
How to Choose Vacuum Circuit Breakers Correctly?
How to Choose Vacuum Circuit Breakers Correctly?
01 PrefaceIn medium-voltage systems, circuit breakers are indispensable primary components. Vacuum circuit breakers dominate the domestic market. Therefore, correct electrical design is inseparable from the proper selection of vacuum circuit breakers. In this section, we will discuss how to correctly select vacuum circuit breakers and common misconceptions in their selection.02 Interrupting Capacity for Short-Circuit Current Need Not Be Excessively HighThe short-circuit interrupting capacity of
James
10/18/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.