Rockwill RCW vacuum recloser with AMF technology, 16kA/25 ops, intelligent FTU, IP67 protection for reliable 11-38kV grid automation.
The adoption of longitudinal magnetic field (AMF) technology in vacuum interrupters for reclosers represents one of the most advanced arc-quenching methods in modern vacuum switchgear. Its core principle is to generate a magnetic field parallel to the arc direction through the contact structure, forcing the arc to remain in a "diffuse state" without contraction under high currents.
This design offers the following significant advantages:
When interrupting large currents in vacuum, the arc tends to constrict into a highly concentrated column (the "arc constriction effect"), causing severe localized temperature rise on the contact surface. With the introduction of an axial magnetic field, charged particles move in spiral trajectories under the magnetic field, effectively limiting radial plasma diffusion and forcing the high-current arc to distribute uniformly across the entire contact surface (maintaining a diffuse state). This greatly increases the upper limit of short-circuit current that the vacuum interrupter can handle.
Since arc energy is evenly distributed over the entire contact surface, the severe localized melting and metal splashing caused by arc constriction in conventional designs are avoided. This results in minimal electrical wear on the contacts, significantly extending the electrical life of the vacuum interrupter. For reclosers that perform frequent "open-close-open" operations in the grid, this erosion resistance is particularly critical.

Physical Photos of Rockwill Outdoor Auto Circuit vacuum recloser
Under axial magnetic field control, the diffuse arc exhibits a very low and stable arc voltage (typically only a few tens of volts). A lower arc voltage means that the total energy (heat) released during the arcing period is greatly reduced, fundamentally lowering the thermal load inside the interrupter.
The core function of a recloser is "fast reclosing" to isolate transient faults, requiring instantaneous recovery of dielectric strength across the open contacts after current zero. With axial magnetic field technology, the low arc energy and absence of severe localized contact overheating ensure that metal vapor production ceases almost immediately after current zero. The residual metal vapor and plasma rapidly disperse and condense on the shield. Consequently, the dielectric recovery speed is exceptionally fast, perfectly meeting the high-speed reclosing demands of reclosers with minimal risk of restrike.

Schematic Diagram of RCW Series Magnetic Actuator and Add manual closing mechanism
Because the axial magnetic field significantly increases the interrupting capacity per unit contact area while reducing thermal load, contacts with smaller diameters and interrupters with smaller volumes can be used when designing switchgear of the same rating. This allows reclosers to be lighter and more compact, facilitating pole-mounted installation on utility poles.
Through the physical mechanism of "evenly distributing thermal load," axial magnetic field technology endows vacuum interrupters with large breaking current capacity, minimal electrical wear, extremely fast dielectric recovery, and compact dimensions — making it the critical technical foundation for reclosers to perform frequent and reliable fault isolation in distribution networks.
Rockwill Automatic Reclosers RCW Series — Pioneers in China's recloser industry, with a complete independent industrial chain from core R&D to mass production and delivery. Designed for 11kV–38kV power grids, they integrate axial magnetic field vacuum interruption (16kA/25 operations, mechanical life >10,000 operations), intelligent control (FTU/GOOSE/SCADA), and industrial-grade protection (IP67, -45°C to +70°C) — delivering reliable fault isolation solutions for distribution networks.
Edited From:Garca