Principles of Sizing and Technical Parameters of Photovoltaic Transformers

Sizing photovoltaic transformers requires a comprehensive consideration of multiple factors, including capacity matching, voltage ratio selection, short-circuit impedance setting, insulation class determination, and thermal design optimization. The key sizing principles are as follows:

(I) Capacity Matching: Fundamental for Load Bearing

Capacity matching is the core prerequisite in sizing photovoltaic transformers. It requires accurately matching the transformer capacity to the installed capacity of the photovoltaic system and the expected maximum output power, ensuring stable operation under the intended load. The capacity calculation formula is:

where U2 represents the secondary-side voltage of the transformer (typically 400V). Considering the inherent variability of photovoltaic systems (e.g., fluctuations in sunlight and load changes), the calculation must incorporate a safety margin (1.1–1.2 times), load-rate fluctuation coefficient (e.g., KT = 1.05, and power factor (usually 0.95).

Example: For a photovoltaic system with a peak power output of 500kW, a 630kVA, 800V/400V transformer can be selected to adapt to different sunlight and load conditions. Additionally, in accordance with the Technical Guidelines for Distributed Photovoltaic Grid Connection, the capacity of a single distributed photovoltaic power station should not exceed 25% of the maximum load in the power supply area of the upper-level transformer, to avoid grid impacts.

(II) Voltage Ratio Selection: Adapting to Fluctuations and Voltage Regulation

The voltage ratio must align with the output characteristics of the photovoltaic system (inverter voltage typically fluctuates by ±5%) and grid connection requirements, featuring dynamic adjustment capabilities. There are two main adjustment methods:

  • Tap-changer adjustment: Applicable to off-load tap-changing transformers, usually with three ±5% taps (e.g., 10.5kV/10kV/9.5kV), requiring a power-off operation.

  • Automatic voltage regulation module adjustment: Applicable to on-load tap-changing transformers, enabling online dynamic adjustment with a response time ≤200ms.

In actual operation, appropriate taps should be selected based on load characteristics: 5% tap for light loads, and 2.5% or 0% taps for heavy loads, balancing voltage rise during high photovoltaic generation and voltage drop during nighttime peak loads.

(III) Short-Circuit Impedance Setting: Balancing Protection and Stability

Short-circuit impedance should be designed according to the system's short-circuit current level and transformer type (oil-immersed/dry-type), with the calculation formula:

Oil-immersed: 4%–8%; dry-type: 6%–12%. For large transformers (e.g., 9150kVA), increase impedance ( Zk ≥ 20% ). Do temperature correction (75°C for oil-immersed, 120°C for dry-type).

(IV) Insulation Class

Fit outdoor environments. Prefer Class F (155°C) or H (180°C). Use H-class for deserts, salt-spray-resistant materials for coasts, moisture-resistant for high humidity. Consider thermal aging: +6°C doubles aging; -6°C halves it.

(V) Thermal Design

Optimize by environment. Cooling methods: natural/forced air cooling, oil-immersed self-cooling. For high-temp areas: forced air or hybrid; high-humidity: dry-type + axial ducts; high-dust: IP54 + filters. A desert station uses micro-channel liquid cooling (7:3 deionized water + ethylene glycol) for 3× efficiency.

V. Sizing & Inspection for Different Scenarios

Solutions for typical scenarios:

(I) Grid-Connected

Sizing: Cover inverter/auxiliary power + 1.15× margin (e.g., 1092.5kVA). Match ±5% voltage, 4%–8% impedance, ≥Class F, natural/oil-air cooling. Inspection: Check insulation, THD ≤ 5%, voltage regulation (±2.5%), impedance (±2% of factory value).

(II) Off-Grid

Sizing: 1.2–1.5× load power. Adapt to inverter (e.g., 800V/400V), 6%–12% impedance, ≤200ms voltage regulation, 400V + 220V windings.
 Inspection: Test overload (≥120%), voltage regulation response, voltage balance, and system fluctuations.

(III) High-Temperature

Sizing: Dry-type + forced air or oil-immersed + naphthenic oil. Use high-temp insulation, IP55, 80°C-start/60°C-stop fans. Inspection: Quarterly thermography, semi-annual oil tests, check cooling, monitor winding temp.

(IV) High-Humidity/Coastal

Sizing: IP65 epoxy dry-type, 316L + fluorocarbon coating, salt-resistant insulation, increased spacing. Inspection: Check coating, oil moisture/gases, salt-spray test (≤5% power drop), monitor hydrogen.

(V) High-Dust

Sizing: Fully sealed, IP54, three-stage filters, enlarged cooling area, wear-resistant windings. Inspection: Replace filters quarterly, thermography, check dust-proofing, clean regularly.

(VI) Electromagnetic Interference

Sizing: Sandwich windings (≤500pF), LC filters ( THD ≤ 4% ), meet EMC (GB/T 21419-2013), dual-redundant comms. Inspection: Annual EMC tests, monitor harmonics/unbalance, check grounding (≤0.5Ω), test bit error 10-8.

(VII) PV-Energy Storage Integration

Sizing: Integrate PCS (Modbus RTU), 400V + 220V windings, ≤200ms reactive compensation, consider combined loads. Inspection: Verify PCS compatibility, voltage balance (≤1%), test voltage regulation (≤±2%), check storage connections.

Summary: Accurate matching of capacity, voltage, impedance, insulation, and thermal design, plus thorough inspection, ensures safe, efficient, and long-life operation, aligning with distributed PV development under carbon goals.

Ba da kyau kuma kara mai rubutu!

Tambayar Da Yawanci

Ko da zaka iya kowa aiki na tashin mafi yawa?
1. Sistem Kontrol SuhuSatu dari penyebab utama kegagalan transformator adalah kerusakan isolasi, dan ancaman terbesar bagi isolasi berasal dari melebihi batas suhu yang diperbolehkan pada gulungan. Oleh karena itu, pemantauan suhu dan penerapan sistem alarm untuk transformator yang beroperasi sangat penting. Berikut ini memperkenalkan sistem kontrol suhu menggunakan TTC-300 sebagai contoh.1.1 Kipas Pendingin OtomatisTermistor dipasang di titik terpanas pada gulungan tegangan rendah untuk mendapa
10/18/2025
Daidaitaccen Masu Kudin Tausayi Da Duk Da Gaskiya?
Daidaitaccen Da Zabe da Kudin Transformer1. Muhammanci na Daidaitaccen Da Zabe da Kudin TransformerTransformers suna da muhimmanci sosai a cikin nufin kuliya. Suna tattara masu zabe don zaɓe da ma'aikata daban-daban, wanda ke jin kuliya da aka gina a cikin kuliyan suka shafi da kuma zama mai amfani. Idan ba a daidaita da zabe ko kudi transformer ba, yana iya haɗa da abubuwa mafi yawan. Misali, idan babbanar ta fiye, transformer ba za su iya taimaka da zabe da ke magance, wanda yake iya haɗa da t
10/18/2025
Gidagida Mai Kula da Hanyoyin Haɗa na Ƙarfin Dutsi na Iya Tafiya da Iya Tafiya Masu Yawan Kirkiro
Mai Tsawo da Muhimmiyar Kiyasin Aiki na Spring na Circuit Breakers na Kirkiro da Tsakiya?An fi sani kiyasin aiki na spring wajen circuit breakers na kirkiro da tsakiya. Yana amfani da zafi mai girma a cikin springs don bincike aiki na bukata da kudeta na breaker. An yi aiki na spring tare da motor mai shirye-shi. Idan an yi aiki na breaker, ana fitar da zafi a gaba don bincike aiki na abubuwa masu harka.Abubuwan Da Dama: Kiyasin aiki na spring yana amfani da zafi mai girma a cikin springs. Yana
10/18/2025
Zaɓe Da Duk: VCB na Gaba ko Kafin Cikin?
Matsayin Tashin Fixed-Type da Withdrawable (Draw-Out) Vacuum Circuit BreakersLittafi na bi tafi karatu masu karkashin fixed-type da withdrawable vacuum circuit breakers, zan kawo yadda aka gina su da yadda ake amfani da su a fannin, kuma za a nuna farkon kayan aiki a cikin amfani da su a wurin.1. Takaitaccen TakaitarDuka abu suna ne a binciken vacuum circuit breakers, suna da aiki mai mahimmanci wanda ke kusa hanyar vacuum interrupter don kafara jirgin kasa. Amma, farkon kayan aiki da hanyoyin a
10/17/2025
Aika tambaya
+86
Dauke kake saita fayil
Kwamfuta
Samun IEE Business Application
Yi amfani da IEE-Business app don samun abubuwan aikin, samun halayyin, haɗi da malamai, kuma kai tsauraran takaiddun kasoshin duka lokaci, duka wurin—dole bai karfin takamaltar hulɗin ku na alintakargida da kasuwanci.